Study guide
9.2 Motor Overload Protection (Article 430 Part III)
Virginia Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Exam Facts, Format & Scoring 1.2 Eligibility, Application & Scheduling 1.3 Open-Book Strategy & Test-Taking
2 Virginia Board Regulations (18VAC50-30)
2.1 Definitions & Qualification for Licensure 2.2 Standards of Practice 2.3 Standards of Conduct & Revocation of Licensure 2.4 Renewal and Reinstatement
3 General Knowledge & Electrical Fundamentals
3.1 General Electrical Knowledge 3.2 Requirements for Electrical Installations (Article 110) 3.3 Electrical-Electronic Fundamentals & Theory
4 Branch Circuits & Load Calculations
4.1 Branch Circuit Requirements (Article 210) 4.2 Dwelling Load Calculations — Standard Method (Article 220 Part III) 4.3 Commercial & Multifamily Load Calculations (Article 220 Part III) 4.4 Neutral Loads & Optional Calculation Methods
5 Services & Feeders
5.1 Service Entrance Requirements (Article 230) 5.2 Feeder Requirements (Article 215) 5.3 Service & Feeder Sizing Calculations
6 Grounding & Bonding
6.1 Grounding Electrode Systems (Article 250 Part II) 6.2 Grounded Conductors & System Bonding (Article 250 Parts III-IV) 6.3 Equipment Grounding & Bonding (Article 250 Parts V-VIII) 6.4 Separately Derived Systems & Special Grounding
7 Conductors & Cables
7.1 Conductor Ampacity (Table 310.16) 7.2 Temperature Correction & Adjustment Factors (310.14/310.15) 7.3 Conductor Selection, Insulation & Parallel Conductors 7.4 Cable Types & Applications (NM, AC, MC, UF, SE)
8 Raceways & Boxes
8.1 Raceway Types & Selection (Articles 342-366) 8.2 Conduit Fill & Raceway Sizing (Chapter 9 Tables) 8.3 Box Sizing & Fill (Article 314) 8.4 Pull Boxes, Junction Boxes & Conduit Bodies
9 Motors, Transformers & Controls
9.1 Motor Branch Circuits & Short-Circuit Protection (Article 430 Part IV) 9.2 Motor Overload Protection (Article 430 Part III) 9.3 Motor Controllers, Circuits & Disconnects (Article 430 Parts II, VII, IX) 9.4 Transformers (Article 450)
10 Special Occupancies, Equipment & Signs
10.1 Hazardous (Classified) Locations (Article 500) 10.2 Garages, Bulk Storage, Health Care & Other Special Occupancies 10.3 Special Equipment (Pools, Industrial Machinery, Selected) 10.4 Electrical Signs & Outline Lighting (Article 600)
11 Utilization Equipment, Lighting & Low-Voltage
11.1 Utilization Equipment (Article 422) 11.2 Lighting & Luminaires (Article 410) 11.3 General Low Voltage Requirements (Article 725) 11.4 Communication Systems (Article 800) 11.5 Fire Detection & Alarm Systems (Article 760)
12 Electrical Safety
12.1 Shock Hazards & Safe Work Practices 12.2 Arc-Flash Hazards & NFPA 70E 12.3 Lockout/Tagout, PPE & Approach Boundaries
9.2 Motor Overload Protection (Article 430 Part III)
Key Takeaways Explain This Topic AI
Overload protection is sized from the motor nameplate FLA per 430.6(A)(2) and 430.32 — the opposite of conductor/OCPD sizing, which uses Table FLC.
For continuous-duty motors, 430.32(A)(1) limits the overload device to 125% of nameplate FLA when the motor has a service factor of 1.15 or greater (or a temperature rise of 40°C or less), and 115% of nameplate FLA for all other motors.
If the overload sized at 125% or 115% will not let the motor start or carry the load, 430.32(C) permits raising the trip rating up to 140% (SF ≥ 1.15 or temp rise ≤ 40°C) or 130% (all other motors).
Overload protection guards the motor against sustained overcurrent above its running rating; it is distinct from the branch-circuit short-circuit/ground-fault device, which guards the conductors and the motor circuit against fault-level current.
Intermittent-duty motors (430.32(B)) and torque motors (430.32(D)) have different rules; exam questions almost always involve continuous-duty motors, so identify duty before applying the 125%/115% rule.
Last updated: August 2026
Overload vs. Short-Circuit Protection — Two Different Jobs
A motor circuit has two protective zones, and confusing them is the classic exam trap:
Branch-circuit short-circuit/ground-fault protection (430.52, Table 430.52) protects the conductors and the motor circuit against fault-level current. It is sized from the Table FLC (430.6(A)(1)) and can be 250% or more of FLC — high enough to ride out inrush.
Motor running overload protection (430.32) protects the motor against sustained current slightly above its nameplate rating that would overheat the insulation over minutes or hours. It is sized from the motor nameplate FLA (430.6(A)(2)) and is set tightly — typically 115% or 125%.
