Study guide

7.2 Temperature Correction & Adjustment Factors (310.14/310.15)

Virginia Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 Exam Facts, Format & Scoring 1.2 Eligibility, Application & Scheduling 1.3 Open-Book Strategy & Test-Taking

2 Virginia Board Regulations (18VAC50-30)

2.1 Definitions & Qualification for Licensure 2.2 Standards of Practice 2.3 Standards of Conduct & Revocation of Licensure 2.4 Renewal and Reinstatement

3 General Knowledge & Electrical Fundamentals

3.1 General Electrical Knowledge 3.2 Requirements for Electrical Installations (Article 110) 3.3 Electrical-Electronic Fundamentals & Theory

4 Branch Circuits & Load Calculations

4.1 Branch Circuit Requirements (Article 210) 4.2 Dwelling Load Calculations — Standard Method (Article 220 Part III) 4.3 Commercial & Multifamily Load Calculations (Article 220 Part III) 4.4 Neutral Loads & Optional Calculation Methods

5 Services & Feeders

5.1 Service Entrance Requirements (Article 230) 5.2 Feeder Requirements (Article 215) 5.3 Service & Feeder Sizing Calculations

6 Grounding & Bonding

6.1 Grounding Electrode Systems (Article 250 Part II) 6.2 Grounded Conductors & System Bonding (Article 250 Parts III-IV) 6.3 Equipment Grounding & Bonding (Article 250 Parts V-VIII) 6.4 Separately Derived Systems & Special Grounding

7 Conductors & Cables

7.1 Conductor Ampacity (Table 310.16) 7.2 Temperature Correction & Adjustment Factors (310.14/310.15) 7.3 Conductor Selection, Insulation & Parallel Conductors 7.4 Cable Types & Applications (NM, AC, MC, UF, SE)

8 Raceways & Boxes

8.1 Raceway Types & Selection (Articles 342-366) 8.2 Conduit Fill & Raceway Sizing (Chapter 9 Tables) 8.3 Box Sizing & Fill (Article 314) 8.4 Pull Boxes, Junction Boxes & Conduit Bodies

9 Motors, Transformers & Controls

9.1 Motor Branch Circuits & Short-Circuit Protection (Article 430 Part IV) 9.2 Motor Overload Protection (Article 430 Part III) 9.3 Motor Controllers, Circuits & Disconnects (Article 430 Parts II, VII, IX) 9.4 Transformers (Article 450)

10 Special Occupancies, Equipment & Signs

10.1 Hazardous (Classified) Locations (Article 500) 10.2 Garages, Bulk Storage, Health Care & Other Special Occupancies 10.3 Special Equipment (Pools, Industrial Machinery, Selected) 10.4 Electrical Signs & Outline Lighting (Article 600)

11 Utilization Equipment, Lighting & Low-Voltage

11.1 Utilization Equipment (Article 422) 11.2 Lighting & Luminaires (Article 410) 11.3 General Low Voltage Requirements (Article 725) 11.4 Communication Systems (Article 800) 11.5 Fire Detection & Alarm Systems (Article 760)

12 Electrical Safety

12.1 Shock Hazards & Safe Work Practices 12.2 Arc-Flash Hazards & NFPA 70E 12.3 Lockout/Tagout, PPE & Approach Boundaries

7.2 Temperature Correction & Adjustment Factors (310.14/310.15)

Key Takeaways Explain This Topic AI

NEC 2020 Table 310.15(B)(1) gives ambient temperature correction factors applied to the 60/75/90°C column ampacity when ambient differs from 30°C; multiply the table ampacity by the factor in the column matching the conductor insulation rating.

NEC 2020 Table 310.15(C)(1) gives adjustment factors for more than three current-carrying conductors in a raceway or cable: 4-6 = 80%, 7-9 = 70%, 10-20 = 50%, 21-30 = 45%, 31-40 = 40%, 41+ = 35%.

Neutral conductors count as current-carrying conductors when they carry unbalanced current of a 3-wire circuit from a 4-wire 3-phase wye system, or when feeding nonlinear loads; equipment grounding conductors never count.

The sizing sequence is: (90°C ampacity × ambient correction × bundling adjustment) ≤ (termination-limited ampacity from 110.14(C)); the lower value governs.

Last updated: August 2026

Ambient Temperature Correction — Table 310.15(B)(1)

Table 310.16 is built on a 30°C (86°F) ambient . When the surrounding air, earth, or conduit environment is hotter or colder than 30°C, you must apply a correction factor from Table 310.15(B)(1) . The factor is read from the column that matches the conductor's insulation temperature rating (60°C, 75°C, or 90°C) — not the termination rating.

