Study guide
6.2 Temperature Coefficient of Resistance
City & Guilds 2365 Level 2 Diploma in Electrical Installations Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Qualification Overview
1.1 About the City & Guilds 2365 Level 2 Qualification 1.2 Study Strategy, Exam Technique & Resource Navigation
2 Health, Safety & Environmental Legislation, Risk Assessment & Permits
2.1 Statutory Framework & Health and Safety Law 2.2 Hazardous Substances, Incident Reporting & Welfare 2.3 Work Equipment, Manual Handling & PPE 2.4 Environmental Legislation, Pollution & Site Waste 2.5 Risk Assessments, Method Statements, Permits to Work & Safety Signs
3 Electrical Safety, Safe Isolation, Site Hazards & Emergencies
3.1 Safe Isolation Procedures & GS38 Compliance 3.2 Electrical Hazards & Electric Shock Physiology 3.3 Fire Safety, Site Supplies & Emergency Response 3.4 Accidents, First Aid, Emergency Procedures & Reporting
4 Working at Height & Access Equipment
4.1 Work at Height Regulations & Risk Management 4.2 Ladders, Stepladders & Podiums 4.3 Mobile Access Towers & Scaffolding Systems
5 Mathematical Principles, Units & Basic Mechanics
5.1 Mathematical Foundations & Transposition for Electricians 5.2 SI Units of Measurement in Electrotechnology 5.3 Basic Mechanics: Force, Work, Power & Mechanical Energy 5.4 Mass, Weight, Levers, Gears & Pulleys
6 Electron Theory, Resistance, Resistivity & DC Circuits
6.1 Resistance, Resistivity & Conductor Dimensions 6.2 Temperature Coefficient of Resistance 6.3 Ohm's Law, Power & Direct Current Calculations 6.4 Series, Parallel & Combination DC Circuits 6.5 Electron Theory, Conductors, Insulators & the Effects of Current
7 Magnetism, Electromagnetism & Transformers
7.1 Magnetic Fields, Flux & Solenoid Properties 7.2 Electromagnetic Induction & Motor/Generator Principles 7.3 Transformer Principles, Construction & Calculations
8 Alternating Current, Three-Phase Systems & Electronic Components
8.1 AC Waveform Generation & Key Values 8.2 AC Circuit Theory: Reactance, Impedance & Power Factor 8.3 Three-Phase Generation, Star-Delta & UK Distribution 8.4 Electronic Components in Electrical Systems
9 Industry Regulations, Technical Information & Drawings
9.1 Electrical Regulations, Standards & Part P 9.2 Electrical Drawings, Diagrams & BS EN 60617 Symbols 9.3 Technical Specifications, Schedules & Environmental Influences
10 Wiring Systems, Cables, Containment & Practical Installation
10.1 Thermoplastic, Armoured & Flexible Cables 10.2 Specialised Cables: MICC & Fire-Performance Cables 10.3 Conduit Systems: Steel & PVC 10.4 Trunking, Cable Tray & Cable Supports 10.5 Unit 204 Practical Skills: Tools, Preparation & Installing Wiring Systems
11 Final Circuits, Protective Devices, Alarm & Control Circuits
11.1 Lighting Circuits & Switching Arrangements 11.2 Power Circuits: Ring Final, Radial & Dedicated Circuits 11.3 Consumer Units, Distribution Boards & Protective Devices 11.4 Alarm, Emergency Lighting, Data & Control Circuits
12 Cable Selection & Structural Installation
12.1 Cable Current-Carrying Capacity & Correction Factors 12.2 Voltage Drop Principles & Calculations 12.3 Structural Integrity & Concealed Cable Routing
13 Supply Systems, Earthing, Shock Protection & Micro-Renewables
13.1 UK Electricity Supply Networks & Distribution 13.2 Earthing System Configurations: TN-S, TN-C-S (PME and PNB) & TT 13.3 Protective Conductors, Bonding & Earth Electrodes 13.4 Automatic Disconnection of Supply (ADS) & Maximum Zs 13.5 Micro-Renewable Energy Technologies
14 Electrical Inspection & Dead Testing Sequence
14.1 Inspection Principles & Testing Safety to GS38 14.2 Continuity Testing: Protective Conductors & Ring Circuits 14.3 Insulation Resistance & Polarity Verification
15 Live Testing, Certification & Handover
15.1 Live Testing: Earth Loop Impedance, PFC & RCD Testing 15.2 Certification, Handover & Commissioning
16 Communicating within Building Services Engineering (Unit 210)
16.1 The Construction Team: Site Management, Trades & Site Visitors 16.2 Information Sources: Legislation, Guidance & Workplace Documents 16.3 Customer Information, Company Policies & Limits of Authority 16.4 Communicating Effectively: Methods, Accessibility & Conflict
6.2 Temperature Coefficient of Resistance
Key Takeaways Explain This Topic AI
Pure metallic conductors exhibit a Positive Temperature Coefficient (PTC), meaning electrical resistance increases as temperature rises due to intensified lattice ion vibrations impeding electron drift.
