11.3 General Low Voltage Requirements (Article 725)
Virginia Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Exam Facts, Format & Scoring 1.2 Eligibility, Application & Scheduling 1.3 Open-Book Strategy & Test-Taking
2 Virginia Board Regulations (18VAC50-30)
2.1 Definitions & Qualification for Licensure 2.2 Standards of Practice 2.3 Standards of Conduct & Revocation of Licensure 2.4 Renewal and Reinstatement
3 General Knowledge & Electrical Fundamentals
3.1 General Electrical Knowledge 3.2 Requirements for Electrical Installations (Article 110) 3.3 Electrical-Electronic Fundamentals & Theory
4 Branch Circuits & Load Calculations
4.1 Branch Circuit Requirements (Article 210) 4.2 Dwelling Load Calculations — Standard Method (Article 220 Part III) 4.3 Commercial & Multifamily Load Calculations (Article 220 Part III) 4.4 Neutral Loads & Optional Calculation Methods
5 Services & Feeders
5.1 Service Entrance Requirements (Article 230) 5.2 Feeder Requirements (Article 215) 5.3 Service & Feeder Sizing Calculations
6 Grounding & Bonding
6.1 Grounding Electrode Systems (Article 250 Part II) 6.2 Grounded Conductors & System Bonding (Article 250 Parts III-IV) 6.3 Equipment Grounding & Bonding (Article 250 Parts V-VIII) 6.4 Separately Derived Systems & Special Grounding
7 Conductors & Cables
7.1 Conductor Ampacity (Table 310.16) 7.2 Temperature Correction & Adjustment Factors (310.14/310.15) 7.3 Conductor Selection, Insulation & Parallel Conductors 7.4 Cable Types & Applications (NM, AC, MC, UF, SE)
8 Raceways & Boxes
8.1 Raceway Types & Selection (Articles 342-366) 8.2 Conduit Fill & Raceway Sizing (Chapter 9 Tables) 8.3 Box Sizing & Fill (Article 314) 8.4 Pull Boxes, Junction Boxes & Conduit Bodies
9 Motors, Transformers & Controls
9.1 Motor Branch Circuits & Short-Circuit Protection (Article 430 Part IV) 9.2 Motor Overload Protection (Article 430 Part III) 9.3 Motor Controllers, Circuits & Disconnects (Article 430 Parts II, VII, IX) 9.4 Transformers (Article 450)
10 Special Occupancies, Equipment & Signs
10.1 Hazardous (Classified) Locations (Article 500) 10.2 Garages, Bulk Storage, Health Care & Other Special Occupancies 10.3 Special Equipment (Pools, Industrial Machinery, Selected) 10.4 Electrical Signs & Outline Lighting (Article 600)
11 Utilization Equipment, Lighting & Low-Voltage
11.1 Utilization Equipment (Article 422) 11.2 Lighting & Luminaires (Article 410) 11.3 General Low Voltage Requirements (Article 725) 11.4 Communication Systems (Article 800) 11.5 Fire Detection & Alarm Systems (Article 760)
12 Electrical Safety
12.1 Shock Hazards & Safe Work Practices 12.2 Arc-Flash Hazards & NFPA 70E 12.3 Lockout/Tagout, PPE & Approach Boundaries
11.3 General Low Voltage Requirements (Article 725)
Key Takeaways Explain This Topic AI
Article 725 covers Class 1, Class 2, and Class 3 circuits that are not part of appliance wiring or Article 760/800 circuits.
Class 1 circuits (725.41) come in two flavors: power-limited (≤ 30 V, ≤ 1,000 VA) and remote-control/signaling (≤ 600 V, no power limit) — both are wired like power circuits.
Class 2 circuits are inherently power-limited (typically ≤ 100 VA / 24 V) and are the backbone of doorbells, thermostats, and low-voltage lighting control; common cable is CL2/CL3.
Class 3 circuits carry higher voltage than Class 2 but with rated cable; they are used for sound/security systems where shock hazard exists but fire hazard is limited.
Per 725.136, Class 2 and Class 3 circuits must be separated from power and Class 1 circuits by barriers or by 2 in. spacing unless specifically permitted to share a raceway.
Last updated: August 2026
Scope of Article 725
Article 725 covers circuits that are not used for appliance wiring (Article 422), fire alarm (Article 760), or communications (Article 800/805). The circuits it governs are remote-control , signaling , and power-limited circuits — the wiring behind doorbells, thermostats, security sensors, HVAC control, and sound systems. The exam divides these into three classes by voltage and power limits.
