10.2 Sizing Leaders, Conductors, Horizontal Storm Drains & Gutters (Virginia Tables)

Virginia Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Virginia Licensing Law & Standards of Practice

1.1 Exam Format, Permitted References & Open-Book Strategy 1.2 Definitions, Licensure Requirement & Qualification for the Exam 1.3 Standards of Practice: Designations, Address Changes & License Use 1.4 Standards of Conduct, Prohibited Acts & Revocation of Licensure

2 Chapter 2: Renewal, USBC Administration & General Regulations

2.1 License Renewal, Continuing Education & Reinstatement 2.2 Virginia USBC Administration, Permits, Inspections & Required Tests 2.3 General Regulations: Materials, Protection, Support, Trenching & Structural Safety

3 Chapter 3: Plumbing Fixtures, Clearances & Temperature Control

3.1 Minimum Plumbing Facilities: Table 403.1, Calculations & Separate Facilities 3.2 Fixture Installation: Clearances, Compartments, Connections, Showers & Accessibility 3.3 Water Conservation, Temperature-Limiting Devices, Flushing Devices & Emergency Fixtures

4 Chapter 4: Fixture Traps, Trap Seals & Interceptors

4.1 Fixture Traps, Trap Seals & Trap Seal Protection 4.2 Grease Interceptors: Where Required, Sizing, Flow Control & Virginia's Disposer Rule 4.3 Oil Separators, Sand & Lint Interceptors, Other Interceptors & Corrosive Waste

5 Chapter 5: Sanitary Drainage Systems & Sizing

5.1 Drainage Principles & Drainage Fixture Units (Tables 709.1 and 709.2) 5.2 Horizontal Branches, Building Drains & Building Sewers: Slope, Sizing & Separation 5.3 Soil & Waste Stacks, Stack Offsets, Branch Connections & Relief Vents

6 Chapter 6: Drainage Fittings, Cleanouts, Indirect Waste & Sumps

6.1 Drainage Fittings, Changes of Direction, Joints & Prohibited Connections 6.2 Cleanouts: Locations, Spacing, Size, Clearance & Access 6.3 Indirect Waste, Air Gaps, Air Breaks, Waste Receptors & Condensate Disposal 6.4 Sumps, Sewage Pumps, Ejectors & Backwater Valves

7 Chapter 7: Vent Systems & Sizing

7.1 Vent Purpose, Terminals, Outdoor Extensions & Vent Connections 7.2 Trap-to-Vent Distance (Table 909.1) & Vent Pipe Sizing (906) 7.3 Common Vents, Wet Venting & Waste Stack Vents 7.4 Circuit Venting, Combination Waste & Vent, Island, Single-Stack & Air Admittance Valves

8 Chapter 8: Water Supply, Distribution Sizing, Hot Water & Water Heaters

8.1 Water Service, Pipe Materials, Joints, Valves, Pressure Control & Disinfection 8.2 Water Distribution Design: Flow and Pressure Criteria, Fixture Supplies & Pipe Sizing 8.3 Hot Water Supply: Delivery Distance, Temperature Control, Recirculation & Thermal Expansion 8.4 Water Heaters: Installation, Relief Valves, Discharge Piping & Drain Pans

9 Chapter 9: Backflow Prevention & Cross-Connection Control

9.1 Cross-Connections, Backsiphonage, Backpressure & Degree of Hazard 9.2 Air Gaps, Atmospheric Vacuum Breakers & Hose Connection Protection 9.3 Testable Assemblies: RP, Double Check, PVB & SVB; Location, Testing & Virginia Certification 9.4 Protecting Specific Connections: Beverage Dispensers, Boilers, Sprinklers, Irrigation & Equipment

10 Chapter 10: Storm Drainage Systems & Sizing (with Virginia Amendments)

10.1 Storm Drainage Basics: Disposal, Materials, Rainfall Rates & Roof Area 10.2 Sizing Leaders, Conductors, Horizontal Storm Drains & Gutters (Virginia Tables) 10.3 Secondary (Emergency) Roof Drains, Scuppers & Roof Ponding 10.4 Subsoil Drains, Building Subdrains, Storm Sumps, Controlled-Flow Roofs & Continuous Flow

10.2 Sizing Leaders, Conductors, Horizontal Storm Drains & Gutters (Virginia Tables)

Key Takeaways Explain This Topic AI

Virginia's 1106.2 sizes vertical conductors and leaders by maximum projected roof area using Tables 1106.2(1) (circular) and 1106.2(2) (rectangular), with rainfall columns from 1 to 12 inches per hour.

