4.1 Overview & Engineering Principles of Classification Codes
City & Guilds 2391-51 Periodic Inspection & Testing of Electrical Installations Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Purpose & Statutory Framework of Periodic Inspection
1.1 Statutory Framework & Purpose of Periodic Inspection 1.2 BS 7671 Chapter 65 Requirements for Periodic Inspection & Testing 1.3 Recommended Inspection Intervals & Trigger Events
2 Chapter 2: Visual Inspection & Sampling Procedures
2.1 Visual Inspection Fundamentals on Existing Installations 2.2 Guidance Note 3 Sampling Principles & Justification 2.3 Sample Expansion & Defect Escalation Criteria
3 Chapter 3: Electrical Installation Condition Report (EICR) Structure
3.1 EICR Layout, Sections, Declarations & Summary of Condition 3.2 Compiling the Schedule of Inspections for Existing Installations 3.3 Schedule of Test Results, Circuit Details & Instrument Data
4 Chapter 4: EICR Classification Coding Principles (C1, C2, C3, FI)
4.1 Overview & Engineering Principles of Classification Codes 4.2 Code C1 (Danger Present) & Code C2 (Potentially Dangerous) Criteria 4.3 Code C3 (Improvement Recommended) & Code FI (Further Investigation) Criteria
5 Chapter 5: Classification Code Application & Practical Scenarios
5.1 Coding Scenarios: Earthing, Bonding & Shock Protection Defects 5.2 Coding Scenarios: Wiring Systems, Accessories & Thermal Effects 5.3 Overall Assessment Determination & Client Communication
6 Chapter 6: Selected Dead Tests on Existing Installations
6.1 Dead Testing Overview & Continuity of Protective Conductors 6.2 Ring Final Circuit Continuity Testing 6.3 Insulation Resistance Testing & Protection of Sensitive Equipment
7 Chapter 7: Selected Live Tests & RCD Verification
7.1 Polarity Verification & Earth Fault Loop Impedance (Ze, Zs) 7.2 Prospective Fault Current (PFC) & RCD Testing 7.3 Functional Testing & Voltage Drop Assessment
8 Chapter 8: Scope, Limitations & Safe Testing Procedures
8.1 Agreeing Extent, Operational & Agreed Limitations 8.2 Safe Isolation Procedures & GS38 Guidance 8.3 Risk Assessment & Restoring Installations to Service
9 Chapter 9: Test Result Interpretation, Temperature Correction & Certification
9.1 Interpreting Zs Values & The 80% Rule (Rule of Thumb) 9.2 Temperature Correction Factors & Historical Trend Analysis 9.3 Certification Sign-off, Competency & Instrument Calibration
4.1 Overview & Engineering Principles of Classification Codes
Key Takeaways Explain This Topic AI
EICR classification codes (C1, C2, C3, FI) are objective engineering evaluations of safety risks against current BS 7671 standards (BS 7671), established in IET Guidance Note 3 (GN3) and Electrical Safety First Best Practice Guide 4 (BPG4 Issue 5).
The primary legal driver for periodic inspection is compliance with the Electricity at Work Regulations 1989 (EAWR Regulation 4(2)), demanding systems be maintained to prevent danger; classification codes communicate urgency to the person ordering the report.
Non-compliance with a current edition of BS 7671 does not automatically warrant a defect code; retrofitting to current standards is not required solely because a regulation has changed, provided the existing installation remains safe.
An overall assessment of UNSATISFACTORY is automatically triggered by the presence of a single C1, C2, or FI code on the condition report summary; only C3 codes permit a SATISFACTORY overall outcome.
Inspectors must exercise professional judgment using evidence-based risk assessment rather than personal preference, ensuring consistency across domestic, commercial, and industrial installations.
Last updated: July 2026
Introduction to EICR Classification Coding
Periodic inspection and testing of existing electrical installations is conducted to determine, as far as reasonably practicable, whether an installation is in a satisfactory condition for continued service. Unlike initial verification for new installations—where strict compliance with the latest edition of BS 7671 is mandatory before certification—periodic inspection evaluates existing infrastructure through an evidence-based engineering risk assessment. The results of this evaluation are formally documented on an Electrical Installation Condition Report (EICR) using four standardized classification codes: Code C1 , Code C2 , Code C3 , and Code FI .
The classification codes provide a standardized, objective framework designed to communicate the level of risk and urgency of remedial action to the person ordering the report (the duty holder, landlord, or building owner). Understanding the engineering logic, legal context, and guidance behind these codes is a core requirement for City & Guilds 2391-51 candidates.
