5.1 Drainage Principles & Drainage Fixture Units (Tables 709.1 and 709.2)

Virginia Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Virginia Licensing Law & Standards of Practice

1.1 Exam Format, Permitted References & Open-Book Strategy 1.2 Definitions, Licensure Requirement & Qualification for the Exam 1.3 Standards of Practice: Designations, Address Changes & License Use 1.4 Standards of Conduct, Prohibited Acts & Revocation of Licensure

2 Chapter 2: Renewal, USBC Administration & General Regulations

2.1 License Renewal, Continuing Education & Reinstatement 2.2 Virginia USBC Administration, Permits, Inspections & Required Tests 2.3 General Regulations: Materials, Protection, Support, Trenching & Structural Safety

3 Chapter 3: Plumbing Fixtures, Clearances & Temperature Control

3.1 Minimum Plumbing Facilities: Table 403.1, Calculations & Separate Facilities 3.2 Fixture Installation: Clearances, Compartments, Connections, Showers & Accessibility 3.3 Water Conservation, Temperature-Limiting Devices, Flushing Devices & Emergency Fixtures

4 Chapter 4: Fixture Traps, Trap Seals & Interceptors

4.1 Fixture Traps, Trap Seals & Trap Seal Protection 4.2 Grease Interceptors: Where Required, Sizing, Flow Control & Virginia's Disposer Rule 4.3 Oil Separators, Sand & Lint Interceptors, Other Interceptors & Corrosive Waste

5 Chapter 5: Sanitary Drainage Systems & Sizing

5.1 Drainage Principles & Drainage Fixture Units (Tables 709.1 and 709.2) 5.2 Horizontal Branches, Building Drains & Building Sewers: Slope, Sizing & Separation 5.3 Soil & Waste Stacks, Stack Offsets, Branch Connections & Relief Vents

6 Chapter 6: Drainage Fittings, Cleanouts, Indirect Waste & Sumps

6.1 Drainage Fittings, Changes of Direction, Joints & Prohibited Connections 6.2 Cleanouts: Locations, Spacing, Size, Clearance & Access 6.3 Indirect Waste, Air Gaps, Air Breaks, Waste Receptors & Condensate Disposal 6.4 Sumps, Sewage Pumps, Ejectors & Backwater Valves

7 Chapter 7: Vent Systems & Sizing

7.1 Vent Purpose, Terminals, Outdoor Extensions & Vent Connections 7.2 Trap-to-Vent Distance (Table 909.1) & Vent Pipe Sizing (906) 7.3 Common Vents, Wet Venting & Waste Stack Vents 7.4 Circuit Venting, Combination Waste & Vent, Island, Single-Stack & Air Admittance Valves

8 Chapter 8: Water Supply, Distribution Sizing, Hot Water & Water Heaters

8.1 Water Service, Pipe Materials, Joints, Valves, Pressure Control & Disinfection 8.2 Water Distribution Design: Flow and Pressure Criteria, Fixture Supplies & Pipe Sizing 8.3 Hot Water Supply: Delivery Distance, Temperature Control, Recirculation & Thermal Expansion 8.4 Water Heaters: Installation, Relief Valves, Discharge Piping & Drain Pans

9 Chapter 9: Backflow Prevention & Cross-Connection Control

9.1 Cross-Connections, Backsiphonage, Backpressure & Degree of Hazard 9.2 Air Gaps, Atmospheric Vacuum Breakers & Hose Connection Protection 9.3 Testable Assemblies: RP, Double Check, PVB & SVB; Location, Testing & Virginia Certification 9.4 Protecting Specific Connections: Beverage Dispensers, Boilers, Sprinklers, Irrigation & Equipment

10 Chapter 10: Storm Drainage Systems & Sizing (with Virginia Amendments)

10.1 Storm Drainage Basics: Disposal, Materials, Rainfall Rates & Roof Area 10.2 Sizing Leaders, Conductors, Horizontal Storm Drains & Gutters (Virginia Tables) 10.3 Secondary (Emergency) Roof Drains, Scuppers & Roof Ponding 10.4 Subsoil Drains, Building Subdrains, Storm Sumps, Controlled-Flow Roofs & Continuous Flow

5.1 Drainage Principles & Drainage Fixture Units (Tables 709.1 and 709.2)

Key Takeaways Explain This Topic AI

Table 709.1 values: lavatory 1 dfu (1-1/4-inch trap), bathtub 2 dfu, kitchen sink 2 dfu (1-1/2-inch trap), bidet 1 dfu, drinking fountain 1/2 dfu, and floor drain 2 dfu (2-inch trap).

Private 1.6 gpf water closets are 3 dfu; public 1.6 gpf water closets and flushometer tanks are 4 dfu; water closets flushing more than 1.6 gpf are 4 dfu private and 6 dfu public.

A bathroom group with a 1.6 gpf water closet is 5 dfu (6 dfu if the closet flushes more than 1.6 gpf); residential clothes washers are 2 dfu and commercial washers 3 dfu, both with 2-inch traps.

Unlisted fixtures use Table 709.2 by trap size (1-1/4 inch = 1 dfu up to 4 inch = 6 dfu); a known flow converts at 1 gpm = 2 dfu (709.3).

Drainage piping may not be reduced in size in the direction of flow, except for a 4-by-3-inch closet flange, a 4-by-3-inch closet bend, or an offset closet flange (704.2).

Last updated: October 2026

How gravity drainage works

A sanitary drain is an open-channel system. Horizontal drains are designed to run partly full , so that air can move above the water and pressures in the system stay close to atmospheric. The vent system keeps any pressure difference at a trap within 1 inch of water column (IPC 901.2). When drainage piping is sized correctly, it carries waste at a velocity that keeps solids moving. Engineers usually aim for about 2 feet per second for self-cleansing flow.