Semiconductors, carbon, electrolytes, and negative temperature coefficient (NTC) thermistors show decreasing resistance with rising temperature as thermal energy releases additional charge carriers into conduction bands.
Specialized alloys such as Constantan and Manganin feature near-zero temperature coefficients, making them indispensable for precision instrument shunts and laboratory reference standards.
The mathematical relationship governing temperature-induced resistance changes is R 2 = R 1 [ 1 + α 1 ( θ 2 − θ 1 ) ] R_2 = R_1 [1 + \alpha_1 (\theta_2 - \theta_1)] R 2 = R 1 [ 1 + α 1 ( θ 2 − θ 1 )] , where α \alpha α represents the fractional resistance change per degree Celsius.
In BS 7671 verification, copper conductor resistance increases by approximately 20% (1.20 multiplier) between a 20 ∘ C 20^\circ\text{C} 2 0 ∘ C ambient test and 70 ∘ C 70^\circ\text{C} 7 0 ∘ C full operating temperature, establishing the 0.8 test rule of thumb.
Last updated: October 2026
Temperature Coefficient of Resistance
In electrotechnical systems, electrical resistance is never strictly constant across operating environments. As an electrical machine, luminaire, or distribution cable carries current, it undergoes thermal changes due to internal I 2 R I^2R I 2 R power dissipation and fluctuations in ambient air temperature. The degree to which a material's electrical resistance changes in response to temperature variations depends directly on its atomic structure and is characterized by its temperature coefficient of resistance (symbolized by the Greek letter alpha, α \alpha α ).
Understanding how temperature alters resistance is fundamental for practicing electricians. Cable current-carrying capacities, voltage drop thresholds, motor winding diagnostics, and statutory earth fault loop impedance ( Z s Z_s Z s ) verification all depend on precise thermal adjustments.
Material Classifications: PTC, NTC, and Zero-Coefficient Alloys
Materials fall into three broad categories based on how their electrical resistance responds to temperature:
1. Positive Temperature Coefficient (PTC) — Pure Metals
All pure metals used in electrical installation work—such as copper , aluminium , silver , gold , and tungsten —possess a Positive Temperature Coefficient (PTC) . For these materials, an increase in temperature produces an increase in electrical resistance.
Microscopic Mechanism : In a metallic conductor, valence electrons are delocalized, forming an "electron gas" that drifts through a rigid crystalline lattice of positive atomic ions. At low temperatures, these lattice ions vibrate with relatively small amplitudes around their fixed equilibrium positions, allowing conduction electrons to drift with infrequent collisions (a longer "mean free path"). As temperature rises, thermal energy causes the positive lattice ions to vibrate with greater velocity and larger amplitudes. These intensified vibrations increase the cross-sectional collision frequency between drifting electrons and the lattice, impeding charge drift velocity and raising bulk electrical resistance.
2. Negative Temperature Coefficient (NTC) — Carbon and Semiconductors
Materials with a Negative Temperature Coefficient (NTC) exhibit an inverse response: as temperature increases, electrical resistance decreases .
Microscopic Mechanism : In materials such as carbon (graphite) , semiconductors ( silicon and germanium ), metallic oxide thermistors, and liquid electrolytes, valence electrons are tightly bound within covalent bonds at room temperature, leaving few charge carriers available in the conduction band. As thermal energy is supplied, covalent bonds are broken, releasing exponential cascades of free electrons and positive holes into the conduction band. This massive increase in the density of available charge carriers far outweighs the minor increase in lattice collision scattering, resulting in a dramatic net decrease in electrical resistance.
