6.1 Drainage Fittings, Changes of Direction, Joints & Prohibited Connections
Virginia Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Virginia Licensing Law & Standards of Practice
1.1 Exam Format, Permitted References & Open-Book Strategy 1.2 Definitions, Licensure Requirement & Qualification for the Exam 1.3 Standards of Practice: Designations, Address Changes & License Use 1.4 Standards of Conduct, Prohibited Acts & Revocation of Licensure
2 Chapter 2: Renewal, USBC Administration & General Regulations
2.1 License Renewal, Continuing Education & Reinstatement 2.2 Virginia USBC Administration, Permits, Inspections & Required Tests 2.3 General Regulations: Materials, Protection, Support, Trenching & Structural Safety
3 Chapter 3: Plumbing Fixtures, Clearances & Temperature Control
3.1 Minimum Plumbing Facilities: Table 403.1, Calculations & Separate Facilities 3.2 Fixture Installation: Clearances, Compartments, Connections, Showers & Accessibility 3.3 Water Conservation, Temperature-Limiting Devices, Flushing Devices & Emergency Fixtures
4 Chapter 4: Fixture Traps, Trap Seals & Interceptors
4.1 Fixture Traps, Trap Seals & Trap Seal Protection 4.2 Grease Interceptors: Where Required, Sizing, Flow Control & Virginia's Disposer Rule 4.3 Oil Separators, Sand & Lint Interceptors, Other Interceptors & Corrosive Waste
5 Chapter 5: Sanitary Drainage Systems & Sizing
5.1 Drainage Principles & Drainage Fixture Units (Tables 709.1 and 709.2) 5.2 Horizontal Branches, Building Drains & Building Sewers: Slope, Sizing & Separation 5.3 Soil & Waste Stacks, Stack Offsets, Branch Connections & Relief Vents
6 Chapter 6: Drainage Fittings, Cleanouts, Indirect Waste & Sumps
6.1 Drainage Fittings, Changes of Direction, Joints & Prohibited Connections 6.2 Cleanouts: Locations, Spacing, Size, Clearance & Access 6.3 Indirect Waste, Air Gaps, Air Breaks, Waste Receptors & Condensate Disposal 6.4 Sumps, Sewage Pumps, Ejectors & Backwater Valves
7 Chapter 7: Vent Systems & Sizing
7.1 Vent Purpose, Terminals, Outdoor Extensions & Vent Connections 7.2 Trap-to-Vent Distance (Table 909.1) & Vent Pipe Sizing (906) 7.3 Common Vents, Wet Venting & Waste Stack Vents 7.4 Circuit Venting, Combination Waste & Vent, Island, Single-Stack & Air Admittance Valves
8 Chapter 8: Water Supply, Distribution Sizing, Hot Water & Water Heaters
8.1 Water Service, Pipe Materials, Joints, Valves, Pressure Control & Disinfection 8.2 Water Distribution Design: Flow and Pressure Criteria, Fixture Supplies & Pipe Sizing 8.3 Hot Water Supply: Delivery Distance, Temperature Control, Recirculation & Thermal Expansion 8.4 Water Heaters: Installation, Relief Valves, Discharge Piping & Drain Pans
9 Chapter 9: Backflow Prevention & Cross-Connection Control
9.1 Cross-Connections, Backsiphonage, Backpressure & Degree of Hazard 9.2 Air Gaps, Atmospheric Vacuum Breakers & Hose Connection Protection 9.3 Testable Assemblies: RP, Double Check, PVB & SVB; Location, Testing & Virginia Certification 9.4 Protecting Specific Connections: Beverage Dispensers, Boilers, Sprinklers, Irrigation & Equipment
10 Chapter 10: Storm Drainage Systems & Sizing (with Virginia Amendments)
10.1 Storm Drainage Basics: Disposal, Materials, Rainfall Rates & Roof Area 10.2 Sizing Leaders, Conductors, Horizontal Storm Drains & Gutters (Virginia Tables) 10.3 Secondary (Emergency) Roof Drains, Scuppers & Roof Ponding 10.4 Subsoil Drains, Building Subdrains, Storm Sumps, Controlled-Flow Roofs & Continuous Flow
6.1 Drainage Fittings, Changes of Direction, Joints & Prohibited Connections
Key Takeaways Explain This Topic AI
Sanitary tees are permitted only for horizontal-to-vertical changes of direction; wyes, combination wye and eighth bends, long sweeps and sixteenth, eighth and sixth bends are permitted in all three directions (Table 706.3).
