7.1 Conductor Ampacity (Table 310.16)

Virginia Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 Exam Facts, Format & Scoring 1.2 Eligibility, Application & Scheduling 1.3 Open-Book Strategy & Test-Taking

2 Virginia Board Regulations (18VAC50-30)

2.1 Definitions & Qualification for Licensure 2.2 Standards of Practice 2.3 Standards of Conduct & Revocation of Licensure 2.4 Renewal and Reinstatement

3 General Knowledge & Electrical Fundamentals

3.1 General Electrical Knowledge 3.2 Requirements for Electrical Installations (Article 110) 3.3 Electrical-Electronic Fundamentals & Theory

4 Branch Circuits & Load Calculations

4.1 Branch Circuit Requirements (Article 210) 4.2 Dwelling Load Calculations — Standard Method (Article 220 Part III) 4.3 Commercial & Multifamily Load Calculations (Article 220 Part III) 4.4 Neutral Loads & Optional Calculation Methods

5 Services & Feeders

5.1 Service Entrance Requirements (Article 230) 5.2 Feeder Requirements (Article 215) 5.3 Service & Feeder Sizing Calculations

6 Grounding & Bonding

6.1 Grounding Electrode Systems (Article 250 Part II) 6.2 Grounded Conductors & System Bonding (Article 250 Parts III-IV) 6.3 Equipment Grounding & Bonding (Article 250 Parts V-VIII) 6.4 Separately Derived Systems & Special Grounding

7 Conductors & Cables

7.1 Conductor Ampacity (Table 310.16) 7.2 Temperature Correction & Adjustment Factors (310.14/310.15) 7.3 Conductor Selection, Insulation & Parallel Conductors 7.4 Cable Types & Applications (NM, AC, MC, UF, SE)

8 Raceways & Boxes

8.1 Raceway Types & Selection (Articles 342-366) 8.2 Conduit Fill & Raceway Sizing (Chapter 9 Tables) 8.3 Box Sizing & Fill (Article 314) 8.4 Pull Boxes, Junction Boxes & Conduit Bodies

9 Motors, Transformers & Controls

9.1 Motor Branch Circuits & Short-Circuit Protection (Article 430 Part IV) 9.2 Motor Overload Protection (Article 430 Part III) 9.3 Motor Controllers, Circuits & Disconnects (Article 430 Parts II, VII, IX) 9.4 Transformers (Article 450)

10 Special Occupancies, Equipment & Signs

10.1 Hazardous (Classified) Locations (Article 500) 10.2 Garages, Bulk Storage, Health Care & Other Special Occupancies 10.3 Special Equipment (Pools, Industrial Machinery, Selected) 10.4 Electrical Signs & Outline Lighting (Article 600)

11 Utilization Equipment, Lighting & Low-Voltage

11.1 Utilization Equipment (Article 422) 11.2 Lighting & Luminaires (Article 410) 11.3 General Low Voltage Requirements (Article 725) 11.4 Communication Systems (Article 800) 11.5 Fire Detection & Alarm Systems (Article 760)

12 Electrical Safety

12.1 Shock Hazards & Safe Work Practices 12.2 Arc-Flash Hazards & NFPA 70E 12.3 Lockout/Tagout, PPE & Approach Boundaries

7.1 Conductor Ampacity (Table 310.16)

Key Takeaways Explain This Topic AI

NEC 2020 Table 310.16 lists allowable ampacities by conductor size (AWG/kcmil), material (copper, aluminum, copper-clad aluminum), and insulation temperature rating column (60°C, 75°C, 90°C) for not more than three current-carrying conductors at 30°C ambient.

110.14(C) caps the usable ampacity at the termination temperature rating: for circuits rated 100 A or less or conductors #1 AWG and smaller, use the 60°C column unless the equipment is marked for 75°C; for larger circuits, 75°C terminations are the norm.

240.4(D) small-conductor limits cap the overcurrent device regardless of the table ampacity: #14 Cu = 15 A, #12 Cu = 20 A, #10 Cu = 30 A (aluminum/copper-clad aluminum values are lower).

The 90°C column ampacity is only used as the starting point for derating (ambient + bundling), not for termination sizing.

Last updated: August 2026

How to Read NEC 2020 Table 310.16

Table 310.16 lists the allowable ampacity of insulated conductors rated up to 2000 V, in raceway or cable or earth, based on an ambient temperature of 30°C (86°F) and not more than three current-carrying conductors . The table is organized by three variables you must combine correctly:

Conductor size in AWG or kcmil (rows, from 18 AWG through 2000 kcmil).

Conductor material : copper (first block), aluminum or copper-clad aluminum (second block). The aluminum ampacities are roughly one size smaller than copper for the same AWG.

