3.3 Electrical-Electronic Fundamentals & Theory
Virginia Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Exam Facts, Format & Scoring 1.2 Eligibility, Application & Scheduling 1.3 Open-Book Strategy & Test-Taking
2 Virginia Board Regulations (18VAC50-30)
2.1 Definitions & Qualification for Licensure 2.2 Standards of Practice 2.3 Standards of Conduct & Revocation of Licensure 2.4 Renewal and Reinstatement
3 General Knowledge & Electrical Fundamentals
3.1 General Electrical Knowledge 3.2 Requirements for Electrical Installations (Article 110) 3.3 Electrical-Electronic Fundamentals & Theory
4 Branch Circuits & Load Calculations
4.1 Branch Circuit Requirements (Article 210) 4.2 Dwelling Load Calculations — Standard Method (Article 220 Part III) 4.3 Commercial & Multifamily Load Calculations (Article 220 Part III) 4.4 Neutral Loads & Optional Calculation Methods
5 Services & Feeders
5.1 Service Entrance Requirements (Article 230) 5.2 Feeder Requirements (Article 215) 5.3 Service & Feeder Sizing Calculations
6 Grounding & Bonding
6.1 Grounding Electrode Systems (Article 250 Part II) 6.2 Grounded Conductors & System Bonding (Article 250 Parts III-IV) 6.3 Equipment Grounding & Bonding (Article 250 Parts V-VIII) 6.4 Separately Derived Systems & Special Grounding
7 Conductors & Cables
7.1 Conductor Ampacity (Table 310.16) 7.2 Temperature Correction & Adjustment Factors (310.14/310.15) 7.3 Conductor Selection, Insulation & Parallel Conductors 7.4 Cable Types & Applications (NM, AC, MC, UF, SE)
8 Raceways & Boxes
8.1 Raceway Types & Selection (Articles 342-366) 8.2 Conduit Fill & Raceway Sizing (Chapter 9 Tables) 8.3 Box Sizing & Fill (Article 314) 8.4 Pull Boxes, Junction Boxes & Conduit Bodies
9 Motors, Transformers & Controls
9.1 Motor Branch Circuits & Short-Circuit Protection (Article 430 Part IV) 9.2 Motor Overload Protection (Article 430 Part III) 9.3 Motor Controllers, Circuits & Disconnects (Article 430 Parts II, VII, IX) 9.4 Transformers (Article 450)
10 Special Occupancies, Equipment & Signs
10.1 Hazardous (Classified) Locations (Article 500) 10.2 Garages, Bulk Storage, Health Care & Other Special Occupancies 10.3 Special Equipment (Pools, Industrial Machinery, Selected) 10.4 Electrical Signs & Outline Lighting (Article 600)
11 Utilization Equipment, Lighting & Low-Voltage
11.1 Utilization Equipment (Article 422) 11.2 Lighting & Luminaires (Article 410) 11.3 General Low Voltage Requirements (Article 725) 11.4 Communication Systems (Article 800) 11.5 Fire Detection & Alarm Systems (Article 760)
12 Electrical Safety
12.1 Shock Hazards & Safe Work Practices 12.2 Arc-Flash Hazards & NFPA 70E 12.3 Lockout/Tagout, PPE & Approach Boundaries
3.3 Electrical-Electronic Fundamentals & Theory
Key Takeaways Explain This Topic AI
Ohm's law (E = I × R) and the power formulas (P = I × E, P = I² × R, P = E²/R) let you compute the fourth quantity when any two are known; the NEC exam frequently tests these in load and voltage-drop calculations.
In a series circuit, resistance adds (R_total = R1 + R2 + ...) and current is the same through every element while voltage divides; in a parallel circuit, voltage is the same across every branch and current divides while total conductance adds (1/R_total = 1/R1 + 1/R2 + ...).
Voltage drop on a 3-phase circuit is Vd = (√3 × L × I × R) / 1000; on a 1-phase circuit it is Vd = (2 × L × I × R) / 1000, where L is one-way length in feet and R is Ω per 1000 ft.
Power factor (PF = W/VA) is the ratio of real to apparent power; a 0.85 PF means only 85% of the supplied VA does useful work, and the NEC requires conductors and OCPDs to carry the full VA.
A transformer's voltage ratio equals its turns ratio: V_primary / V_secondary = N_primary / N_secondary, and the current ratio is inverse: I_primary × V_primary = I_secondary × V_secondary for an ideal transformer.
Last updated: August 2026
Why This Matters on the Exam
The NEC tells you what to install; theory tells you why the rules exist and lets you compute values the tables do not list. The Virginia Journeyman blueprint assigns 2 questions to Electrical-Electronic Fundamentals, but the formulas appear in every load calculation, voltage-drop, and transformer question on the rest of the exam. Skip this section and you will not be able to verify any answer arithmetically.
Ohm's Law
Ohm's law: E = I × R , where E is voltage in volts, I is current in amperes, and R is resistance in ohms. Rearrangements:
- I = E / R
- R = E / I
If a 120V circuit draws 12 A, the total resistance is R = 120 / 12 = 10 Ω. If the same circuit's resistance rises to 12 Ω (a loose connection), current falls to 10 A — the drop in current is a troubleshooting signal.