Quarter bends and short sweeps may be used vertical-to-horizontal or horizontal-to-horizontal only on fixture drains 2 inches or smaller; short sweeps 3 inches or larger are also allowed vertical-to-horizontal (Table 706.3 notes a and b).
Double sanitary tees may not receive back-to-back water closets or pumping fixtures unless the horizontal developed length from each closet outlet to the fitting is at least 18 inches (706.3).
Heel-inlet quarter bends are acceptable except where the bend serves a water closet, and a low-heel inlet may not be used as a wet-vented connection (706.4).
Prohibited joints include cement or concrete joints, mastic or hot-pour bituminous joints, rolling O-rings between different pipe diameters, solvent joints between different plastics (except 705.16.4), and saddle fittings (707.1).
Last updated: October 2026
Why fittings are regulated
Drainage depends on gravity and momentum. A fitting that turns flow too sharply in the wrong orientation slows the water, drops solids, and can push air back toward traps. IPC 706.1 requires approved drainage fittings for all connections and changes of direction. 706.2 prohibits fittings with ledges, shoulders or reductions that could slow or block flow. Threaded drainage fittings must be the recessed drainage type . 706.3 requires fittings to guide sewage and waste in the direction of flow, using Table 706.3 .
Table 706.3: fittings for changes in direction
- Fitting pattern Horizontal to vertical Vertical to horizontal Horizontal to horizontal
- Sixteenth bend (22-1/2°) Yes Yes Yes
- Eighth bend (45°) Yes Yes Yes
- Sixth bend (60°) Yes Yes Yes
- Quarter bend (90°) Yes Note a Note a
- Short sweep Yes Notes a and b Note a
- Long sweep Yes Yes Yes
- Sanitary tee Yes (note c) No No
- Wye Yes Yes Yes
- Combination wye and eighth bend Yes Yes Yes
Note a: permitted only for a 2-inch or smaller fixture drain .
Note b: 3 inches or larger . A short sweep 3 inches or larger may be used vertical to horizontal.
Note c: see 706.3 for the limit on double sanitary tees.
Combination fittings, side inlets and increasers are judged by the flow pattern they create.
What this means in practice:
Branch into a stack (horizontal to vertical): a sanitary tee is the usual fitting.
Base of a 4-inch stack (vertical to horizontal): use a long sweep, a short sweep (3 inches or larger), a wye with an eighth bend, a combination wye and eighth bend, or two eighth bends. A 4-inch sanitary tee or a regular quarter bend is not allowed, since quarter bends are limited to 2-inch fixture drains.
Horizontal branch joining a horizontal drain: use a wye or a combination wye and eighth bend. A sanitary tee laid on its side is never allowed horizontal to horizontal.
Double sanitary tees and back-to-back fixtures (IPC 706.3)
Double sanitary tee patterns shall not receive the discharge of back-to-back water closets or of fixtures or appliances with pumping action discharge. The short-turn pattern lets one closet's flush shoot across into the opposite inlet.
Exception: back-to-back water closets may connect to a double sanitary tee if the horizontal developed length between each water closet outlet and the fitting is 18 inches or greater .
Back-to-back water closets are normally connected with a double combination wye and eighth bend , or with a double fixture fitting designed for that use.
Heel- and side-inlet quarter bends (IPC 706.4)
Heel-inlet quarter bends are acceptable except where the quarter bend serves a water closet .
