9.2 Temperature Correction Factors & Historical Trend Analysis

City & Guilds 2391-51 Periodic Inspection & Testing of Electrical Installations Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Purpose & Statutory Framework of Periodic Inspection

1.1 Statutory Framework & Purpose of Periodic Inspection 1.2 BS 7671 Chapter 65 Requirements for Periodic Inspection & Testing 1.3 Recommended Inspection Intervals & Trigger Events

2 Chapter 2: Visual Inspection & Sampling Procedures

2.1 Visual Inspection Fundamentals on Existing Installations 2.2 Guidance Note 3 Sampling Principles & Justification 2.3 Sample Expansion & Defect Escalation Criteria

3 Chapter 3: Electrical Installation Condition Report (EICR) Structure

3.1 EICR Layout, Sections, Declarations & Summary of Condition 3.2 Compiling the Schedule of Inspections for Existing Installations 3.3 Schedule of Test Results, Circuit Details & Instrument Data

4 Chapter 4: EICR Classification Coding Principles (C1, C2, C3, FI)

4.1 Overview & Engineering Principles of Classification Codes 4.2 Code C1 (Danger Present) & Code C2 (Potentially Dangerous) Criteria 4.3 Code C3 (Improvement Recommended) & Code FI (Further Investigation) Criteria

5 Chapter 5: Classification Code Application & Practical Scenarios

5.1 Coding Scenarios: Earthing, Bonding & Shock Protection Defects 5.2 Coding Scenarios: Wiring Systems, Accessories & Thermal Effects 5.3 Overall Assessment Determination & Client Communication

6 Chapter 6: Selected Dead Tests on Existing Installations

6.1 Dead Testing Overview & Continuity of Protective Conductors 6.2 Ring Final Circuit Continuity Testing 6.3 Insulation Resistance Testing & Protection of Sensitive Equipment

7 Chapter 7: Selected Live Tests & RCD Verification

7.1 Polarity Verification & Earth Fault Loop Impedance (Ze, Zs) 7.2 Prospective Fault Current (PFC) & RCD Testing 7.3 Functional Testing & Voltage Drop Assessment

8 Chapter 8: Scope, Limitations & Safe Testing Procedures

8.1 Agreeing Extent, Operational & Agreed Limitations 8.2 Safe Isolation Procedures & GS38 Guidance 8.3 Risk Assessment & Restoring Installations to Service

9 Chapter 9: Test Result Interpretation, Temperature Correction & Certification

9.1 Interpreting Zs Values & The 80% Rule (Rule of Thumb) 9.2 Temperature Correction Factors & Historical Trend Analysis 9.3 Certification Sign-off, Competency & Instrument Calibration

9.2 Temperature Correction Factors & Historical Trend Analysis

Key Takeaways Explain This Topic AI

Conductor temperature correction factor Ctu (IET GN3 Table 2D) corrects copper resistance from ambient testing temperature (theta_a) to maximum operating temperature (70°C for PVC).

The formula for Ctu for copper conductors is Ctu = (230 + 70) / (230 + theta_a) = 300 / (230 + theta_a), yielding Ctu = 1.20 at 20°C ambient.

When calculating expected Zs under load: Zs(corrected) = Ze + [(R1 + R2)ambient x Ctu]. Ctu is applied ONLY to the conductor resistance (R1 + R2), NOT to external loop impedance Ze.

Historical trend analysis requires comparing current (R1 + R2), Re, and insulation resistance against original EICs and previous EICRs to detect progressive copper oxidation or insulation breakdown.

A drop in insulation resistance (e.g., from 350 MΩ to 3.2 MΩ) requires investigation (Code C3 or FI) even if it remains above the 1.0 MΩ absolute minimum requirement.

Last updated: July 2026

9.2 Temperature Correction Factors & Historical Trend Analysis

When an earth fault loop impedance ( Z s Z_s Z s ​ ) measurement exceeds the 80% Rule of Thumb limit ( 0.8 × Z s ( tabulated ) 0.8 \times Z_{s(\text{tabulated})} 0.8 × Z s ( tabulated ) ​ ) but remains below the 100% tabulated maximum value in BS 7671 Chapter 41, the inspector cannot make a definitive compliance judgment without performing exact temperature correction .