Practical Applications : NTC thermistors are widely utilized as temperature sensors in electronic thermostats, boiler water temperature monitors, digital thermometers, and inrush-current limiters that safely suppress initial current spikes in power supplies.
3. Zero or Negligible Temperature Coefficient Alloys
Specialized metallic alloys have been engineered to exhibit virtually zero change in electrical resistance across wide working temperature ranges:
Constantan (Eureka) : Composed of 55% copper and 45% nickel, Constantan has a temperature coefficient of approximately α ≈ ± 0.000008 per ∘ C \alpha \approx \pm 0.000008\text{ per }^\circ\text{C} α ≈ ± 0.000008 per ∘ C (essentially zero).
Manganin : Composed of 84% copper, 12% manganese, and 4% nickel, Manganin exhibits a temperature coefficient of roughly α ≈ ± 0.00001 per ∘ C \alpha \approx \pm 0.00001\text{ per }^\circ\text{C} α ≈ ± 0.00001 per ∘ C .
Engineering Importance : When constructing precision measurement instruments—such as ammeter shunts, voltmeter multipliers, Wheatstone bridges, and calibrated resistance decade boxes—resistor values must remain invariant regardless of whether ambient room temperature fluctuates or internal current flow generates heat. Using pure copper for an ammeter shunt would cause the meter calibration to drift by roughly 4% for every 10 ∘ C 10^\circ\text{C} 1 0 ∘ C rise; zero-coefficient alloys eliminate this thermal error.
Material Class Typical Materials Response to Rising Temperature ( Δ θ > 0 \Delta\theta > 0 Δ θ > 0 ) Temperature Coefficient ( α \alpha α at 20 ∘ C 20^\circ\text{C} 2 0 ∘ C ) Typical Electrotechnical Application
PTC (Pure Metals) Annealed Copper Resistance Increases + 0.00393 / ∘ C +0.00393\text{ /}^\circ\text{C} + 0.00393 / ∘ C ( + 0.393 % / ∘ C +0.393\%\text{ /}^\circ\text{C} + 0.393% / ∘ C ) Power distribution cables, motor field coils, busbars.
PTC (Pure Metals) Aluminium Resistance Increases + 0.00403 / ∘ C +0.00403\text{ /}^\circ\text{C} + 0.00403 / ∘ C ( + 0.403 % / ∘ C +0.403\%\text{ /}^\circ\text{C} + 0.403% / ∘ C ) Overhead lines, large sub-main distribution cables.
PTC (Pure Metals) Tungsten Resistance Increases Strongly + 0.00450 / ∘ C +0.00450\text{ /}^\circ\text{C} + 0.00450 / ∘ C ( + 0.450 % / ∘ C +0.450\%\text{ /}^\circ\text{C} + 0.450% / ∘ C ) Incandescent lamps (resistance increases 10 × 10\times 10 × to 12 × 12\times 12 × when lit).
NTC (Semiconductors) Carbon (Graphite) Resistance Decreases − 0.00050 / ∘ C -0.00050\text{ /}^\circ\text{C} − 0.00050 / ∘ C ( − 0.050 % / ∘ C -0.050\%\text{ /}^\circ\text{C} − 0.050% / ∘ C ) Motor commutator brushes, arc furnace electrodes.
NTC (Oxide Ceramics) NTC Thermistor Resistance Decreases Sharply Up to − 0.05000 / ∘ C -0.05000\text{ /}^\circ\text{C} − 0.05000 / ∘ C ( − 5.0 % / ∘ C -5.0\%\text{ /}^\circ\text{C} − 5.0% / ∘ C ) Central heating thermistors, motor thermal overload probes.
Near-Zero Alloys Constantan & Manganin Resistance Remains Constant ≈ ± 0.00001 / ∘ C \approx \pm 0.00001\text{ /}^\circ\text{C} ≈ ± 0.00001 / ∘ C (Negligible) Ammeter current shunts, precision calibration standards.
Mathematical Calculation of Temperature Variations
The temperature coefficient of resistance ( α \alpha α ) is defined as the fractional change in electrical resistance per degree Celsius ( ∘ C ^\circ\text{C} ∘ C ) change in temperature from a given baseline temperature.