Excerpt of Table 310.15(B)(1) Correction Factors

  • Ambient °C 60°C col 75°C col 90°C col
  • 21-25 1.08 1.05 1.04
  • 26-30 (base) 1.00 1.00 1.00
  • 31-35 0.91 0.94 0.96
  • 36-40 0.82 0.88 0.91
  • 41-45 0.71 0.82 0.87
  • 46-50 0.58 0.75 0.82
  • 51-55 0.41 0.67 0.76

If ambient is below 30°C the factor is greater than 1.00, so ampacity increases — but the increase is capped by the termination temperature limit (you cannot uprate past the 60°C or 75°C termination ampacity). If ambient is above 30°C the factor is less than 1.00, so the conductor's ampacity drops.

Which Column?

The correction factor uses the insulation rating column , not the termination column. THHN/THWN-2 (90°C insulation) is always corrected from the 90°C column, even when the terminations force you to use the 60°C or 75°C ampacity for final sizing. This is why the 90°C column is called the "derating starting point."

Conductor-Count Adjustment — Table 310.15(C)(1)

When more than three current-carrying conductors are installed in a raceway or cable longer than 600 mm (24 in.), the Table 310.16 ampacity must be multiplied by an adjustment factor from Table 310.15(C)(1) (renumbered in NEC 2020 from the 2017 edition's 310.15(B)(3)(a)):

  • Current-Carrying Conductors Adjustment Factor
  • 1-3 100% (no adjustment)
  • 4-6 80%
  • 7-9 70%
  • 10-20 50%
  • 21-30 45%
  • 31-40 40%
  • 41 and above 35%
  • Counting Current-Carrying Conductors

The Informational Note in 310.15(C)(1) and the rules in 310.15(C)(1) explain what to count:

Ungrounded (hot) conductors — always count.

Neutral on a 3-wire circuit from a 4-wire, 3-phase wye system — count as a current-carrying conductor because harmonic current adds to the neutral.

Neutral of a balanced 3-wire single-phase circuit (e.g., a 120/240 V residential circuit) does not count — the neutral carries only the unbalanced load.

Neutral feeding nonlinear (harmonic) loads — count it.

Equipment grounding/bonding conductors — never count.

Spare conductors that are energized in the future — count.

Conductors not energized simultaneously (e.g., 3-way switch travelers, only one of which carries current at a time) — do not count.

The Full Derating Sequence

The correct sizing procedure combines both factors and the termination rule:

Look up the 90°C column ampacity from Table 310.16 (the derating starting point).

Multiply by the ambient correction factor from Table 310.15(B)(1) using the 90°C column factor.

Multiply by the adjustment factor from Table 310.15(C)(1).

Compare the derated result to the termination-limited ampacity (60°C or 75°C column from 110.14(C)).

The smaller value is the final allowable ampacity.

Worked Example: Six Current-Carrying #6 THHN Cu in 40°C Ambient

A conduit contains six #6 AWG copper THHN conductors (three two-wire circuits, neutral counted on each because the loads are nonlinear), in a boiler room with 40°C ambient. Terminations are on a 60 A breaker rated 75°C.

Step 1 — 90°C base ampacity. #6 Cu THHN = 75 A (90°C column).

Step 2 — Ambient correction. 40°C ambient, 90°C column factor = 0.91. 75 × 0.91 = 68.25 A .

Step 3 — Bundling adjustment. Six current-carrying conductors = 80%. 68.25 × 0.80 = 54.6 A .

Step 4 — Termination limit. Breaker rated 75°C → use 75°C column = 65 A for #6 Cu.

Step 5 — Compare. 54.6 A (derated) vs. 65 A (termination) → the smaller value governs → 54.6 A final ampacity .

The 60 A breaker is not allowed because the derated ampacity (54.6 A) is less than 60 A. You would need to either reduce the load, use a larger conductor (#4 Cu gives more headroom), or split the conductors into two raceways. Note that 240.4(B) next-size-up cannot help here because the derated ampacity (54.6 A) does not equal a standard breaker size and is below the 60 A rating.

Common Traps

Applying correction to the termination ampacity. The correction factor always multiplies the insulation-column (90°C) ampacity, not the 60°C or 75°C termination ampacity.

Forgetting to re-check the termination limit. After derating, the smaller of the derated ampacity and the termination ampacity wins — many candidates stop at the derated value.

Miscounting the neutral. A 3-wire circuit from a 4-wire wye counts the neutral; a 120/240 V single-phase circuit does not.