7.3 Conductor Selection, Insulation & Parallel Conductors
Virginia Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Exam Facts, Format & Scoring 1.2 Eligibility, Application & Scheduling 1.3 Open-Book Strategy & Test-Taking
2 Virginia Board Regulations (18VAC50-30)
2.1 Definitions & Qualification for Licensure 2.2 Standards of Practice 2.3 Standards of Conduct & Revocation of Licensure 2.4 Renewal and Reinstatement
3 General Knowledge & Electrical Fundamentals
3.1 General Electrical Knowledge 3.2 Requirements for Electrical Installations (Article 110) 3.3 Electrical-Electronic Fundamentals & Theory
4 Branch Circuits & Load Calculations
4.1 Branch Circuit Requirements (Article 210) 4.2 Dwelling Load Calculations — Standard Method (Article 220 Part III) 4.3 Commercial & Multifamily Load Calculations (Article 220 Part III) 4.4 Neutral Loads & Optional Calculation Methods
5 Services & Feeders
5.1 Service Entrance Requirements (Article 230) 5.2 Feeder Requirements (Article 215) 5.3 Service & Feeder Sizing Calculations
6 Grounding & Bonding
6.1 Grounding Electrode Systems (Article 250 Part II) 6.2 Grounded Conductors & System Bonding (Article 250 Parts III-IV) 6.3 Equipment Grounding & Bonding (Article 250 Parts V-VIII) 6.4 Separately Derived Systems & Special Grounding
7 Conductors & Cables
7.1 Conductor Ampacity (Table 310.16) 7.2 Temperature Correction & Adjustment Factors (310.14/310.15) 7.3 Conductor Selection, Insulation & Parallel Conductors 7.4 Cable Types & Applications (NM, AC, MC, UF, SE)
8 Raceways & Boxes
8.1 Raceway Types & Selection (Articles 342-366) 8.2 Conduit Fill & Raceway Sizing (Chapter 9 Tables) 8.3 Box Sizing & Fill (Article 314) 8.4 Pull Boxes, Junction Boxes & Conduit Bodies
9 Motors, Transformers & Controls
9.1 Motor Branch Circuits & Short-Circuit Protection (Article 430 Part IV) 9.2 Motor Overload Protection (Article 430 Part III) 9.3 Motor Controllers, Circuits & Disconnects (Article 430 Parts II, VII, IX) 9.4 Transformers (Article 450)
10 Special Occupancies, Equipment & Signs
10.1 Hazardous (Classified) Locations (Article 500) 10.2 Garages, Bulk Storage, Health Care & Other Special Occupancies 10.3 Special Equipment (Pools, Industrial Machinery, Selected) 10.4 Electrical Signs & Outline Lighting (Article 600)
11 Utilization Equipment, Lighting & Low-Voltage
11.1 Utilization Equipment (Article 422) 11.2 Lighting & Luminaires (Article 410) 11.3 General Low Voltage Requirements (Article 725) 11.4 Communication Systems (Article 800) 11.5 Fire Detection & Alarm Systems (Article 760)
12 Electrical Safety
12.1 Shock Hazards & Safe Work Practices 12.2 Arc-Flash Hazards & NFPA 70E 12.3 Lockout/Tagout, PPE & Approach Boundaries
7.3 Conductor Selection, Insulation & Parallel Conductors
Key Takeaways Explain This Topic AI
Common insulation types: THWN/THWN-2 (75°C/90°C, wet or dry), THHN (90°C dry), XHHW/XHHW-2 (75°C/90°C wet or dry), USE-2 (90°C wet, underground), TW (60°C wet/dry); the suffix -2 means 90°C rating in wet locations.
Parallel conductors per 310.10(H) are permitted only for phase, neutral, and grounded conductors sized 1/0 AWG and larger; each parallel set must be same length, material, size, insulation type, and termination method.
240.4(D) caps overcurrent protection for small conductors: #14 Cu = 15 A, #12 Cu = 20 A, #10 Cu = 30 A; aluminum/copper-clad aluminum is lower (#12 Al = 15 A, #10 Al = 25 A).
Conductor DC resistance is in NEC Chapter 9, Table 8 (stranded copper values used for voltage-drop and fault-current estimates); the table distinguishes uncoated vs. coated copper.
Last updated: August 2026
Insulation Types and Where They May Be Used
NEC Article 310 organizes conductor insulations by temperature rating and by suitability for dry, damp, and wet locations. The letter codes encode this:
T = thermoplastic; R = thermoset (rubber-like); X = cross-linked synthetic polymer.
H = high heat (75°C); HH = higher heat (90°C); W = wet-location approved; -2 suffix = 90°C wet.