The drainage fixture unit (dfu) is a load factor, not a flow rate. It comes from Roy B. Hunter's work at the National Bureau of Standards ( Methods of Estimating Loads in Plumbing Systems , BMS 65, 1940). Fixtures are used intermittently and seldom all at once. The dfu values combine each fixture's discharge rate, duration and frequency of use, so a system can be sized for a realistic peak load instead of the sum of every fixture's maximum flow. Under IPC 709.1 , the Table 709.1 values are used with Tables 710.1(1) and 710.1(2) to size soil and waste pipes.

Table 709.1: drainage fixture units and minimum trap sizes

  • Fixture dfu Minimum trap
  • Automatic clothes washer, residential 2 2 inches
  • Automatic clothes washer, commercial 3 2 inches
  • Bathroom group (1.6 gpf water closet) 5 —
  • Bathroom group (water closet over 1.6 gpf) 6 —
  • Bathtub, with or without overhead shower or whirlpool 2 1-1/2 inches
  • Bidet 1 1-1/4 inches
  • Combination sink and tray 2 1-1/2 inches
  • Dental lavatory; dental unit or cuspidor 1 1-1/4 inches
  • Dishwashing machine, domestic 2 1-1/2 inches
  • Drinking fountain 1/2 1-1/4 inches
  • Emergency floor drain 0 2 inches
  • Floor drain 2 2 inches
  • Kitchen sink, domestic (with or without disposer or dishwasher) 2 1-1/2 inches
  • Laundry tray (1 or 2 compartments) 2 1-1/2 inches
  • Lavatory 1 1-1/4 inches

Shower, 5.7 gpm or less / over 5.7 to 12.3 / over 12.3 to 25.8 / over 25.8 to 55.6 gpm 2 / 3 / 5 / 6 1-1/2 / 2 / 3 / 4 inches

  • Service sink; sink 2 1-1/2 inches
  • Urinal / urinal 1 gpf or less / nonwater urinal 4 / 2 / 1/2 Note d
  • Wash sink (circular or multiple), each set of faucets 2 1-1/2 inches
  • Water closet, flushometer tank, public or private 4 Note d
  • Water closet, private, 1.6 gpf 3 Note d
  • Water closet, private, over 1.6 gpf 4 Note d
  • Water closet, public, 1.6 gpf 4 Note d
  • Water closet, public, over 1.6 gpf 6 Note d

Table notes to remember:

Note d: trap size must match the fixture outlet size. For traps larger than 3 inches, use Table 709.2.

A showerhead over a bathtub or a whirlpool attachment does not increase the bathtub's dfu value.

For computing loads on building drains and sewers , water closets and urinals may not be given a lower dfu value unless testing confirms it.

For fixtures added to a bathroom group, add their dfu values to the group's value.

Shower dfu values depend on the total flow through showerheads and body sprays.

See 406.2 for clothes washer standpipe sizing: the trap and fixture drain must be 2 inches or larger and must connect to a 3-inch or larger branch or stack.

The Table 709.1 lavatory value is 1 dfu . The table does not separate public and private lavatories, so a choice giving "2 dfu for a public lavatory" is wrong.

A bathroom group is a water closet, lavatory, and bathtub or shower, with or without a bidet, an emergency floor drain or both, located together on the same floor level (IPC Chapter 2).

Fixtures not in the table (IPC 709.2)

  • Fixture drain or trap size dfu
  • 1-1/4 inches 1
  • 1-1/2 inches 2
  • 2 inches 3
  • 2-1/2 inches 4
  • 3 inches 5
  • 4 inches 6

The minimum trap for an unlisted fixture is the size of its drain outlet, but not less than 1-1/4 inches .

Converting flow to dfu (IPC 709.3)

Where a discharge is known only in gpm, 1 gpm equals 2 dfu . This applies to pumps, ejectors, equipment drains and similar continuous or semicontinuous flows into the sanitary system.

Example: a mechanical room has two floor drains (2 dfu each = 4), a service sink (2), and a pumped discharge of 25 gpm (25 × 2 = 50). The total load is 56 dfu .

Indirect waste receptors (IPC 709.4 and 709.4.1)

The dfu load of an indirect waste receptor is the sum of the fixtures discharging to it, but not less than the receptor's own Table 709.1 or 709.2 value.

A floor drain, floor sink or hub drain that receives only clear-water waste from display cases, refrigerated cases, ice bins, coolers and freezers is rated at 1/2 dfu .

Size never decreases downstream (IPC 704.2)

The size of drainage piping shall not be reduced in the direction of flow . These are not treated as reductions:

a 4-by-3-inch water closet flange ;

a water closet bend with a 4-inch inlet and a 3-inch outlet, if the 4-inch leg is upright and below the closet flange;

an offset closet flange .

Related rules:

1002.5: a trap must not be larger than the drain it discharges into.

Table 710.1(1) note a: the minimum size of any building drain serving a water closet is 3 inches .

704.4: drainage piping for future fixtures must end with an approved cap or plug, and 710.2 requires future fixtures to be counted when sizing drains.

Worked example: a small apartment

A two-bedroom apartment has one full bathroom (1.6 gpf water closet, lavatory, tub), a powder room (1.6 gpf water closet and lavatory), a kitchen sink with a dishwasher, and a residential clothes washer.

  • Item dfu
  • Bathroom group 5
  • Powder room water closet (private 1.6 gpf) 3
  • Powder room lavatory 1
  • Kitchen sink (dishwasher included) 2
  • Residential clothes washer 2
  • Total 13

You would size the horizontal branches and stack with Table 710.1(2), and the building drain with Table 710.1(1), as covered in the next two sections.