In addition, interpreting test results during periodic inspection requires historical trend analysis —comparing current readings against initial verification records (Electrical Installation Certificates) and prior Electrical Installation Condition Reports (EICRs) to identify progressive electrical degradation.

Mathematical Derivation of Conductor Temperature Correction ( C t u C_{tu} C t u ​ )

The electrical resistance of metallic conductors varies with temperature. For copper, the resistance increases linearly as temperature increases. In IET Guidance Note 3 (Appendix 2) , the temperature correction factor C t u C_{tu} C t u ​ is used to adjust measured conductor resistance from ambient testing temperature ( θ a \theta_a θ a ​ ) to the maximum operating temperature ( θ m = 70 ∘ C \theta_m = 70^\circ\text{C} θ m ​ = 7 0 ∘ C for thermoplastic/PVC conductors).

The C t u C_{tu} C t u ​ Multiplier Formula

The standard formula for calculating the temperature correction multiplier factor C t u C_{tu} C t u ​ for copper conductors is: C t u = 230 + θ m 230 + θ a = 230 + 70 230 + θ a = 300 230 + θ a C_{tu} = \frac{230 + \theta_m}{230 + \theta_a} = \frac{230 + 70}{230 + \theta_a} = \frac{300}{230 + \theta_a} C t u ​ = 230 + θ a ​ 230 + θ m ​ ​ = 230 + θ a ​ 230 + 70 ​ = 230 + θ a ​ 300 ​

Where:

230 230 230 is the inferential zero-resistance temperature constant for copper (in ∘ C ^\circ\text{C} ∘ C ).

θ m \theta_m θ m ​ is the maximum conductor operating temperature under normal load ( 70 ∘ C 70^\circ\text{C} 7 0 ∘ C for PVC, 90 ∘ C 90^\circ\text{C} 9 0 ∘ C for XLPE).

θ a \theta_a θ a ​ is the actual ambient air temperature at the time of testing ( ∘ C ^\circ\text{C} ∘ C ).

(For aluminum conductors, the constant is 228, giving C t u = 228 + 70 228 + θ a = 298 228 + θ a C_{tu} = \frac{228 + 70}{228 + \theta_a} = \frac{298}{228 + \theta_a} C t u ​ = 228 + θ a ​ 228 + 70 ​ = 228 + θ a ​ 298 ​ .)

Tabulated C t u C_{tu} C t u ​ Values for Copper Conductors (PVC Insulated)

Ambient Test Temperature ( θ a \theta_a θ a ​ ) Formula Calculation Temperature Correction Factor ( C t u C_{tu} C t u ​ )

10 ∘ C 10^\circ\text{C} 1 0 ∘ C 300 / ( 230 + 10 ) = 300 / 240 300 / (230 + 10) = 300 / 240 300/ ( 230 + 10 ) = 300/240 1.25

15 ∘ C 15^\circ\text{C} 1 5 ∘ C 300 / ( 230 + 15 ) = 300 / 245 300 / (230 + 15) = 300 / 245 300/ ( 230 + 15 ) = 300/245 1.22

20 ∘ C 20^\circ\text{C} 2 0 ∘ C 300 / ( 230 + 20 ) = 300 / 250 300 / (230 + 20) = 300 / 250 300/ ( 230 + 20 ) = 300/250 1.20

25 ∘ C 25^\circ\text{C} 2 5 ∘ C 300 / ( 230 + 25 ) = 300 / 255 300 / (230 + 25) = 300 / 255 300/ ( 230 + 25 ) = 300/255 1.18

At a standard ambient reference temperature of 20 ∘ C 20^\circ\text{C} 2 0 ∘ C , C t u = 1.20 C_{tu} = 1.20 C t u ​ = 1.20 , which mathematically demonstrates why the 80% rule of thumb ( 1 1.20 = 0.833 ≈ 0.80 \frac{1}{1.20} = 0.833 \approx 0.80 1.20 1 ​ = 0.833 ≈ 0.80 ) is used as a quick conservative field check.

Applying Temperature Correction to Earth Fault Loop Impedance

A common error in City & Guilds 2391 examinations is applying the C t u C_{tu} C t u ​ factor to the entire measured Z s Z_s Z s ​ value .

