8.1 Raceway Types & Selection (Articles 342-366)
Virginia Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Exam Facts, Format & Scoring 1.2 Eligibility, Application & Scheduling 1.3 Open-Book Strategy & Test-Taking
2 Virginia Board Regulations (18VAC50-30)
2.1 Definitions & Qualification for Licensure 2.2 Standards of Practice 2.3 Standards of Conduct & Revocation of Licensure 2.4 Renewal and Reinstatement
3 General Knowledge & Electrical Fundamentals
3.1 General Electrical Knowledge 3.2 Requirements for Electrical Installations (Article 110) 3.3 Electrical-Electronic Fundamentals & Theory
4 Branch Circuits & Load Calculations
4.1 Branch Circuit Requirements (Article 210) 4.2 Dwelling Load Calculations — Standard Method (Article 220 Part III) 4.3 Commercial & Multifamily Load Calculations (Article 220 Part III) 4.4 Neutral Loads & Optional Calculation Methods
5 Services & Feeders
5.1 Service Entrance Requirements (Article 230) 5.2 Feeder Requirements (Article 215) 5.3 Service & Feeder Sizing Calculations
6 Grounding & Bonding
6.1 Grounding Electrode Systems (Article 250 Part II) 6.2 Grounded Conductors & System Bonding (Article 250 Parts III-IV) 6.3 Equipment Grounding & Bonding (Article 250 Parts V-VIII) 6.4 Separately Derived Systems & Special Grounding
7 Conductors & Cables
7.1 Conductor Ampacity (Table 310.16) 7.2 Temperature Correction & Adjustment Factors (310.14/310.15) 7.3 Conductor Selection, Insulation & Parallel Conductors 7.4 Cable Types & Applications (NM, AC, MC, UF, SE)
8 Raceways & Boxes
8.1 Raceway Types & Selection (Articles 342-366) 8.2 Conduit Fill & Raceway Sizing (Chapter 9 Tables) 8.3 Box Sizing & Fill (Article 314) 8.4 Pull Boxes, Junction Boxes & Conduit Bodies
9 Motors, Transformers & Controls
9.1 Motor Branch Circuits & Short-Circuit Protection (Article 430 Part IV) 9.2 Motor Overload Protection (Article 430 Part III) 9.3 Motor Controllers, Circuits & Disconnects (Article 430 Parts II, VII, IX) 9.4 Transformers (Article 450)
10 Special Occupancies, Equipment & Signs
10.1 Hazardous (Classified) Locations (Article 500) 10.2 Garages, Bulk Storage, Health Care & Other Special Occupancies 10.3 Special Equipment (Pools, Industrial Machinery, Selected) 10.4 Electrical Signs & Outline Lighting (Article 600)
11 Utilization Equipment, Lighting & Low-Voltage
11.1 Utilization Equipment (Article 422) 11.2 Lighting & Luminaires (Article 410) 11.3 General Low Voltage Requirements (Article 725) 11.4 Communication Systems (Article 800) 11.5 Fire Detection & Alarm Systems (Article 760)
12 Electrical Safety
12.1 Shock Hazards & Safe Work Practices 12.2 Arc-Flash Hazards & NFPA 70E 12.3 Lockout/Tagout, PPE & Approach Boundaries
8.1 Raceway Types & Selection (Articles 342-366)
Key Takeaways Explain This Topic AI
RMC (Article 344) and IMC (Article 342) are threaded metal raceways approved for underground, concrete, and physical-damage locations; EMT (Article 358) is thin-wall, unthreaded, and NOT permitted where subject to severe physical damage.
PVC Schedule 40 (Article 352) is corrosion-proof and approved for underground use, but Schedule 80 is required where the conduit is subject to physical damage.
FMC (Article 348) has the tightest support spacing of common metal raceways: secured within 1 ft of termination and supported every 4.5 ft maximum.
ENT (Article 362) is a pliable corrugated nonmetallic raceway permitted only in concealed locations — never exposed or outdoors.
EMT, RMC, and IMC are each secured within 3 ft of termination and supported at intervals not exceeding 10 ft; if structural members prevent 3-ft securing, 5 ft is allowed for these three metal types.
Last updated: August 2026
Why Raceway Selection Matters on the Exam
A raceway is an enclosed channel designed expressly for holding conductors. The NEC defines nine common raceway types across Articles 342 through 366, and the Virginia Journeyman exam expects you to know which type belongs in which environment, what Article governs it, and how it must be supported. Choosing the wrong raceway for a wet location or an area exposed to physical damage is a common exam trap — the answer options will all "work" electrically, but only one complies with the Code for the stated condition.
Metal Raceways
Rigid Metal Conduit (RMC) — Article 344: Threaded, thick-wall steel or aluminum conduit. RMC is the most mechanically rugged raceway and is permitted in almost any location: underground, in concrete slabs, exposed to physical damage, wet, corrosive (with proper coating), and hazardous locations. RMC is the default answer when a question describes severe physical abuse or direct burial without additional protection.
