9.2 Air Gaps, Atmospheric Vacuum Breakers & Hose Connection Protection
Virginia Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Virginia Licensing Law & Standards of Practice
1.1 Exam Format, Permitted References & Open-Book Strategy 1.2 Definitions, Licensure Requirement & Qualification for the Exam 1.3 Standards of Practice: Designations, Address Changes & License Use 1.4 Standards of Conduct, Prohibited Acts & Revocation of Licensure
2 Chapter 2: Renewal, USBC Administration & General Regulations
2.1 License Renewal, Continuing Education & Reinstatement 2.2 Virginia USBC Administration, Permits, Inspections & Required Tests 2.3 General Regulations: Materials, Protection, Support, Trenching & Structural Safety
3 Chapter 3: Plumbing Fixtures, Clearances & Temperature Control
3.1 Minimum Plumbing Facilities: Table 403.1, Calculations & Separate Facilities 3.2 Fixture Installation: Clearances, Compartments, Connections, Showers & Accessibility 3.3 Water Conservation, Temperature-Limiting Devices, Flushing Devices & Emergency Fixtures
4 Chapter 4: Fixture Traps, Trap Seals & Interceptors
4.1 Fixture Traps, Trap Seals & Trap Seal Protection 4.2 Grease Interceptors: Where Required, Sizing, Flow Control & Virginia's Disposer Rule 4.3 Oil Separators, Sand & Lint Interceptors, Other Interceptors & Corrosive Waste
5 Chapter 5: Sanitary Drainage Systems & Sizing
5.1 Drainage Principles & Drainage Fixture Units (Tables 709.1 and 709.2) 5.2 Horizontal Branches, Building Drains & Building Sewers: Slope, Sizing & Separation 5.3 Soil & Waste Stacks, Stack Offsets, Branch Connections & Relief Vents
6 Chapter 6: Drainage Fittings, Cleanouts, Indirect Waste & Sumps
6.1 Drainage Fittings, Changes of Direction, Joints & Prohibited Connections 6.2 Cleanouts: Locations, Spacing, Size, Clearance & Access 6.3 Indirect Waste, Air Gaps, Air Breaks, Waste Receptors & Condensate Disposal 6.4 Sumps, Sewage Pumps, Ejectors & Backwater Valves
7 Chapter 7: Vent Systems & Sizing
7.1 Vent Purpose, Terminals, Outdoor Extensions & Vent Connections 7.2 Trap-to-Vent Distance (Table 909.1) & Vent Pipe Sizing (906) 7.3 Common Vents, Wet Venting & Waste Stack Vents 7.4 Circuit Venting, Combination Waste & Vent, Island, Single-Stack & Air Admittance Valves
8 Chapter 8: Water Supply, Distribution Sizing, Hot Water & Water Heaters
8.1 Water Service, Pipe Materials, Joints, Valves, Pressure Control & Disinfection 8.2 Water Distribution Design: Flow and Pressure Criteria, Fixture Supplies & Pipe Sizing 8.3 Hot Water Supply: Delivery Distance, Temperature Control, Recirculation & Thermal Expansion 8.4 Water Heaters: Installation, Relief Valves, Discharge Piping & Drain Pans
9 Chapter 9: Backflow Prevention & Cross-Connection Control
9.1 Cross-Connections, Backsiphonage, Backpressure & Degree of Hazard 9.2 Air Gaps, Atmospheric Vacuum Breakers & Hose Connection Protection 9.3 Testable Assemblies: RP, Double Check, PVB & SVB; Location, Testing & Virginia Certification 9.4 Protecting Specific Connections: Beverage Dispensers, Boilers, Sprinklers, Irrigation & Equipment
10 Chapter 10: Storm Drainage Systems & Sizing (with Virginia Amendments)
10.1 Storm Drainage Basics: Disposal, Materials, Rainfall Rates & Roof Area 10.2 Sizing Leaders, Conductors, Horizontal Storm Drains & Gutters (Virginia Tables) 10.3 Secondary (Emergency) Roof Drains, Scuppers & Roof Ponding 10.4 Subsoil Drains, Building Subdrains, Storm Sumps, Controlled-Flow Roofs & Continuous Flow
9.2 Air Gaps, Atmospheric Vacuum Breakers & Hose Connection Protection
Key Takeaways Explain This Topic AI
A potable water air gap is measured vertically from the lowest end of the outlet to the flood level rim of the fixture or receptacle (IPC 608.14.1).
Table 608.16.1: openings up to 1/2 inch need 1 inch away from walls or 1-1/2 inches near walls; up to 3/4 inch need 1-1/2 or 2-1/2 inches; up to 1 inch need 2 or 3 inches; over 1 inch need 2 or 3 times the opening.
Atmospheric and pressure-type vacuum breakers protecting an outlet must have their critical level at least 6 inches above the flood level rim of the fixture or device (608.16.4).
Deck-mounted and integral vacuum breakers must have their critical level at least 1 inch above the flood level rim (608.16.4.1).
Sillcocks, hose bibbs and wall hydrants must be protected by an atmospheric or pressure-type vacuum breaker or a permanently attached hose connection vacuum breaker (608.16.4.2).
Last updated: October 2026
The air gap (IPC 608.14.1 and 608.16.1)
An air gap in a water distribution system is the unobstructed vertical distance through free air between the lowest opening of a pipe or faucet supplying water to a tank, fixture or device and the flood level rim of the receptacle. With no moving parts, it protects against backsiphonage and backpressure at any hazard level .
608.14.1: the air gap is measured vertically from the lowest end of the potable outlet to the flood level rim. Air gaps meet ASME A112.1.2, and air gap fittings meet ASME A112.1.3.
