3.3 Water Conservation, Temperature-Limiting Devices, Flushing Devices & Emergency Fixtures
Virginia Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Virginia Licensing Law & Standards of Practice
1.1 Exam Format, Permitted References & Open-Book Strategy 1.2 Definitions, Licensure Requirement & Qualification for the Exam 1.3 Standards of Practice: Designations, Address Changes & License Use 1.4 Standards of Conduct, Prohibited Acts & Revocation of Licensure
2 Chapter 2: Renewal, USBC Administration & General Regulations
2.1 License Renewal, Continuing Education & Reinstatement 2.2 Virginia USBC Administration, Permits, Inspections & Required Tests 2.3 General Regulations: Materials, Protection, Support, Trenching & Structural Safety
3 Chapter 3: Plumbing Fixtures, Clearances & Temperature Control
3.1 Minimum Plumbing Facilities: Table 403.1, Calculations & Separate Facilities 3.2 Fixture Installation: Clearances, Compartments, Connections, Showers & Accessibility 3.3 Water Conservation, Temperature-Limiting Devices, Flushing Devices & Emergency Fixtures
4 Chapter 4: Fixture Traps, Trap Seals & Interceptors
4.1 Fixture Traps, Trap Seals & Trap Seal Protection 4.2 Grease Interceptors: Where Required, Sizing, Flow Control & Virginia's Disposer Rule 4.3 Oil Separators, Sand & Lint Interceptors, Other Interceptors & Corrosive Waste
5 Chapter 5: Sanitary Drainage Systems & Sizing
5.1 Drainage Principles & Drainage Fixture Units (Tables 709.1 and 709.2) 5.2 Horizontal Branches, Building Drains & Building Sewers: Slope, Sizing & Separation 5.3 Soil & Waste Stacks, Stack Offsets, Branch Connections & Relief Vents
6 Chapter 6: Drainage Fittings, Cleanouts, Indirect Waste & Sumps
6.1 Drainage Fittings, Changes of Direction, Joints & Prohibited Connections 6.2 Cleanouts: Locations, Spacing, Size, Clearance & Access 6.3 Indirect Waste, Air Gaps, Air Breaks, Waste Receptors & Condensate Disposal 6.4 Sumps, Sewage Pumps, Ejectors & Backwater Valves
7 Chapter 7: Vent Systems & Sizing
7.1 Vent Purpose, Terminals, Outdoor Extensions & Vent Connections 7.2 Trap-to-Vent Distance (Table 909.1) & Vent Pipe Sizing (906) 7.3 Common Vents, Wet Venting & Waste Stack Vents 7.4 Circuit Venting, Combination Waste & Vent, Island, Single-Stack & Air Admittance Valves
8 Chapter 8: Water Supply, Distribution Sizing, Hot Water & Water Heaters
8.1 Water Service, Pipe Materials, Joints, Valves, Pressure Control & Disinfection 8.2 Water Distribution Design: Flow and Pressure Criteria, Fixture Supplies & Pipe Sizing 8.3 Hot Water Supply: Delivery Distance, Temperature Control, Recirculation & Thermal Expansion 8.4 Water Heaters: Installation, Relief Valves, Discharge Piping & Drain Pans
9 Chapter 9: Backflow Prevention & Cross-Connection Control
9.1 Cross-Connections, Backsiphonage, Backpressure & Degree of Hazard 9.2 Air Gaps, Atmospheric Vacuum Breakers & Hose Connection Protection 9.3 Testable Assemblies: RP, Double Check, PVB & SVB; Location, Testing & Virginia Certification 9.4 Protecting Specific Connections: Beverage Dispensers, Boilers, Sprinklers, Irrigation & Equipment
10 Chapter 10: Storm Drainage Systems & Sizing (with Virginia Amendments)
10.1 Storm Drainage Basics: Disposal, Materials, Rainfall Rates & Roof Area 10.2 Sizing Leaders, Conductors, Horizontal Storm Drains & Gutters (Virginia Tables) 10.3 Secondary (Emergency) Roof Drains, Scuppers & Roof Ponding 10.4 Subsoil Drains, Building Subdrains, Storm Sumps, Controlled-Flow Roofs & Continuous Flow
3.3 Water Conservation, Temperature-Limiting Devices, Flushing Devices & Emergency Fixtures
Key Takeaways Explain This Topic AI
Table 604.4 maximums: water closets 1.6 gallons per flush, urinals 1.0 gallon per flush, showerheads 2.5 gpm at 80 psi, private lavatories 2.2 gpm, and public non-metering lavatories 0.5 gpm at 60 psi.
