4.3 Commercial & Multifamily Load Calculations (Article 220 Part III)
Virginia Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Exam Facts, Format & Scoring 1.2 Eligibility, Application & Scheduling 1.3 Open-Book Strategy & Test-Taking
2 Virginia Board Regulations (18VAC50-30)
2.1 Definitions & Qualification for Licensure 2.2 Standards of Practice 2.3 Standards of Conduct & Revocation of Licensure 2.4 Renewal and Reinstatement
3 General Knowledge & Electrical Fundamentals
3.1 General Electrical Knowledge 3.2 Requirements for Electrical Installations (Article 110) 3.3 Electrical-Electronic Fundamentals & Theory
4 Branch Circuits & Load Calculations
4.1 Branch Circuit Requirements (Article 210) 4.2 Dwelling Load Calculations — Standard Method (Article 220 Part III) 4.3 Commercial & Multifamily Load Calculations (Article 220 Part III) 4.4 Neutral Loads & Optional Calculation Methods
5 Services & Feeders
5.1 Service Entrance Requirements (Article 230) 5.2 Feeder Requirements (Article 215) 5.3 Service & Feeder Sizing Calculations
6 Grounding & Bonding
6.1 Grounding Electrode Systems (Article 250 Part II) 6.2 Grounded Conductors & System Bonding (Article 250 Parts III-IV) 6.3 Equipment Grounding & Bonding (Article 250 Parts V-VIII) 6.4 Separately Derived Systems & Special Grounding
7 Conductors & Cables
7.1 Conductor Ampacity (Table 310.16) 7.2 Temperature Correction & Adjustment Factors (310.14/310.15) 7.3 Conductor Selection, Insulation & Parallel Conductors 7.4 Cable Types & Applications (NM, AC, MC, UF, SE)
8 Raceways & Boxes
8.1 Raceway Types & Selection (Articles 342-366) 8.2 Conduit Fill & Raceway Sizing (Chapter 9 Tables) 8.3 Box Sizing & Fill (Article 314) 8.4 Pull Boxes, Junction Boxes & Conduit Bodies
9 Motors, Transformers & Controls
9.1 Motor Branch Circuits & Short-Circuit Protection (Article 430 Part IV) 9.2 Motor Overload Protection (Article 430 Part III) 9.3 Motor Controllers, Circuits & Disconnects (Article 430 Parts II, VII, IX) 9.4 Transformers (Article 450)
10 Special Occupancies, Equipment & Signs
10.1 Hazardous (Classified) Locations (Article 500) 10.2 Garages, Bulk Storage, Health Care & Other Special Occupancies 10.3 Special Equipment (Pools, Industrial Machinery, Selected) 10.4 Electrical Signs & Outline Lighting (Article 600)
11 Utilization Equipment, Lighting & Low-Voltage
11.1 Utilization Equipment (Article 422) 11.2 Lighting & Luminaires (Article 410) 11.3 General Low Voltage Requirements (Article 725) 11.4 Communication Systems (Article 800) 11.5 Fire Detection & Alarm Systems (Article 760)
12 Electrical Safety
12.1 Shock Hazards & Safe Work Practices 12.2 Arc-Flash Hazards & NFPA 70E 12.3 Lockout/Tagout, PPE & Approach Boundaries
4.3 Commercial & Multifamily Load Calculations (Article 220 Part III)
Key Takeaways Explain This Topic AI
Table 220.12 gives unit lighting loads by non-dwelling occupancy in VA/sq ft — e.g., office/banks 1.3, retail 1.9, manufacturing 2.2, warehouse 1.2, hospitals 1.6, hotels/motels 1.7, courthouses 1.4, parking garages 0.3.
Non-dwelling receptacles are calculated at 180 VA per yoke [220.14(I)]; Table 220.44 allows 100% of the first 10,000 VA and 50% of the remainder.
Continuous loads in commercial installations must be sized at 125% on both conductors and overcurrent devices [210.19(A)(1), 210.20(A), 215.2(A)(1)].
Sign outlets are calculated at 1200 VA per outlet [220.14(F)]; show-window lighting uses 200 VA per linear foot [220.14(G)].
Multifamily dwellings with electric cooking and electric HVAC may use the optional method of 220.84 with Table 220.84 demand factors by number of units.
Last updated: August 2026
General Lighting Load by Occupancy (Table 220.12)
In the 2020 NEC, section 220.12 is titled Lighting Load for Non-Dwelling Occupancies and Table 220.12 is General Lighting Loads by Non-Dwelling Occupancy . The table was rebuilt around ASHRAE/IECC occupancy names, and dwelling units were taken out of it entirely — the 3 VA/sq ft dwelling figure now lives in 220.14(J). Some values fell and some rose, so never carry a 2017 number forward. Values worth being able to find in seconds:
- Occupancy VA/sq ft
- Office (banks are office-type, note d) 1.3
- Retail (stores, barber shops, beauty parlors, notes g and h) 1.9
- Courthouse 1.4
- Gymnasium (armories and auditoriums, note a) 1.7
- Hospital 1.6
- Hotel/motel (lodge rooms, note b) 1.7
- Manufacturing (industrial commercial loft buildings, note c) 2.2
- Parking garage (commercial storage garages, note e) 0.3
- Warehouse 1.2
The real table carries more rows than these — restaurants and clubs, schools, religious buildings, libraries, and others — and the exam is open-book, so read the value straight out of your own Table 220.12 instead of trusting a memorized figure. The footnotes carry as much weight as the numbers : they are what tell you a "store" is priced as retail and an "industrial commercial loft building" as manufacturing .