Power Formulas
The three power equations:
- P = I × E (power = current × voltage)
- P = I² × R (power lost as heat in resistance)
- P = E² / R (power from voltage across resistance)
A 120V heater drawing 12 A dissipates P = 12 × 120 = 1440 W. A 10 Ω resistor at 120V dissipates P = 120² / 10 = 1440 W — same answer, different entry point.
Series Circuits
In a series circuit:
Resistance adds : R_total = R1 + R2 + R3 + ...
Current is the same through every element.
Voltage divides across each resistor proportional to its resistance.
Three resistors (4 Ω, 6 Ω, 10 Ω) in series across 120 V: R_total = 20 Ω, I = 120/20 = 6 A. Voltage across the 10 Ω resistor = 6 × 10 = 60 V. Christmas-tree mini-lights are a classic series string — one open element kills the whole string.
Parallel Circuits
In a parallel circuit:
Voltage is the same across every branch.
Current divides among branches (inversely to resistance).
Conductance adds : 1/R_total = 1/R1 + 1/R2 + 1/R3 + ...
Two 10 Ω resistors in parallel: 1/R_total = 1/10 + 1/10 = 0.2, so R_total = 5 Ω — half of either resistor. A practical shortcut for two resistors: R_total = (R1 × R2) / (R1 + R2) = (10 × 10) / (10 + 10) = 100/20 = 5 Ω.
Series vs. Parallel at a Glance
Loading diagram...
The series loop carries 6 A through every resistor (20 Ω total); each parallel branch carries 12 A (120/10), for 24 A total at the source — the parallel circuit draws four times the series current.
Voltage Drop Calculation
The NEC recommends (Informational Notes, not enforceable) ≤3% voltage drop on branch circuits and ≤5% combined feeder + branch. The formula:
- 1-phase : Vd = (2 × L × I × R) / 1000
- 3-phase : Vd = (√3 × L × I × R) / 1000
Where L = one-way length in feet, I = load current in amperes, R = conductor resistance in Ω per 1000 ft (Chapter 9, Table 8 for copper; use AC values at 75°C for typical ampacity).
Worked Example: Voltage Drop and Parallel Resistance
Part A — Voltage drop. A 208V, 3-phase feeder carries 100 A for 150 ft through 1/0 AWG aluminum (≈0.201 Ω/kft at 75°C). Voltage drop:
Vd = (√3 × 150 × 100 × 0.201) / 1000 = (1.732 × 150 × 100 × 0.201) / 1000 ≈ 5.22 V
Percentage drop = 5.22 / 208 ≈ 2.5% — within the 3% feeder recommendation.
Part B — Parallel resistance. Two loads, 6 Ω and 12 Ω, share a 120V source. R_total = (6 × 12) / (6 + 12) = 72/18 = 4 Ω. Total current = 120/4 = 30 A; individual currents are 20 A (120/6) and 10 A (120/12), which sum to 30 A — Kirchhoff's current law verified.
AC vs. DC
Direct current (DC) flows in one direction at constant magnitude (batteries, solar PV). Alternating current (AC) reverses direction periodically; US power operates at 60 Hz (60 cycles/second). AC permits transformers to step voltage up for transmission and down for use; DC cannot be transformed directly. The NEC addresses AC and DC throughout — pay attention to which article applies (e.g., Article 690 for solar PV, Article 692 for fuel cells).
Single-Phase vs. Three-Phase
Single-phase, 2-wire, 120V — one ungrounded conductor and one grounded (neutral) conductor; serves small loads.
Single-phase, 3-wire, 120/240V — two ungrounded conductors 180° out of phase plus a neutral; common in dwellings (ranges, dryers use 240 V, lighting uses 120 V).
Three-phase, 4-wire, 208Y/120V — three ungrounded conductors 120° apart plus a neutral; common in commercial buildings.
Three-phase, 4-wire, 480Y/277V — common in industrial and large commercial; 277 V line-to-neutral serves lighting.
Three-phase delivers power more efficiently (three conductors carry the power of six) and produces a constant total power (no 120 Hz pulsation as in single-phase).
Power Factor and Efficiency
Power factor (PF) = W / VA , ranging 0 to 1.0. Resistive loads (heaters) have PF = 1.0; inductive loads (motors, ballasts) have PF < 1.0. A 10 kW motor at PF 0.8 draws 10,000 / 0.8 = 12,500 VA — the conductors and overcurrent device must carry the 12,500 VA equivalent current, not the 10 kW.
Efficiency (η) = P_out / P_in. A 5 HP motor (3730 W output) drawing 4500 W input has η = 3730/4500 ≈ 0.83 (83%). The 770 W difference is lost as heat.
Transformers: Turns Ratio
For an ideal transformer (no losses):
- V_primary / V_secondary = N_primary / N_secondary (turns ratio)
- I_primary × V_primary = I_secondary × V_secondary (power in = power out)
A 480V:120V transformer has a 4:1 turns ratio. If the secondary delivers 40 A at 120V (4800 VA), the primary draws 10 A at 480V (also 4800 VA). The VA is constant; only voltage and current trade. Real transformers have losses (core + copper) and efficiency typically 95–99%.