Individual shower and tub-shower valves must be balanced-pressure, thermostatic or combination valves (ASSE 1016 or ASME A112.18.1), with a limit stop field-adjusted to 120°F (IPC 412.3).
Bidet water is limited to 110°F by an ASSE 1070 device (IPC 408.3); public hand-washing lavatories deliver tempered water through an ASSE 1070 device (IPC 419.5).
Bathtub and whirlpool valves are limited to 120°F by an ASSE 1070 device or an ASSE 1082/1084 water heater, unless a combination tub/shower valve is used (IPC 412.5).
Emergency showers and eyewash stations meet ISEA Z358.1, and where hot and cold water are supplied, the temperature may be controlled only by an ASSE 1071 mixing valve (IPC 411).
Last updated: October 2026
Maximum flow rates (IPC 604.4 and Table 604.4)
- Fixture or fitting Maximum flow or quantity
- Lavatory, private 2.2 gpm at 60 psi
- Lavatory, public (metering) 0.25 gallon per metering cycle
- Lavatory, public (other than metering) 0.5 gpm at 60 psi
- Shower head (a hand-held shower spray counts as a shower head) 2.5 gpm at 80 psi
- Sink faucet 2.2 gpm at 60 psi
- Urinal 1.0 gallon per flushing cycle
- Water closet 1.6 gallons per flushing cycle
Exceptions (604.4): blowout-design water closets using no more than 3-1/2 gallons per flush; vegetable sprays; clinical sinks using no more than 4-1/2 gallons per flush; service sinks; and emergency showers.
Lower-flow products such as 1.28-gallon water closets or 1.5-gpm lavatory faucets are allowed, since the table sets maximums. The table itself does not list lower values. Table 604.3 is a different table: it gives the minimum flow and pressure the distribution system must deliver to each outlet (see Section 8.2).
Why temperature limits exist
Scald injury depends on temperature and contact time. Burn research commonly cited by the plumbing industry shows that water around 140°F can cause a serious burn in seconds, while 120°F water takes several minutes of contact. Water heaters often store water hotter than is safe at the outlet. The code therefore requires a limiting device at, or serving, the fixture for showers, tubs, bidets, public lavatories and similar fixtures.
Temperature limits by fixture
Fixture Code section Maximum Device
Individual shower and tub-shower 412.3 120°F (limit stop field-adjusted to manufacturer instructions) Balanced-pressure, thermostatic or combination valve meeting ASSE 1016 /ASME A112.1016/CSA B125.16 or ASME A112.18.1/CSA B125.1, installed at the point of use
Multiple (gang) showers on one tempered supply 412.4 120°F ASSE 1069 or CSA B125.3 automatic temperature control valve, or individual ASSE 1016 valves at each head
Bathtub and whirlpool bathtub 412.5 120°F ASSE 1070 limiting device, or an ASSE 1082 or 1084 water heater, unless a combination tub/shower valve under 412.3 is used
- Bidet 408.3 110°F ASSE 1070
- Public hand-washing lavatories and group wash fixtures 419.5 Tempered water (85°F to 110°F) ASSE 1070
Head shampoo sinks 412.10 120°F ASSE 1070, an ASSE 1082 water heater, or an ASSE 1062 device; integral check valves required
Footbaths and pedicure baths 423.3 120°F ASSE 1070 or an ASSE 1082 water heater
Emergency shower or eyewash with hot and cold supply 411.3 Tepid (Z358.1) Controlled only by an ASSE 1071 mixing valve; a water heater supplying the station directly must meet ASSE 1085
"Tempered water" is defined in IPC Chapter 2 as water between 85°F and 110°F . Under 607.1.2 , tempered water is controlled by an ASSE 1070 device set no higher than 110°F, an ASSE 1017 thermostatic mixing valve, or an ASSE 1082 or ASSE 1084 water heater. Neither option replaces the protective shower valves required by 412.3.