Insulation temperature rating column : 60°C, 75°C, or 90°C. Each column lists the insulation types that qualify (e.g., 60°C includes TW and UF; 75°C includes RHW, THW, THWN, XHHW; 90°C includes THHN, THWN-2, XHHW-2, RHH, RHW-2).

The 90°C column value is larger than the 75°C value, which is larger than the 60°C value for the same size — but you cannot simply pick the highest number. Termination limits (110.14(C)) decide which column actually governs the final circuit ampacity.

Copper Ampacity Excerpt (Table 310.16)

  • Size 60°C 75°C 90°C
  • 14 AWG* 15 A 20 A 25 A
  • 12 AWG* 20 A 25 A 30 A
  • 10 AWG* 30 A 35 A 40 A
  • 8 AWG 40 A 50 A 55 A
  • 6 AWG 55 A 65 A 75 A
  • 4 AWG 70 A 85 A 95 A
  • 2 AWG 95 A 115 A 130 A
  • 1/0 AWG 125 A 150 A 170 A
  • 4/0 AWG 195 A 230 A 260 A

Asterisked sizes are capped by the 240.4(D) small-conductor rule — see Section 7.3.

Termination Limits — 110.14(C)

The termination temperature rule is the most-tested ampacity concept on the Virginia journeyman exam. 110.14(C)(1)(a) requires that conductors be sized based on the temperature rating of the equipment terminations, not on the insulation rating printed on the wire:

For equipment rated 100 A or less or for conductors #1 AWG and smaller , use the 60°C column unless the equipment is marked 75°C .

For equipment rated above 100 A or for conductors larger than #1 AWG , use the 75°C column unless marked otherwise.

Because most residential circuit-breaker panels and device terminations are rated 60°C (or 75°C only when explicitly marked), a #6 THHN copper conductor on a 60 A breaker whose terminations are not marked 75°C must be sized using the 60°C column (#6 Cu = 55 A), even though THHN itself is a 90°C-rated insulation. You may use the 90°C ampacity as the starting point only for applying ambient and bundling derating factors (Section 7.2).

Worked Example: Sizing a 50 A Branch-Circuit Conductor

A 50 A continuous-duty circuit (say, a 9 kW electric range) uses standard circuit-breaker terminations rated for 60°C only.

Step 1 — Termination column. Equipment ≤100 A, not marked 75°C → use the 60°C column .

Step 2 — Find a size whose 60°C copper ampacity ≥50 A. From the excerpt: #6 Cu = 55 A (OK), #8 Cu = 40 A (too small).

Step 3 — Verify the overcurrent limit. A 50 A breaker protects #6 Cu (55 A ≥50 A), and 240.4(D) does not restrict #6, so the breaker can be 50 A. Answer: #6 AWG copper THWN (or THHN run at the 60°C column value).

If the breaker and panel were marked 75°C, you could use the 75°C column: #8 Cu = 50 A exactly, which would be acceptable on a 50 A device (assuming the calculated load is exactly 50 A and the next-size-up rule of 240.4(B) is not needed).

Why Termination Limits Cap the Column

The rule exists because a conductor's insulation may survive 90°C, but the lug or breaker terminal it lands on is usually listed only for 60°C or 75°C. Heat migrates from the copper into the lug, so 110.14(C) forbids loading a conductor above the ampacity in the column matching the lowest-rated termination, regardless of insulation rating. Equipment marked 75°C lets you use the 75°C column; otherwise the 60°C column governs for ≤100 A equipment.

Worked Example 2: 100 A Feeder — Copper vs Aluminum at 75°C

A 100 A feeder lands on a subpanel marked 75°C , so 110.14(C) allows sizing from the 75°C column .

#3 AWG copper THHN = 100 A at 75°C — matches the breaker exactly; 240.4(D) does not restrict #3. Acceptable.

#1 AWG aluminum = 100 A at 75°C — also matches (use lugs marked AL/AL-CU). Lighter and cheaper for long runs.

If the terminations were 60°C only, both drop to 85 A — too small — and you would step up to #1 Cu (110 A at 60°C) or 1/0 Al (100 A at 60°C).

Common Exam Traps

Picking the 90°C number directly. A #12 THHN Cu conductor is not a 30 A conductor on a 20 A breaker; 240.4(D) caps #12 Cu at 20 A and 110.14(C) usually forces the 60°C column (20 A) anyway.

Forgetting the 60°C column for ≤100 A equipment. The exam will offer THHN/THWN-2 in the answer choices to bait you into the 90°C ampacity.

Using aluminum ampacities for copper sizes. Always read the correct material block of the table.