The Reference Temperature Formula
When calculating final resistance from a baseline reference temperature of 0 ∘ C 0^\circ\text{C} 0 ∘ C :
R θ = R 0 ( 1 + α 0 θ ) R_\theta = R_0 (1 + \alpha_0 \theta) R θ = R 0 ( 1 + α 0 θ )
Where:
- R θ R_\theta R θ = Conductor resistance at operating temperature θ \theta θ ( Ω \Omega Ω )
- R 0 R_0 R 0 = Conductor resistance at 0 ∘ C 0^\circ\text{C} 0 ∘ C ( Ω \Omega Ω )
α 0 \alpha_0 α 0 = Temperature coefficient of the material at 0 ∘ C 0^\circ\text{C} 0 ∘ C ( per ∘ C \text{per }^\circ\text{C} per ∘ C )
- θ \theta θ = Conductor temperature in degrees Celsius ( ∘ C ^\circ\text{C} ∘ C )
- The Practical Working Temperature Formula
In electrical contracting, baseline tests are rarely conducted at 0 ∘ C 0^\circ\text{C} 0 ∘ C . Instead, measurements are typically taken at ambient workshop temperature (standardized as θ 1 = 20 ∘ C \theta_1 = 20^\circ\text{C} θ 1 = 2 0 ∘ C ). To calculate the resistance at a second operating temperature θ 2 \theta_2 θ 2 :
R 2 = R 1 [ 1 + α 1 ( θ 2 − θ 1 ) ] R_2 = R_1 [1 + \alpha_1 (\theta_2 - \theta_1)] R 2 = R 1 [ 1 + α 1 ( θ 2 − θ 1 )]
Where:
- R 1 R_1 R 1 = Initial resistance at temperature θ 1 \theta_1 θ 1 ( Ω \Omega Ω )
- R 2 R_2 R 2 = Final resistance at temperature θ 2 \theta_2 θ 2 ( Ω \Omega Ω )
α 1 \alpha_1 α 1 = Temperature coefficient at initial temperature θ 1 \theta_1 θ 1 (for copper at 20 ∘ C 20^\circ\text{C} 2 0 ∘ C , α 20 ≈ 0.00393 / ∘ C \alpha_{20} \approx 0.00393\text{ /}^\circ\text{C} α 20 ≈ 0.00393 / ∘ C , often rounded to 0.004 / ∘ C 0.004\text{ /}^\circ\text{C} 0.004 / ∘ C )
( θ 2 − θ 1 ) = Δ θ (\theta_2 - \theta_1) = \Delta\theta ( θ 2 − θ 1 ) = Δ θ = Temperature rise in degrees Celsius ( ∘ C ^\circ\text{C} ∘ C )
Worked Example 1: Contactor Coil Hot Resistance
Problem: The copper field coil of an AC contactor has a resistance of 24.0 Ω 24.0\ \Omega 24.0 Ω when measured in an unenergized panel at 20 ∘ C 20^\circ\text{C} 2 0 ∘ C . After six hours of continuous energization under heavy factory load, the coil temperature stabilizes at 70 ∘ C 70^\circ\text{C} 7 0 ∘ C . Calculate the operating resistance of the coil, taking α 20 = 0.00393 / ∘ C \alpha_{20} = 0.00393\text{ /}^\circ\text{C} α 20 = 0.00393 / ∘ C .
Solution:
Identify known values:
- R 1 = 24.0 Ω R_1 = 24.0\ \Omega R 1 = 24.0 Ω
- θ 1 = 20 ∘ C \theta_1 = 20^\circ\text{C} θ 1 = 2 0 ∘ C
- θ 2 = 70 ∘ C \theta_2 = 70^\circ\text{C} θ 2 = 7 0 ∘ C
- Δ θ = 70 − 20 = 50 ∘ C \Delta\theta = 70 - 20 = 50^\circ\text{C} Δ θ = 70 − 20 = 5 0 ∘ C
- α 1 = 0.00393 / ∘ C \alpha_1 = 0.00393\text{ /}^\circ\text{C} α 1 = 0.00393 / ∘ C
Substitute into the formula: R 2 = 24.0 × [ 1 + 0.00393 × 50 ] R_2 = 24.0 \times [1 + 0.00393 \times 50] R 2 = 24.0 × [ 1 + 0.00393 × 50 ]
Evaluate bracket terms: 0.00393 × 50 = 0.1965 0.00393 \times 50 = 0.1965 0.00393 × 50 = 0.1965 1 + 0.1965 = 1.1965 1 + 0.1965 = 1.1965 1 + 0.1965 = 1.1965
Calculate final resistance: R 2 = 24.0 × 1.1965 = 28.716 Ω ≈ 28.72 Ω R_2 = 24.0 \times 1.1965 = 28.716\ \Omega \approx 28.72\ \Omega R 2 = 24.0 × 1.1965 = 28.716 Ω ≈ 28.72 Ω
Worked Example 2: Temperature Rise Diagnostic in an Electric Motor
Problem: During machine maintenance, an induction motor stator winding has a cold resistance of 4.50 Ω 4.50\ \Omega 4.50 Ω at an ambient room temperature of 15 ∘ C 15^\circ\text{C} 1 5 ∘ C . Following a 4-hour full-load thermal run, the hot winding resistance measures 5.58 Ω 5.58\ \Omega 5.58 Ω . Determine the final operating temperature of the winding, taking α 15 = 0.0040 / ∘ C \alpha_{15} = 0.0040\text{ /}^\circ\text{C} α 15 = 0.0040 / ∘ C .