Related rules:
613.1: temperature-actuated mixing valves installed to reduce water temperatures to defined limits must meet ASSE 1017 . These are typically source (master) mixing valves.
607.1.1: a water heater thermostat may serve as the temperature-limiting means only if the water heater complies with ASSE 1082 or ASSE 1085 .
412.7: ASSE 1062 temperature-actuated, flow-reduction devices may limit an individual fitting to 120°F, but they cannot replace the shower valves of 412.3 or the bathtub limiting devices of 412.5.
604.11: ASSE 1066 in-line pressure-balancing valves for individual fittings also cannot replace 412.3 shower valves.
501.6: water from tankless water heaters for domestic use must not exceed 140°F .
Comparing the ASSE standards
Standard What it is Where it goes
ASSE 1016 Individual shower/tub-shower valve (balanced-pressure, thermostatic or combination) Point of use, in the shower valve
- ASSE 1017 Temperature-actuated mixing valve for a hot water distribution system At the source or on a branch
- ASSE 1069 Automatic temperature control mixing valve Gang showers
ASSE 1070 Water temperature limiting device Point of use: tubs, bidets, public lavatories, shampoo sinks, pedicure baths
ASSE 1071 Temperature-actuated mixing valve for plumbed emergency equipment Emergency showers and eyewash stations
An ASSE 1017 master valve at the water heater does not satisfy 412.3. Every individual shower still needs its own point-of-use ASSE 1016 (or ASME A112.18.1) valve. A balanced-pressure valve reacts to pressure changes in the supply lines; a thermostatic valve reacts to outlet temperature.
Flushing devices (IPC 415)
415.1: water closets, urinals, clinical sinks and other fixtures that depend on trap siphonage need a flushometer valve, flushometer tank or flush tank. 415.1.1: one flushing device may not serve more than one fixture.
415.2: flushometer valves and tanks meet ASSE 1037. Their vacuum breakers meet ASSE 1001 and must be accessible. Flushometer valves must be the water-conservation type, must complete their cycle automatically, and need a way to regulate flow. They must not be used where the water pressure is below the minimum required for normal operation.
415.3.1: flush tanks need an antisiphon fill valve meeting ASSE 1002 , with the fill valve backflow preventer at least 1 inch above the full opening of the overflow pipe .
415.3.2: the flush tank overflow discharges to the water closet or urinal and is sized to prevent flooding at the maximum supply rate.
415.4: flush pipes and fittings must be nonferrous.
Emergency showers and eyewash stations (IPC 411; ISEA Z358.1)
411.1: they must conform to ISEA Z358.1 .
411.2: a waste connection is not required .
411.3: where hot and cold water are supplied, the temperature is controlled only by an ASSE 1071 temperature-actuated mixing valve. A water heater that supplies the station directly must meet ASSE 1085 .
ISEA Z358.1 requires tepid water, defined as 60°F to 100°F , for a 15-minute flushing period. Its minimum flow rates are 20 gpm for a plumbed drench shower, 0.4 gpm for an eyewash, and 3.0 gpm for an eye/face wash. The IPC exempts emergency showers from the Table 604.4 flow limits.
Other fixture rules
416.1: a food waste disposer must not increase the drainage fixture unit load. 416.4: disposers need a water supply.
417: garbage can washers need protected water supply and a trapped waste with a removable basket.
418: laundry trays need a waste outlet of at least 1-1/2 inches with a strainer or crossbar.