Intermediate Metal Conduit (IMC) — Article 342: Threaded like RMC but with a thinner wall — about halfway between RMC and EMT. IMC is lighter and less expensive than RMC while still permitted in most of the same locations, including underground and in concrete. IMC cannot be used where it will be subject to severe physical damage unless it qualifies under the exceptions in 342.10.
Electrical Metallic Tubing (EMT) — Article 358: Thin-wall, unthreaded metallic tubing joined by setscrew or compression fittings. EMT is the workhorse of commercial and residential indoor wiring. It is not permitted "where subject to severe physical damage" per 358.12(1), though it can be used under floors where adequately protected. EMT is the most common raceway answer for indoor, non-hazardous, non-abuse installations.
Flexible Metal Conduit (FMC) — Article 348: A helically wound, flexible metal raceway used to connect equipment that vibrates or moves, such as motors and transformers. FMC is not a substitute for fixed raceway in most permanent runs. Its flexibility comes with restrictions: FMC has a tighter support spacing (4.5 ft maximum per 348.30) and a 1-ft secure-within requirement at terminations.
Liquidtight Flexible Metal Conduit (LFMC) — Article 350: Like FMC but with a liquidtight plastic jacket, making it suitable for wet locations and outdoor equipment connections. Common for air conditioner disconnects and pump connections.
Nonmetallic Raceways
Rigid PVC Conduit (Schedule 40 and 80) — Article 352: A nonmetallic, corrosion-proof raceway widely used underground and in wet or corrosive environments. Schedule 40 is the standard wall; Schedule 80 has thicker walls and is required where the conduit is "subject to physical damage" per 352.10(F). PVC expands and contracts significantly with temperature, so expansion fittings per 352.44 are required when the expected length change reaches ¼ inch or more. Support spacing varies by trade size — consult Table 352.30, not a fixed 10 ft.
Reinforced Thermosetting Resin Conduit (RTRC) — Article 355: Fiberglass conduit, electrically nonconductive and corrosion-resistant. Similar in application to PVC but can be used in some physical-damage locations where PVC Schedule 40 cannot.
Liquidtight Flexible Nonmetallic Conduit (LFNC) — Article 356: A flexible, liquidtight, nonmetallic raceway for wet, damp, or corrosive environments where flexibility is needed. Common in chemical plants and outdoor equipment.
Electrical Nonmetallic Tubing (ENT) — Article 362: A pliable, corrugated raceway used only in concealed locations — behind walls, in floors, or above ceilings. ENT is not permitted in exposed locations subject to physical damage per 362.12(1) and cannot be used outdoors.
Selection by Environment
- Environment Recommended Raceways Article
- Indoor, no physical damage EMT, RMC, IMC 358, 344, 342
- Underground / in concrete RMC, IMC, PVC Sch 40, RTRC 344, 342, 352, 355
- Wet / damp / corrosive PVC, RTRC, LFMC, LFNC 352, 355, 350, 356
- Exposed to physical damage RMC, IMC, PVC Sch 80, RTRC 344, 342, 352, 355
- Vibration / equipment connection FMC, LFMC, LFNC 348, 350, 356
- Concealed only ENT 362
- Trade Sizes
Raceway trade sizes use the same nominal system across types: 1/2, 3/4, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3, 3-1/2, 4, 5, and 6 inches. Metric designators (16, 21, 27, 35, 41, 53, 63, 78, 91, 103, 129, 155) appear alongside trade sizes in the NEC. A trade size 3/4 EMT and a trade size 3/4 RMC have the same nominal trade size but different internal diameters — which matters for conduit fill calculations.
Supports and Spacing
Support rules are exam favorites because they are article-specific and easy to test:
- Raceway Article Secure Within Max Support Spacing
- RMC 344 3 ft of termination 10 ft
- IMC 342 3 ft of termination 10 ft
- EMT 358 3 ft of termination 10 ft
- FMC 348 1 ft of termination 4.5 ft
- PVC Sch 40 352 3 ft of termination Per Table 352.30
The 3-ft termination rule has an exception: if structural framing prevents securing within 3 ft, you may secure within 5 ft for RMC, IMC, and EMT. FMC has no such exception — its 1-ft rule is strict. Horizontal runs through bored or punched framing members count as supported at those points, but the raceway must still be secured within the required distance of terminations.
Number of Conductors in One Raceway — Overview
How many conductors fit in a given raceway is governed by Chapter 9, Table 1 fill limits, detailed in the next section. The key concept: every conductor — including the equipment grounding conductor — occupies physical space, and the total cross-sectional area of all conductors cannot exceed the permitted fill percentage of the raceway's internal area.
Exam Traps
PVC Schedule 40 vs 80 : A question will describe "subject to physical damage" — Schedule 40 alone does not qualify; you need Schedule 80.
EMT in physical-damage areas : EMT is NOT permitted where subject to severe physical damage. If the scenario describes a warehouse floor or loading dock, EMT is wrong.
ENT outdoors or exposed : ENT is concealed-only and never permitted in exposed or outdoor locations.
FMC support spacing : FMC's 4.5-ft maximum is the tightest of all metal raceways. Do not confuse it with EMT's 10 ft.
Article number confusion : RMC is Article 344, not 342. Article 342 is IMC. The exam may list both as distractors.