A combination starter (contactor + overload block + OCPD in one listed enclosure) handles both jobs, but the calculations are independent.
The 125% vs. 115% Rule — 430.32(A)(1)
For continuous-duty motors rated more than 1 hp without integral thermal protection, 430.32(A)(1) sets the maximum separate overload device rating as a percentage of motor nameplate FLA :
- Motor Characteristic Max Overload (% of nameplate FLA)
- Service factor ≥ 1.15 (or temperature rise ≤ 40°C ) 125%
- All other motors (SF < 1.15 and temp rise > 40°C) 115%
The service factor is the safety margin printed on the nameplate (e.g., SF 1.15 means the motor can carry 15% above rated horsepower intermittantly). A motor with a 1.15 service factor can tolerate a slightly higher overload trip setting because its thermal headroom is larger.
Worked Example — SF 1.15 Motor, Nameplate 17 A
Determine the multiplier: SF 1.15 ≥ 1.15 → use 125% .
Overload trip rating = 17 A × 1.25 = 21.25 A .
Select the next lower standard overload heater or selectable electronic trip rating that does not exceed 21.25 A (e.g., a 21 A overload block). If the motor will not start with that setting, 430.32(C) allows raising it toward 140% of nameplate (17 × 1.40 = 23.8 A) — but never above.
Worked Example — SF 1.0 Motor, Nameplate 26 A (Separate Overload Relay)
Read the nameplate: SF 1.0, temperature rise > 40°C → use the 115% column of 430.32(A)(1).
Maximum trip rating = 26 × 1.15 = 29.9 A .
Selecting a separate overload relay. Overload relays come as bimetallic heater elements (sized from a manufacturer's chart) or electronic overloads with a dial or DIP-switch range. For a bimetallic heater, look up the element rated at or below 29.9 A — if the nearest available heaters are 28 A and 32 A, pick the 28 A heater (next lower size), because 430.32 caps the rating at 115% of nameplate and you may not exceed it. For an electronic overload with 0.1 A steps, set the dial at 29.9 A or the next lower setting (e.g., 29.5 A).
Start-up bump (430.32(C)). If the motor will not start at that setting, raise the trip rating toward the 130% ceiling for SF < 1.15 motors: 26 × 1.30 = 33.8 A , and no higher. The 140% ceiling applies only to motors with SF ≥ 1.15 or temp rise ≤ 40°C.
Where the Nameplate Comes From
The motor nameplate FLA reflects the actual motor design at its rated voltage, frequency, and duty. Two 10 hp motors from different manufacturers can have slightly different nameplate FLA values — that is exactly why 430.6(A)(2) uses nameplate for overload (the protection must track the actual motor's heating) while 430.6(A)(1) uses the Table value for everything else (replacement motors must still have adequate conductor and short-circuit protection).
Continuous Duty vs. Intermittent Duty
430.32(A) covers continuous-duty motors — the default assumption on the exam. Intermittent-duty motors (short-time rated motors such as hoists, valve actuators, or crane motors) are covered by 430.32(B) and are sized to the duty-cycle nameplate current, with different — often higher — permitted percentages. Always confirm duty classification on the nameplate before applying the 125%/115% rule. If a question gives you only horsepower and voltage with no duty statement, assume continuous duty.
Integral Thermal Protection
Some motors carry internal thermal protectors (TP motors per 430.32(A)(2)–(A)(4)). When the motor is marked to indicate that integral protection complies with 430.32, separate overload protection is not required. The exam will usually ask whether separate overload protection is required — read the nameplate marking first.
Why Overload and Branch Protection Are Both Required
A frequent error is treating the overload relay and the branch-circuit OCPD as interchangeable — they are not. The overload relay (430.32) is a slow, low-magnitude device: it trips after seconds-to-minutes of current 115–125% above nameplate, protecting the motor's insulation from cumulative heating. The branch-circuit OCPD (430.52) is a fast, high-magnitude device: it clears in cycles when current reaches 250% (breaker) or 175% (fuse) of Table FLC, protecting conductors against bolted faults. A motor can run at 130% of nameplate indefinitely without tripping a 250% inverse-time breaker — which is why the Code requires both devices in series. The two occupy different parts of the time-current curve and neither substitutes for the other.
Common Exam Traps
Using Table FLC instead of nameplate FLA for overload sizing — wrong current.
Applying 125% to a motor with SF 1.0 — should be 115%.
Forgetting the 430.32(C) start-up bump and insisting the original setting is the only permitted value.
Treating overload protection as a substitute for branch-circuit short-circuit protection — they are independent and both are required.
Quick Check
If a question gives you a 15 hp, 460V, 3-phase motor with nameplate 19 A and SF 1.15:
Conductor ampacity uses Table FLC 21 A × 1.25 = 26.25 A → #10 AWG.
Breaker uses Table FLC 21 A × 2.50 = 52.5 A → 60 A (next standard up).
Overload uses nameplate 19 A × 1.25 = 23.75 A → 23 A overload block.
Three different starting currents, three different devices — and the exam loves to mix them.