6.2 Continuity of Ring Final Circuits (r1, rn, r2)
City & Guilds 2391-52 Combined Inspection & Testing of Electrical Installations Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the 2391-52 Exam 1.2 How to Use This Guide & Open-Book Exam Strategy
2 Chapter 2: Statutory & Non-Statutory Documents
2.1 Statutory Documents 2.2 Non-Statutory Documents 2.3 Roles, Responsibilities & the Statutory/Non-Statutory Relationship
3 Chapter 3: Certification & Documentation
3.1 The Electrical Installation Certificate (EIC) & Schedules 3.2 The Minor Electrical Installation Works Certificate (MEIWC) 3.3 The Electrical Installation Condition Report (EICR) & Schedules 3.4 Why the Documents Exist: Reasons, Information Needed, Recording & Retention
4 Chapter 4: Initial Verification & Safe Isolation
4.1 Safe Isolation & Safety Management 4.2 Visual Inspection Requirements 4.3 Initial Verification: Requirements & Process 4.4 Additions & Alterations to an Existing Installation 4.5 Inspection Methods: The Senses, Verifying Items & IP Classification
5 Chapter 5: Sequence of Tests & Test Instruments
5.1 The Correct Sequence of Tests 5.2 Test Instruments: Selection, Calibration & Accuracy 5.3 Factors That Affect Test Results & Tests That May Be Unnecessary at Periodic Inspection
6 Chapter 6: Continuity Testing
6.1 Continuity of Protective Conductors (R1+R2) 6.2 Continuity of Ring Final Circuits (r1, rn, r2) 6.3 Main & Supplementary Protective Bonding Continuity
7 Chapter 7: Insulation Resistance & Polarity
7.1 Insulation Resistance Testing 7.2 Polarity Verification 7.3 Verifying SELV, PELV & Electrical Separation
8 Chapter 8: Earth Fault Loop Impedance
8.1 Ze & Zs Measurement 8.2 Zs Limits, Disconnection Times & the 0.8 Rule 8.3 Prospective Fault Current (PFC/PSCC)
9 Chapter 9: RCD & Earth Electrode Testing
9.1 RCD Testing 9.2 Earth Electrode Resistance on TT Systems
10 Chapter 10: Periodic Inspection & EICR Reporting
10.1 Purpose, Scope & Limitations of Periodic Inspection 10.2 Sampling & Extent of Inspection 10.3 Observation Classification Codes C1/C2/C3/FI 10.4 Outcomes, Inspection Intervals & Completing the EICR
11 Chapter 11: Phase Sequence, Functional Testing & Voltage Drop
11.1 Check of Phase Sequence 11.2 Functional Testing 11.3 Verification of Voltage Drop
12 Chapter 12: The 2391-502 Practical Assignment
12.1 The Practical Assignment & Establishing a Safe System of Work 12.2 Carrying Out the Practical: Inspection, Tests, Verification & Documentation
6.2 Continuity of Ring Final Circuits (r1, rn, r2)
Key Takeaways Explain This Topic AI
A ring final circuit needs a special three-step test because its two parallel paths mean a broken ring can still show continuity via the other half
Step 1 measures end-to-end r1, rn, r2 at the DB; r1 ≈ rn, and r2 ≈ 1.67 × r1 when the CPC is 1.5 mm² against 2.5 mm² phase
Step 2 (P–N crossover) gives (r1+rn)/4 at every socket; step 3 (P–CPC crossover) gives (r1+r2)/4 at every socket, which is the R1+R2 recorded for the ring
The /4 value arises because the cross-connection forms a figure-of-eight with two equal parallel halves, so each accessory sees one quarter of the total loop
A socket that reads markedly higher than the others in step 2 or 3 is a spur off the ring or has a high-resistance joint
Last updated: August 2026
Why Ring Final Circuits Need a Special Test
A ring final circuit (the standard UK domestic socket circuit, BS 7671 Appendix 15) is wired as a loop: the phase, neutral, and CPC conductors each run from the distribution board, through every socket, and back to the distribution board. Each conductor therefore forms a closed ring with two parallel paths from the board to any given socket.
This parallel-path geometry defeats an ordinary end-to-end continuity test. If the ring is broken at one point, current can still reach every socket via the other half of the ring — so a simple end-to-end test at the board would still show continuity and miss the break. BS 7671 therefore requires a three-step ring continuity test , described in GN3 10th Edition and examined heavily on the 2391-52.
Step 1: End-to-End Resistance of Each Conductor (r1, rn, r2)
At the distribution board, identify and label the three conductor pairs . A ring has two ends for each conductor returned to the board:
Phase (line): two ends, labelled r1 — call them P1 and P2.