Legal Context & Standards Framework
The legal foundation for periodic inspection in the United Kingdom rests upon several key pieces of legislation:
Electricity at Work Regulations 1989 (EAWR) : Regulation 4(2) mandates that "As may be necessary to prevent danger, all systems shall be maintained so as to prevent, so far as is reasonably practicable, such danger." Periodic inspection is the primary mechanism by which duty holders verify compliance with Regulation 4(2).
Health and Safety at Work etc. Act 1974 (HASAWA) : Sections 2 and 3 place a general duty of care on employers and self-employed persons to ensure the safety of employees and non-employees.
The Housing Act 2004 & Landlord and Tenant Act 1985 (as amended) : Including the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 , which mandate 5-yearly EICRs for private rented residential properties, requiring landlord action within 28 days for any C1, C2, or FI observations.
Industry Guidance & Best Practice
To ensure consistency across the UK electrical industry, classification coding must align with two authoritative publications:
IET Guidance Note 3 (Inspection, Testing & Certification) : Provides technical guidance on the inspection process, test procedures, and coding definitions under BS 7671.
Electrical Safety First Best Practice Guide 4 (BPG4 Issue 5/6) : Electrical installation condition reporting: Classification codes for domestic and similar electrical installations . BPG4 was developed by an industry consortium (including IET, NICEIC, NAPIT, ECA, Select, and Electrical Safety First) to eliminate subjective coding and establish consensus examples for C1, C2, C3, and FI codes.
Fundamental Engineering Principles of Coding
When assessing observations during periodic inspection, inspectors must adhere to three governing principles:
1. Objective Assessment Against Current BS 7671
Observations must be evaluated against the safety requirements of the current edition of BS 7671 (currently BS 7671). However, non-compliance with a current regulation does not automatically mean that an installation is unsafe or requires a defect code.
2. Retrospective Compliance & Existing Installations
BS 7671 is not retrospective. Existing installations that complied with earlier editions of the Wiring Regulations at the time of installation may not comply with every current requirement (e.g., absence of RCD protection on all lighting circuits or lack of Surge Protection Devices). Such items must not automatically be coded as dangerous (C1 or C2) unless an actual hazard or potential hazard exists due to the environment, usage, or degraded condition.
Engineering Rule: An installation built to a previous edition of BS 7671 is not necessarily unsafe. A defect code is assigned only if the observed condition presents immediate danger (C1), potential danger (C2), recommends safety enhancement (C3), or requires further investigation (FI).
3. Risk-Based Engineering Judgement
Inspectors must evaluate the likelihood and severity of harm. Factors to consider include:
The presence of vulnerable persons or specialized environments (e.g., medical locations, educational facilities, wet rooms).
The operational environment (e.g., external weather exposure, mechanical impact risk).
The presence and integrity of protective measures (e.g., Automatic Disconnection of Supply [ADS], double insulation, earthing and bonding).
Summary of Classification Codes
- Code Definition Action Required Overall EICR Impact
- C1 Danger Present Risk of injury. Immediate remedial action required. UNSATISFACTORY
- C2 Potentially Dangerous Urgent remedial action required. UNSATISFACTORY
- C3 Improvement Recommended Non-compliance with current standard, safety enhancement. SATISFACTORY
- FI Further Investigation Required Investigation required without delay to verify safety. UNSATISFACTORY
- Overall Assessment Outcome: Satisfactory vs Unsatisfactory
The overall condition assessment recorded on Page 1 of the EICR is a binary determination derived directly from the individual observation codes recorded during inspection:
UNSATISFACTORY : Triggered if one or more observations are assigned Code C1 , Code C2 , or Code FI . A single C1, C2, or FI code makes the overall report Unsatisfactory.
SATISFACTORY : Permitted only if there are no C1, C2, or FI codes recorded. An installation with multiple Code C3 observations (or no defect codes at all) achieves an overall assessment outcome of SATISFACTORY .
The Inspector's Professional Responsibilities
The inspector carries a legal and professional duty of care when conducting an EICR:
Descriptive Documentation : Each recorded observation must clearly specify the exact nature of the defect, its precise location (e.g., "DB-1 Circuit 4 - socket outlet adjacent to main entrance"), and the relevant BS 7671 regulation number where applicable.
Vague Language Ban : Phrasing such as "rewire required", "old installation", or "does not meet modern standards" is strictly prohibited. Observations must explicitly describe the physical defect or non-compliance.
Immediate Hazard Protocol : If a Code C1 (or severe C2) condition is discovered, the inspector must immediately inform the duty holder verbally and in writing using an Electrical Danger Notification or Emergency Action Form , advising immediate isolation of the affected circuit with the client's consent.