Floor area is taken from outside dimensions per 220.11, excluding open porches, garages, and unfinished spaces not adaptable for future use. The note to Table 220.12 states that the 125% continuous-load multiplier of 210.20(A) is already built into these unit loads , so do not apply it a second time. Under 220.12(B) , a building designed and constructed to an adopted energy code may instead be calculated with the energy code's unit values, but only where a power monitoring system continuously reports the building's total general lighting load, an alarm annunciates if that load exceeds the energy-code values, the 220.42 demand factors are not applied, and the 125% continuous multiplier is applied.
Receptacle Load (220.14(I))
Non-dwelling receptacle outlets are calculated at not less than 180 VA per yoke [ 220.14(I) ]. A duplex receptacle on one strap counts as 180 VA, not 360 VA. An assembly of four or more receptacles counts at 90 VA per receptacle.
Table 220.44 Demand Factors (Non-Dwelling Receptacles)
General-purpose receptacle loads and fixed multioutlet assemblies in non-dwelling occupancies may be reduced by Table 220.44 :
- Portion of Receptacle Load (VA) Demand Factor
- First 10,000 VA or less 100%
- Remainder over 10,000 VA 50%
Alternative: you may instead add receptacle VA to the general lighting load and apply Table 220.42 lighting demand factors to the combined total.
Worked Example — Receptacle Demand
150 receptacles × 180 VA = 27,000 VA. First 10,000 × 100% = 10,000; remaining 17,000 × 50% = 8500. Demand = 18,500 VA .
Continuous Loads at 125%
Commercial installations frequently have continuous loads (store lighting, signage, refrigeration). Per 210.19(A)(1) (conductors), 210.20(A) (overcurrent), and 215.2(A)(1) (feeders), size at 125% of the continuous portion. A 60A continuous lighting feeder needs 60 × 1.25 = 75A conductor and a 75A or larger breaker.
Motors, Signs, and Show Windows
Motors : motor loads are calculated per 430.22 at 125% of the motor's full-load current rating (FLC) for continuous-duty motors. A feeder supplying a motor plus other loads adds the motor load at 125% plus the other loads at 100%.
Sign outlets : 1200 VA per sign outlet [ 220.14(F) ].
Show windows : 200 VA per linear foot of show window [ 220.14(G) ] — often a trap question because candidates forget to convert linear feet to VA.
Worked Example — Retail Store Service Load
A 5000 sq ft retail store on 120/208V three-phase, with 80 receptacles, a 5 hp motor (FLC 15.2A at 208V, or roughly 5500 VA), and 40 ft of show window. All lighting is LED track (continuous).
Step 1 — General lighting (Table 220.12, retail = 1.9 VA/sq ft): 5000 × 1.9 = 9500 VA (no extra 125% multiplier — the note to Table 220.12 says it is already inside the unit load)
Step 2 — Receptacles (220.14(I)): 80 × 180 = 14,400 VA
Apply Table 220.44: first 10,000 × 100% = 10,000; remaining 4400 × 50% = 2200. Demand = 12,200 VA.
- Step 3 — Show window (220.14(G)): 40 ft × 200 VA/ft = 8000 VA
- Step 4 — Motor (430.22, 125%): 5500 VA × 1.25 = 6875 VA
- Step 5 — Total service load: 9500 + 12,200 + 8000 + 6875 = 36,575 VA
Step 6 — Convert to amps (208V three-phase, √3 = 1.732): 36,575 ÷ (208 × 1.732) = 36,575 ÷ 360.3 = 101.5 A → the next standard size in 240.6(A) is 110 A , so a 110A or 125A service.
Multifamily Dwellings (Standard Method)
Standard method for multifamily: calculate each unit individually per Part III (general lighting 3 VA/sq ft, small-appliance, laundry, appliances, dryer, range), then add common house loads (corridor lighting, parking, common laundry) calculated per Part III. Demand factors of 220.42 apply per unit; the optional 220.84 method (covered in 4.4) often yields a smaller building service when all units have electric cooking and HVAC.
Common Exam Traps
Using 3 VA/sq ft for a commercial space — that's the dwelling value in 220.14(J). Commercial uses Table 220.12 by occupancy, and in the 2020 edition a store is retail at 1.9 VA/sq ft, not the old 3.
Forgetting 125% on continuous commercial lighting and motors.
Counting a duplex receptacle as 360 VA — it's 180 VA per yoke, not per opening.
Forgetting show-window 200 VA/ft and sign 1200 VA/outlet.
Mixing up Table 220.42 (lighting, 35% tier) with Table 220.44 (non-dwelling receptacles, 50% over 10 kVA).