Solution:
Transpose the equation for temperature rise Δ θ \Delta\theta Δ θ : R 2 = R 1 [ 1 + α 1 Δ θ ] ⟹ R 2 R 1 = 1 + α 1 Δ θ ⟹ R 2 R 1 − 1 = α 1 Δ θ R_2 = R_1 [1 + \alpha_1 \Delta\theta] \implies \frac{R_2}{R_1} = 1 + \alpha_1 \Delta\theta \implies \frac{R_2}{R_1} - 1 = \alpha_1 \Delta\theta R 2 = R 1 [ 1 + α 1 Δ θ ] ⟹ R 1 R 2 = 1 + α 1 Δ θ ⟹ R 1 R 2 − 1 = α 1 Δ θ Δ θ = R 2 R 1 − 1 α 1 \Delta\theta = \frac{\frac{R_2}{R_1} - 1}{\alpha_1} Δ θ = α 1 R 1 R 2 − 1
Substitute measured values: R 2 R 1 = 5.58 4.50 = 1.24 \frac{R_2}{R_1} = \frac{5.58}{4.50} = 1.24 R 1 R 2 = 4.50 5.58 = 1.24 Δ θ = 1.24 − 1 0.0040 = 0.24 0.0040 = 60 ∘ C \Delta\theta = \frac{1.24 - 1}{0.0040} = \frac{0.24}{0.0040} = 60^\circ\text{C} Δ θ = 0.0040 1.24 − 1 = 0.0040 0.24 = 6 0 ∘ C
Calculate final temperature θ 2 \theta_2 θ 2 : θ 2 = θ 1 + Δ θ = 15 ∘ C + 60 ∘ C = 75 ∘ C \theta_2 = \theta_1 + \Delta\theta = 15^\circ\text{C} + 60^\circ\text{C} = 75^\circ\text{C} θ 2 = θ 1 + Δ θ = 1 5 ∘ C + 6 0 ∘ C = 7 5 ∘ C
The BS 7671 Rule of Thumb: The 20% Increase and the 0.8 Factor
In practical UK electrical installation inspection and testing under BS 7671 (IET Wiring Regulations) , temperature variations have direct statutory safety implications. This is most critical when verifying earth fault loop impedance ( Z s Z_s Z s ) .
The Operational Problem
Initial Verification Testing : Carried out before an installation is energized and loaded, under cold ambient site conditions—typically assumed to be 20 ∘ C 20^\circ\text{C} 2 0 ∘ C .
Full-Load Operating State : When an installation carries design current ( I b I_b I b ), continuous I 2 R I^2R I 2 R power dissipation heats the copper conductors to their maximum permissible continuous operating temperature:
70 ∘ C 70^\circ\text{C} 7 0 ∘ C for standard thermoplastic (PVC) insulated cables.
90 ∘ C 90^\circ\text{C} 9 0 ∘ C for thermosetting (XLPE / LSOH) insulated cables.