A low-heel inlet may not be used as a wet-vented connection.
Side-inlet quarter bends are acceptable for drainage, wet venting and stack venting.
Drainage pipe materials (IPC 702)
Use Table Examples of listed materials
Above-ground drainage and vent pipe 702.1 ABS and PVC (solid, cellular core or composite wall), cast iron (ASTM A74, A888, CISPI 301), copper or copper-alloy (Type K, L, M or DWV), galvanized steel, glass, polyolefin, PVDF, stainless steel
Underground building drainage and vent pipe 702.2 ABS, cast iron, PVC, copper and others listed for underground use
- Building sewer pipe 702.3 ABS, cast iron, concrete, PVC sewer pipe, polypropylene, vitrified clay and others
- Fittings 702.4 Must match the pipe material standard
702.5: where wastewater will be hotter than 140°F , the sanitary drainage pipe must be rated for the highest wastewater temperature.
702.6: chemical waste systems must be separate and of corrosion-resistant material (see Section 4.3).
303.3: plastic pipe and fittings must be third-party certified to NSF 14.
Joints (IPC 705)
Material Joint method and key rule
ABS (705.2) Solvent cement meeting ASTM D2235. Mechanical joints with elastomeric seals are installed only underground unless otherwise approved.
PVC (705.10.2) Purple primer meeting ASTM F656 , then solvent cement that is not purple , meeting ASTM D2564 or listed CSA standards, applied to all joint surfaces. Virginia deleted the model exception that let some DWV joints of 4 inches or smaller skip primer, so primer is required in Virginia . Solvent joints may be above or below ground.
Cast iron, hub and spigot, caulked (705.3.1) Firmly packed oakum or hemp, then molten lead poured in one operation to at least 1 inch deep, not more than 1/8 inch below the hub rim, caulked tight. No paint or coatings until tested and approved.
Cast iron, compression gasket (705.3.2) Gaskets meeting ASTM C564, tested to ASTM C1563.
Cast iron, hubless (705.3.3) Coupling with an elastomeric sleeve (with center stop) and a metal shield meeting CISPI 310, ASTM C1277 or C1540.
Copper (705.5 and 705.6) Solder joints per ASTM B828 with ASTM B813 flux and ASTM B32 solder; brazed or mechanical joints are also listed. Ream tube ends to full diameter.
Different materials (705.16) Mechanical compression or mechanical-sealing joints with elastomeric seals, or the specific methods in 705.16.1 to 705.16.7
Joints between different materials:
705.16.1: copper to cast-iron hub pipe uses a copper or copper-alloy ferrule, or a compression joint.
705.16.2: copper to galvanized steel uses a copper-alloy or dielectric fitting.
705.16.4: different plastics join with an approved adapter. The only solvent joint between ABS and PVC allowed is a single joint at the end of the building drain and the start of the building sewer, using solvent cement meeting ASTM D3138 .
705.17: drainage slip joints follow 405.9: only on the trap inlet, trap outlet and within the trap seal.
Prohibited joints and connections (IPC 707.1)
Cement or concrete joints.
Mastic or hot-pour bituminous joints.
Joints made with fittings not approved for the specific installation.
Joints between different diameter pipes made with elastomeric rolling O-rings .
Solvent-cement joints between different types of plastic pipe , except as 705.16.4 allows.
Saddle-type fittings.
To add a branch to an existing drain, cut in an approved wye or tee with approved couplings. Strapping a saddle over a hole is never allowed.
Other connection rules
704.2: no reduction in size in the direction of flow (4-by-3 closet flanges and bends are not reductions).
704.3: branches connect at least 10 stack diameters downstream of a stack base or horizontal offset.
1101.6: storm drainage uses the same Table 706.3 fittings.
708.1.12: a threaded cleanout opening may not be used to add a fixture or extend piping unless another cleanout of equal size is installed.