Common Insulations
- Type Temp Rating Suitable Locations
- TW 60°C Dry and wet
- THW 75°C Dry and wet
- THWN 75°C Dry and wet
- THWN-2 90°C Dry and wet
- THHN 90°C Dry (and damp)
- XHHW 75°C wet / 90°C dry Dry and wet
- XHHW-2 90°C Dry and wet
- USE-2 90°C wet Underground, direct burial (service entrance)
- RHW / RHW-2 75°C / 90°C Dry and wet
Note: THHN is 90°C dry only; in a wet location it is not rated for the full 90°C unless marked THWN-2 or XHHW-2. Conduits outdoors or underground are "wet locations," so a conductor used there must carry a W suffix or be listed for wet use at the applied temperature. The exam frequently tests this distinction.
Conductor Materials and Coating
Copper (Cu) — highest conductivity per size; the default for small conductors.
Aluminum (Al) — lighter and cheaper; requires larger size for the same ampacity and needs antioxidant compound at terminals unless listed.
Copper-clad aluminum (CCA) — aluminum core with copper cladding; ampacity is read from the Al/CCA block of Table 310.16.
Tin-coated ("tinned") copper — used in older installations and some marine/industrial; Chapter 9 Table 8 lists both coated and uncoated resistance values.
Small-Conductor Rule — 240.4(D)
Even when Table 310.16 and the termination rule allow a higher ampacity, 240.4(D) caps the overcurrent device for small conductors unless an exception in 240.4(E) or (G) applies (motor circuits, HVAC, fixture wires, fire pumps, etc.):
- Conductor Max OCPD (Cu) Max OCPD (Al or CCA)
- 18 AWG 7 A —
- 16 AWG 10 A —
- 14 AWG 15 A 15 A
- 12 AWG 20 A 15 A
- 10 AWG 30 A 25 A
This rule overrides the next-size-up allowance of 240.4(B) for small conductors. A #12 THHN Cu conductor might have a 75°C ampacity of 25 A and a 90°C ampacity of 30 A, but 240.4(D) still limits the breaker to 20 A for a standard branch circuit. Aluminum #12 is capped at 15 A and aluminum #10 at 25 A — a common trap.
Parallel Conductors — 310.10(H)
310.10(H) permits phase, neutral, and grounded conductors to be run in parallel only when each conductor is 1/0 AWG or larger . The rules for a parallel set (a single phase, neutral, or grounded conductor made up of multiple paralleled conductors):
Same length — the conductors in one set must be the same length to balance impedance.
Same conductor material — all copper or all aluminum, no mixing.
Same size in circular mil area — same AWG/kcmil.
Same insulation type — same temperature rating and dielectric.
Same termination method — set-screw or compression; do not mix.
Equipment grounding conductors run in parallel are sized per 250.122(F) and are not required to be 1/0 AWG or larger, but each parallel raceway or cable must contain an EGC. The phase, neutral, and EGC must be grouped so each raceway contains a full set per 300.3(B)(1) . Each current-carrying conductor of a paralleled set is counted as a current-carrying conductor for 310.15(C)(1) adjustment.
Why Parallel?
A 400 A service using a single 600 kcmil copper conductor is expensive, heavy, and hard to bend. Three parallel runs of 4/0 Cu (230 A each at 75°C × 3 = 690 A capacity, well above 400 A) are lighter, easier to pull, and cheaper — but only 1/0 AWG and larger can be paralleled, so 4/0 is legal and #2 is not.
Conductor Resistance — Chapter 9, Table 8
NEC Chapter 9, Table 8 lists DC resistance at 75°C for stranded and solid conductors, used for voltage-drop calcs and fault-current estimates. Key values for stranded copper at 75°C:
- Size Ω / 1000 ft (Cu, uncoated)
- 14 AWG 3.07
- 12 AWG 1.93
- 10 AWG 1.21
- 8 AWG 0.764
- 6 AWG 0.491
- 4 AWG 0.308
- 2 AWG 0.194
- 1/0 AWG 0.122
- 4/0 AWG 0.0766
Coated copper (tinned) has slightly higher resistance — read the correct column on the exam. Voltage drop is computed as VD = 2 × L × R × I / 1000 for single-phase, or VD = √3 × L × R × I / 1000 for three-phase.
Common Traps
Using 90°C THHN ampacity directly on a 20 A breaker. 240.4(D) caps #12 Cu at 20 A regardless of insulation.
Paralleling #2 AWG. Anything smaller than 1/0 AWG cannot be paralleled for phase/neutral conductors.
Mixing copper and aluminum in a parallel set. 310.10(H) requires identical material.
Forgetting the W suffix for wet locations. THHN alone is a dry/damp-location insulation; outdoors or underground needs THWN-2 or XHHW-2.