The 20% Resistance Increase Multiplier
To determine how much copper conductor resistance increases between ambient testing ( 20 ∘ C 20^\circ\text{C} 2 0 ∘ C ) and maximum thermoplastic operating temperature ( 70 ∘ C 70^\circ\text{C} 7 0 ∘ C ):
Δ θ = 70 ∘ C − 20 ∘ C = 50 ∘ C \Delta\theta = 70^\circ\text{C} - 20^\circ\text{C} = 50^\circ\text{C} Δ θ = 7 0 ∘ C − 2 0 ∘ C = 5 0 ∘ C R 70 = R 20 × [ 1 + 0.00393 × 50 ] = R 20 × [ 1 + 0.1965 ] = R 20 × 1.1965 ≈ 1.20 × R 20 R_{70} = R_{20} \times [1 + 0.00393 \times 50] = R_{20} \times [1 + 0.1965] = R_{20} \times 1.1965 \approx 1.20 \times R_{20} R 70 = R 20 × [ 1 + 0.00393 × 50 ] = R 20 × [ 1 + 0.1965 ] = R 20 × 1.1965 ≈ 1.20 × R 20
Important
The electrical resistance of copper conductors increases by approximately 20% (a multiplier of 1.20 1.20 1.20 ) as temperature rises from a 20 ∘ C 20^\circ\text{C} 2 0 ∘ C ambient dead-test condition to a maximum continuous full-load operating temperature of 70 ∘ C 70^\circ\text{C} 7 0 ∘ C .
The 0.8 Rule-of-Thumb Factor for Maximum Z s Z_s Z s Verification
To ensure that protective devices (such as BS EN 60898 circuit breakers or BS 88 fuses) disconnect automatically within the required statutory time limits ( 0.4 seconds 0.4\text{ seconds} 0.4 seconds for 230 V 230\text{ V} 230 V final circuits up to 32 A 32\text{ A} 32 A ), the operating earth fault loop impedance must not exceed the maximum values published in BS 7671 and the IET On-Site Guide ( Z s ≤ Z s ( tabulated ) Z_s \le Z_{s(\text{tabulated})} Z s ≤ Z s ( tabulated ) ).
However, the maximum values published in BS 7671 are calculated for conductors operating at their maximum operating temperature of 70 ∘ C 70^\circ\text{C} 7 0 ∘ C . If an electrician measures Z s Z_s Z s at 20 ∘ C 20^\circ\text{C} 2 0 ∘ C , the measured reading will naturally be lower than the impedance during a live fault under load.
To confirm compliance during initial testing at ambient temperatures, the electrician can:
Multiply the measured ambient loop impedance by 1.20 1.20 1.20 to project its value at 70 ∘ C 70^\circ\text{C} 7 0 ∘ C : Z s ( operating ) = Z s ( measured ) × 1.20 ≤ Z s ( tabulated ) Z_{s(\text{operating})} = Z_{s(\text{measured})} \times 1.20 \le Z_{s(\text{tabulated})} Z s ( operating ) = Z s ( measured ) × 1.20 ≤ Z s ( tabulated )
Or, divide both sides by 1.20 1.20 1.20 to compare the measured value directly against a reduced limit: Z s ( measured ) ≤ Z s ( tabulated ) 1.20 = Z s ( tabulated ) × 0.833 Z_{s(\text{measured})} \le \frac{Z_{s(\text{tabulated})}}{1.20} = Z_{s(\text{tabulated})} \times 0.833 Z s ( measured ) ≤ 1.20 Z s ( tabulated ) = Z s ( tabulated ) × 0.833
To provide an additional safety margin covering supply voltage variations and earthing conductor variations, BS 7671 and the IET On-Site Guide specify a conservative 0.80 multiplier (known as the "rule-of-thumb factor" ):
Z s ( measured ) ≤ 0.80 × Z s ( tabulated ) Z_{s(\text{measured})} \le 0.80 \times Z_{s(\text{tabulated})} Z s ( measured ) ≤ 0.80 × Z s ( tabulated )
If a 32 A Type B MCB has a tabulated maximum Z s Z_s Z s of 1.37 Ω 1.37\ \Omega 1.37 Ω in BS 7671, the maximum permissible reading on an instrument at 20 ∘ C 20^\circ\text{C} 2 0 ∘ C is: Z s ( test ) ≤ 1.37 × 0.80 = 1.096 Ω ≈ 1.10 Ω Z_{s(\text{test})} \le 1.37 \times 0.80 = 1.096\ \Omega \approx 1.10\ \Omega Z s ( test ) ≤ 1.37 × 0.80 = 1.096 Ω ≈ 1.10 Ω