Class 1, 2, 3 Definitions — 725.41 and Article 100
Class Voltage limit Power limit Typical use Wiring treatment
Class 1 — Power-Limited [725.41(A)] ≤ 30 V ≤ 1,000 VA Low-voltage motors, remote-controlled window blinds Like power circuits
Class 1 — Remote-Control/Signaling [725.41(B)] ≤ 600 V None HVAC control, relay logic Like power circuits
Class 2 Per Chapter 9 Table 11(A)/11(B) — typically ≤ 30 V AC or 60 V DC and ≤ 100 VA Inherently limited by the power supply Doorbells, thermostats, networking, low-voltage lighting controls Lighter cable (CL2, CL3) permitted
Class 3 Higher than Class 2 voltage but still power-limited (≤ 100 V, with current limits per Table 11) Inherently limited Sound systems, security circuits where shock hazard exists Rated cable required (CL3, CL3R, CL3P)
Class 1 — 725.41(A) and (B)
Class 1 circuits are not considered safe from fire or shock initiation on their own. They are installed using the same wiring methods as power circuits (Chapter 3 wiring methods like EMT, MC, FMC, NM). 725.41(A) power-limited circuits are limited to 30 V maximum and 1,000 VA output. 725.41(B) remote-control and signaling circuits may operate up to 600 V with no power-output limit, and are treated as power circuits for installation purposes. Overcurrent protection for Class 1 circuits follows 725.23 (limited to conductor ampacity per Table 310.16; for 18 AWG no more than 7 A, for 16 AWG no more than 10 A).
Class 2 — The Doorbell Standard
A Class 2 circuit is the portion of the wiring system on the load side of a Class 2 power supply — a listed supply whose output is inherently limited so that it is safe from a fire-initiation standpoint and presents an acceptable shock hazard. The classic limit is 100 VA at 24 V (a 24 V / 4.16 A doorbell transformer is a Class 2 supply). Common cable types are CL2 and CL3 (general purpose), with riser (CL2R/CL3R) and plenum (CL2P/CL3P) variants for vertical and air-handling runs.
Class 3 — Higher Voltage, Still Power-Limited
A Class 3 circuit permits higher voltage (up to 100 V) than Class 2 but with current limits that keep it power-limited. It is used where the higher voltage would present a shock hazard (sound systems, security alarm loops). The cable must be CL3-rated or better — Class 2 cable cannot substitute for a Class 3 circuit.
Permitted Wiring Methods and Cable Types
- Circuit Permitted cables Raceway
- Class 1 Same as power wiring (NM, MC, AC, FMC, EMT, RMC) Chapter 3 methods required
- Class 2 / Class 3 CL2, CL3, CL2P, CL3P, CL2R, CL3R, PLTC May use Chapter 3 raceways; PLTC cable for industrial
Power-limited tray cable (PLTC) PLTC, PLTC-ER for exposed runs Tray, raceway, or cable tray in industrial occupancies
725.121 lists the power sources permitted for Class 2 and Class 3 circuits. 725.130 restricts installation: Class 2 and Class 3 circuits shall not be placed in the same raceway, cable, enclosure, or fitting with power or Class 1 conductors unless separated by a barrier .
Separation from Power Circuits — 725.136
725.136 is the central separation rule. Key provisions:
725.136(A) — Class 2 and Class 3 conductors shall not be placed in the same raceway, cable, enclosure, or fitting with conductors of electric power, lighting, or Class 1 circuits.
Exceptions: (1) separated by a listed barrier or divider ; (2) power conductors introduced only to supply Class 2/3 equipment and separated by at least ¼ in. (6 mm) from the low-voltage conductors; (3) in a manhole with fixed spacing.
725.136(B) — in cable trays, Class 2/3 cables must be separated from power cables by a solid fixed barrier .
725.136(C) — underground installations must maintain a minimum 12 in. spacing where Class 2/3 and power conductors share a trench.
Worked Example: Doorbell Wiring
A 16 V / 10 VA doorbell transformer is a Class 2 power supply — its output is below the 30 V and 100 VA limits. The button wiring from the transformer to the chime is therefore a Class 2 circuit and may be run as CL2 cable (a small, two-conductor jacketed cable). It cannot be run in the same NM-B sheath as the 120 V lighting circuit feeding the transformer. The 120 V primary side is a standard power circuit; the 16 V secondary side is Class 2.
Worked Example: HVAC Thermostat Control
A modern HVAC control circuit carrying 24 V AC at <100 VA from a transformer inside the air handler to the wall thermostat is Class 2 . The cable must be CL2 or CL3 . If the installer routes the thermostat cable through the same conduit as the 240 V condenser conductors, the installation violates 725.136(A) unless a listed barrier separates the two. The correct approach is to run the Class 2 cable in its own raceway or use a separate sleeve.
Exam Traps
Treating a Class 1 remote-control circuit as "low voltage" and wiring it with thermostat wire — wrong. Class 1 is wired like power.
Running Class 2 and power conductors in the same NM cable — violates 725.136(A) unless a barrier is present.
Using CL2 cable for a Class 3 sound system — wrong; Class 3 requires CL3-rated cable.
Assuming any 24 V circuit is Class 2 — only true if the power supply is listed as Class 2 (≤ 100 VA). A 24 V / 10 A supply is not Class 2.