Neutral: two ends, labelled rn — N1 and N2.
CPC: two ends, labelled r2 — CPC1 and CPC2.
With the circuit isolated, measure the end-to-end resistance of each conductor by connecting the ohmmeter across its two ends at the board. This confirms each conductor is unbroken around the ring.
- Conductor End-to-end value Expected relationship
- Phase r1 e.g. 0.40 Ω —
- Neutral rn e.g. 0.40 Ω rn ≈ r1 (same CSA)
- CPC r2 e.g. 0.67 Ω r2 ≈ 1.67 × r1 if CPC is 1.5 mm² and phase is 2.5 mm²
The phase and neutral are normally the same cross-sectional area (2.5 mm² thermoplastic), so r1 ≈ rn . The CPC is often 1.5 mm² — 60% of the phase CSA — so its resistance is higher by the ratio 2.5 / 1.5 = 1.67 . If r2 is roughly 1.67 times r1, the CPC is the right size and unbroken. If r1 and rn differ significantly, investigate before proceeding — one conductor may be a different length or have a poor joint.
Step 2: Phase–Neutral Crossover (P1–N2 and P2–N1)
Cross-connect the phase and neutral ends across the ring: link P1 to N2 and P2 to N1 at the distribution board. This creates a figure-of-eight loop. Now test between phase and neutral at every socket on the ring.
The reading at every socket should be approximately:
(r1 + rn) / 4
and the readings should be roughly equal at every socket .
Why /4?
The cross-connection puts the two conductor rings in parallel as a figure-of-eight. From any socket, the test current can travel to the board by two equal paths — one clockwise, one anticlockwise — each of half the total conductor length. The resistance seen at the socket is therefore one quarter of the sum of the two conductor resistances: (r1 + rn) / 4. If every socket gives the same value, the ring is correctly formed phase-to-neutral.
- Worked Example (Steps 1 and 2)
- r1 = 0.40 Ω, rn = 0.40 Ω, r2 = 0.67 Ω
- Step 2 expected reading at every socket = (0.40 + 0.40) / 4 = 0.20 Ω
A socket that gives a markedly higher reading in step 2 is not on the ring — it is a spur, or there is a high-resistance joint. Spurs are identified this way: the ring sockets all read about 0.20 Ω, and the spur reads higher because it adds an extra radial run on top of the ring value.
Step 3: Phase–CPC Crossover (P1–CPC2 and P2–CPC1)
Cross-connect the phase and CPC ends: link P1 to CPC2 and P2 to CPC1 at the distribution board. Test between phase and earth at every socket.
The reading at every socket should be approximately:
(r1 + r2) / 4
and again roughly equal at every socket. This value is the R1+R2 for the ring final circuit and is what you record on the schedule of test results — not the end-to-end r1 or r2 from step 1.
- Worked Example (Step 3)
- r1 = 0.40 Ω, r2 = 0.67 Ω
- Step 3 expected reading at every socket = (0.40 + 0.67) / 4 = 0.2675 ≈ 0.27 Ω
Record R1+R2 = 0.27 Ω on the schedule.
Then Zs = Ze + (R1+R2) = Ze + 0.27 Ω, compared to the tabulated maximum for the protective device (typically a 32 A Type B MCB, or a 30 mA RCD on a TT system).
Summary of the Three Steps
- Step Action Connect at DB Test at each socket Expected reading
- 1 End-to-end each conductor Across own two ends — r1, rn, r2 (r1≈rn; r2≈1.67×r1)
- 2 P–N crossover P1–N2, P2–N1 Phase to Neutral (r1+rn)/4
- 3 P–CPC crossover P1–CPC2, P2–CPC1 Phase to Earth (r1+r2)/4 = R1+R2
- Exam-Critical Points
Record (r1+r2)/4 as R1+R2 , not the end-to-end r1 or r2. The end-to-end value is a check that each conductor is unbroken; the crossover value is the figure used for Zs.
The figure-of-eight is why you divide by 4 — two equal parallel halves each carry half the current, so each accessory sees one quarter of the total loop. This derivation is exam-critical.
A socket reading higher than the others in step 2 or 3 indicates a spur or a fault — investigate before recording the circuit's R1+R2.
Always null the test leads before step 1; lead resistance is significant at these values and propagates into every subsequent reading if not removed.
The three step-1 end-to-end values confirm each conductor is unbroken; the two crossover steps confirm the ring is correctly formed and give the recorded R1+R2.