The external loop impedance Z e Z_e Z e ​ (comprising the supply transformer winding, line conductor, and utility earth path) is measured directly at the distribution board origin while the supply is energized. It reflects the utility network's existing operating temperature and impedance. Therefore, C t u C_{tu} C t u ​ must ONLY be applied to the internal installation conductor resistance ( R 1 + R 2 ) (R_1 + R_2) ( R 1 ​ + R 2 ​ ) .

Correct Z s Z_s Z s ​ Temperature Correction Formula Z s ( corrected at 70 ∘ C ) = Z e + [ ( R 1 + R 2 ) ambient × C t u ] Z_{s(\text{corrected at } 70^\circ\text{C})} = Z_e + \left[ (R_1 + R_2)_{\text{ambient}} \times C_{tu} \right] Z s ( corrected at 7 0 ∘ C ) ​ = Z e ​ + [ ( R 1 ​ + R 2 ​ ) ambient ​ × C t u ​ ]

Alternatively, if Z s Z_s Z s ​ was measured directly at a remote point on a live circuit rather than calculated from Z e + ( R 1 + R 2 ) Z_e + (R_1 + R_2) Z e ​ + ( R 1 ​ + R 2 ​ ) : ( R 1 + R 2 ) ambient = Z s ( measured ) − Z e (R_1 + R_2)_{\text{ambient}} = Z_{s(\text{measured})} - Z_e ( R 1 ​ + R 2 ​ ) ambient ​ = Z s ( measured ) ​ − Z e ​ Z s ( corrected ) = Z e + [ ( Z s ( measured ) − Z e ) × C t u ] Z_{s(\text{corrected})} = Z_e + \left[ (Z_{s(\text{measured})} - Z_e) \times C_{tu} \right] Z s ( corrected ) ​ = Z e ​ + [ ( Z s ( measured ) ​ − Z e ​ ) × C t u ​ ]

Worked Exam Problem:

Scenario : A 230 V final circuit protected by a 32 A Type B MCB (BS 7671 Table 41.2 Max Z s = 1.37 Ω Z_s = 1.37\ \Omega Z s ​ = 1.37 Ω ) is tested at an ambient temperature of 10 ∘ C 10^\circ\text{C} 1 0 ∘ C .

Measured Z e = 0.25 Ω Z_e = 0.25\ \Omega Z e ​ = 0.25 Ω .

Measured ( R 1 + R 2 ) (R_1 + R_2) ( R 1 ​ + R 2 ​ ) at 10 ∘ C = 0.88 Ω 10^\circ\text{C} = 0.88\ \Omega 1 0 ∘ C = 0.88 Ω .

Measured total Z s Z_s Z s ​ at ambient = 0.25 + 0.88 = 1.13 Ω = 0.25 + 0.88 = 1.13\ \Omega = 0.25 + 0.88 = 1.13 Ω .

Evaluation :

Check 80% Rule: 1.37 × 0.8 = 1.10 Ω 1.37 \times 0.8 = 1.10\ \Omega 1.37 × 0.8 = 1.10 Ω . Measured Z s Z_s Z s ​ ( 1.13 Ω 1.13\ \Omega 1.13 Ω ) exceeds 1.10 Ω 1.10\ \Omega 1.10 Ω . The circuit fails the 80% rule of thumb check.

Calculate C t u C_{tu} C t u ​ for 10 ∘ C 10^\circ\text{C} 1 0 ∘ C : C t u = 300 230 + 10 = 300 240 = 1.25 C_{tu} = \frac{300}{230 + 10} = \frac{300}{240} = 1.25 C t u ​ = 230 + 10 300 ​ = 240 300 ​ = 1.25

Apply C t u C_{tu} C t u ​ to ( R 1 + R 2 ) (R_1 + R_2) ( R 1 ​ + R 2 ​ ) : ( R 1 + R 2 ) 70 ∘ C = 0.88 × 1.25 = 1.10 Ω (R_1 + R_2)_{70^\circ\text{C}} = 0.88 \times 1.25 = 1.10\ \Omega ( R 1 ​ + R 2 ​ ) 7 0 ∘ C ​ = 0.88 × 1.25 = 1.10 Ω

Calculate Corrected Operating Z s Z_s Z s ​ : Z s ( corrected ) = 0.25 + 1.10 = 1.35 Ω Z_{s(\text{corrected})} = 0.25 + 1.10 = 1.35\ \Omega Z s ( corrected ) ​ = 0.25 + 1.10 = 1.35 Ω

Final Comparison: Compare corrected Z s Z_s Z s ​ ( 1.35 Ω 1.35\ \Omega 1.35 Ω ) against BS 7671 Table 41.2 maximum ( 1.37 Ω 1.37\ \Omega 1.37 Ω ).