608.16.1: openings and outlets protected by an air gap must have the gap in Table 608.16.1 . Openings equipped for hose connection must be protected by a method other than an air gap , because a hose can extend the outlet below the rim.
Table 608.16.1: minimum required air gaps
- Fixture Away from a wall Close to a wall
- Lavatories and other fixtures with effective openings not greater than 1/2 inch 1 inch 1-1/2 inches
Sinks, laundry trays, gooseneck back faucets and other fixtures with openings not greater than 3/4 inch 1-1/2 inches 2-1/2 inches
Over-rim bath fillers and other fixtures with openings not greater than 1 inch 2 inches 3 inches
Drinking water fountains: single orifice not greater than 7/16 inch, or multiple orifices with total area of 0.150 square inch 1 inch 1-1/2 inches
Effective openings greater than 1 inch 2 times the diameter of the effective opening 3 times the diameter of the effective opening
"Away from a wall" applies where walls or obstructions are spaced from the nearest inside edge of the spout more than three times the effective opening diameter for a single wall, or more than four times it for two intersecting walls. Closer than that, use the "close to a wall" column. Water flowing near a wall clings to it, so more separation is needed.
Worked examples
A 3/4-inch fill pipe discharges into a tank. The nearest wall is 6 inches away, which is more than 3 × 3/4 = 2.25 inches. The required air gap is 1-1/2 inches .
A 2-inch fill line discharges 4 inches from a single wall, which is less than 3 × 2 = 6 inches. The required air gap is 3 × 2 = 6 inches .
A 1-inch outlet is 1-1/2 inches from a concrete wall, which is less than 3 inches. The over-rim filler row applies "close to a wall," so the gap is 3 inches .
Atmospheric vacuum breakers (IPC 608.14.6 and 608.16.4)
An atmospheric vacuum breaker (AVB) has a float check (poppet) and an air inlet. When water flows forward, the poppet rises and seals the air inlet. When supply pressure drops, the poppet falls, seals the inlet side and opens the air port, which breaks the siphon.
Standards (608.14.6): pipe-applied AVBs meet ASSE 1001 or CSA B64.1.1. Hose-connection vacuum breakers meet ASME A112.21.3, ASSE 1011, ASSE 1019, ASSE 1035, ASSE 1052 or the CSA equivalents. "These devices shall operate under normal atmospheric pressure when the critical level is installed at the required height."
Height (608.16.4): the critical level of an atmospheric or pressure-type vacuum breaker must be at least 6 inches above the flood level rim of the fixture or device. Pipe-applied vacuum breakers must be at least 6 inches above the flood level rim of the fixture, receptor or device served.
Location (608.16.4): vacuum breakers may not be installed under exhaust hoods or similar locations that will contain toxic fumes or vapors.
Backsiphonage only: an AVB gives no protection against backpressure, and Table 608.1 rates it for backsiphonage only.
No valve downstream: an AVB must not be kept under continuous pressure. For lawn irrigation, 608.17.5 states "valves shall not be installed downstream from an atmospheric vacuum breaker," since a closed downstream valve would hold the AVB under pressure and its poppet could stick shut against the air port. Manufacturers also limit how long an AVB may stay under pressure, often to 12 hours in any 24.
Deck-mounted and integral vacuum breakers (IPC 608.16.4.1)
Approved deck-mounted or equipment-mounted vacuum breakers, and faucets with integral AVBs or spill-resistant vacuum breakers, are installed per the manufacturer and the labeling requirements, with the critical level at least 1 inch above the flood level rim .
Hose connections (IPC 608.16.4.2)
Sillcocks, hose bibbs, wall hydrants and other openings with a hose connection must be protected by:
- an atmospheric-type vacuum breaker;
- a pressure-type vacuum breaker; or
a permanently attached hose connection vacuum breaker .
Exceptions: water heater and boiler drain valves with hose threads intended only for draining the tank or vessel, and clothes washer supply valves where backflow protection is otherwise provided or built into the machine.
Common hose devices:
ASSE 1011 hose connection vacuum breaker: screws onto the hose thread. It protects against backsiphonage and low head backpressure, and it is not designed for continuous pressure, such as a hose left pressurized against a closed spray nozzle. Field-installed units have a breakaway set screw that shears off when tightened, so the device cannot be removed. That is how the "permanently attached" requirement is met.
ASSE 1052 hose connection backflow preventer: Table 608.1 rates it for low head backpressure, rated working pressure, backpressure or backsiphonage.
ASSE 1019 vacuum breaker wall hydrant: a frost-resistant, automatic-draining wall hydrant with built-in vacuum breaker protection.
Other atmospheric methods
Flush tank fill valves (415.3.1): an antisiphon fill valve meeting ASSE 1002 , with its backflow preventer at least 1 inch above the full opening of the overflow pipe.
Flushometer valves (415.2): their vacuum breakers meet ASSE 1001 or CSA B64.1.1 and need access.
Barometric loop (608.14.4): the loop must come before the point of connection and rise 35 feet vertically. It works only as an atmospheric or pressure-type vacuum breaker, against backsiphonage.
Hand showers (412.2): backflow protection per ASME A112.18.1, or a device meeting ASME A112.18.3.
Air gap or vacuum breaker?
- Feature Air gap AVB Hose connection vacuum breaker
- Backsiphonage Yes Yes Yes
- Backpressure Yes No Low head only (ASSE 1011)
- Hazard High or low High or low High or low
- Continuous pressure Yes No No for ASSE 1011
- Height rule Table 608.16.1 Critical level at least 6 inches above flood rim On the hose thread