Because 1.35 Ω ≤ 1.37 Ω 1.35\ \Omega \le 1.37\ \Omega 1.35 Ω ≤ 1.37 Ω , the circuit is fully compliant for Automatic Disconnection of Supply under maximum operating temperature.

Historical Trend Analysis & Comparative Assessment

Periodic inspection is not merely a single point-in-time pass/fail audit. BS 7671 Chapter 65 requires the inspector to review previous certificates and test results to identify trends of deterioration before catastrophic electrical failure occurs.

Continuity Trend Analysis ( R 1 + R 2 R_1 + R_2 R 1 ​ + R 2 ​ and R p e R_{pe} R p e ​ )

Minor variations : Fluctuations of ± 0.05 Ω \pm 0.05\ \Omega ± 0.05 Ω between successive EICRs are typically attributable to instrument resolution, ambient temperature differences, or contact resistance on probe tips.

Significant increases : An unexplained increase in ( R 1 + R 2 ) (R_1 + R_2) ( R 1 ​ + R 2 ​ ) of 10% to 15% or more compared to initial verification baseline values indicates:

Loose or high-resistance terminal connections due to thermal cycling.

Progressive copper corrosion/oxidation in damp environments.

Mechanical damage or reduction in cross-sectional area (frayed multi-strand conductors).

Insulation Resistance Deterioration Trends

Baseline comparison : Initial verification certificates for new PVC cable assemblies typically show insulation resistance readings in excess of 200 M Ω 200\text{ M}\Omega 200 M Ω to 500 M Ω 500\text{ M}\Omega 500 M Ω (often recorded as > 500 M Ω >500\text{ M}\Omega > 500 M Ω ).

Degradation analysis : BS 7671 Table 64.1 specifies a absolute minimum passing threshold of 1.0 M Ω 1.0\text{ M}\Omega 1.0 M Ω for low voltage circuits operating at 500 V DC test voltage.

Diagnostic evaluation : If a circuit reads 3.0 M Ω 3.0\text{ M}\Omega 3.0 M Ω , it technically passes the absolute BS 7671 threshold. However, if the previous EICR recorded 250 M Ω 250\text{ M}\Omega 250 M Ω , this sharp decline represents a 98.8% loss of insulation integrity .

Causes : Thermal overheating, moisture ingress, chemical degradation, or cable sheath damage by rodents or mechanical stress. [ Insulation Resistance Baseline: > 500 MΩ ] ──► Initial Verification (EIC)

  • │
  • ▼
  • [ Periodic Inspection 1 (Year 5): 150 MΩ ] ──► Normal Minor Drift
  • │
  • ▼

[ Periodic Inspection 2 (Year 10): 3.5 MΩ ] ──► Severe Progressive Breakdown!

  • (Passes >1MΩ limit, but requires
  • Classification Code C3 / FI)
  • Classification Coding Based on Results & Trends

When test results or trend analyses reveal non-compliances, the inspector assigns one of four standardized outcome codes on the EICR:

Code Standard Meaning Action Required Example Scenario

C1 Danger Present Immediate remedial action required. Client notified immediately in writing. Exposed live conductors or broken main protective bonding resulting in active shock risk.

C2 Potentially Dangerous Urgent remedial action required. Corrected Z s Z_s Z s ​ exceeds BS 7671 Table 41 limit with no RCD fault protection present.

C3 Improvement Recommended Non-compliance with current BS 7671 edition that does not present immediate danger. Severe drop in insulation resistance (e.g. 3 M Ω 3\text{ M}\Omega 3 M Ω ) or lack of modern safety signage.

FI Further Investigation Required Investigation required without delay to reveal potential hazard. Missing historical records combined with unexplained high continuity readings or hidden junction boxes.