In Virginia Table 1106.2(1), a 4-inch circular leader serves 18,400 square feet at 1 inch per hour and 6,130 at 3 inches per hour; a 3-inch leader serves 8,800 and 2,930.

Virginia's 1106.3 sizes building storm drains, storm sewers and their horizontal branches at slopes up to 1/2 inch per foot from Table 1106.3, with a minimum slope of 1/8 inch per foot unless otherwise approved.

At 1 inch per hour, Virginia Table 1106.3 allows 7,520 square feet for a 4-inch drain at 1/8 inch per foot, 10,600 at 1/4 inch and 15,040 at 1/2 inch.

The model 2021 IPC instead uses gpm capacities, for example Table 1106.2 (4-inch vertical 180 gpm) and Table 1106.3 (4-inch leader 192 gpm); for Virginia work, the VCC's area tables govern.

Last updated: October 2026

Two versions of the same tables

Your permitted exam reference is the model 2021 IPC . In it, storm piping is sized by flow rate : Equation 11-1 converts roof area to gpm, and Table 1106.2 (storm drain pipe), Table 1106.3 (leaders) and Table 1106.6 (gutters) give capacities in gpm. Virginia's VCC 2901.1.1, items 29 to 34, replaces those sections with the older projected-roof-area tables, and adds 1114.1. PSI's bulletin says a state code overrides the national code where they conflict, so for Virginia work, use the Virginia tables below. Be able to read both, because a question may be written from either.

Virginia Table 1106.2(1): circular vertical conductors and leaders

Maximum horizontally projected roof area (square feet):

  • Leader diameter 1 in/hr 2 in/hr 3 in/hr 4 in/hr
  • 2 in see note 1,440 960 720
  • 3 in 8,800 4,400 2,930 2,200
  • 4 in 18,400 9,200 6,130 4,600
  • 5 in 34,600 17,300 11,530 8,650
  • 6 in 54,000 27,000 17,995 13,500
  • 8 in 116,000 58,000 38,660 29,000

The table continues to 12 inches per hour. Each column is the 1-inch-per-hour area divided by the rate, so a rate between columns, such as 3.3, can be handled by dividing the 1-inch value by the rate. The 2-inch row prints 2,280 square feet in the 1-inch column, while its other columns follow 2,880 divided by the rate. Use the printed column for the rate you have. Sizes in the table are circular diameters. Other shapes are allowed if they fully enclose that circle, and interpolation between pipe sizes is permitted.

Virginia Table 1106.2(2): rectangular leaders

  • Leader (width × length, inches) 1 in/hr 2 in/hr 3 in/hr 4 in/hr
  • 1-3/4 × 2-1/2 3,410 1,700 1,130 850
  • 2 × 3 5,540 2,770 1,840 1,380
  • 2-3/4 × 4-1/4 12,830 6,410 4,270 3,200
  • 3 × 4 13,210 6,600 4,400 3,300
  • 3-1/2 × 4 15,900 7,950 5,300 3,970
  • 4 × 6 32,980 16,490 10,990 8,240

For rectangular shapes not in the table, compute an equivalent circular diameter, then use Table 1106.2(1): D e = width × length D_e = \sqrt{\text{width} \times \text{length}} D e ​ = width × length ​

Example: a 3 × 5-inch leader has D e = 15 ≈ 3.87 D_e = \sqrt{15} \approx 3.87 D e ​ = 15 ​ ≈ 3.87 inches, which falls between the 3-inch and 4-inch rows. Interpolation is permitted.

Virginia Table 1106.3: building storm drains and sewers

Under Virginia 1106.3, building storm drains, building storm sewers and their horizontal branches with slopes of 1/2 inch per foot or less are sized by projected roof area. The slope of horizontal branches must be at least 1/8 inch per foot unless otherwise approved .

Pipe size 1/8 in/ft, 1 in/hr 1/8 in/ft, 3 in/hr 1/4 in/ft, 1 in/hr 1/4 in/ft, 3 in/hr 1/2 in/ft, 1 in/hr 1/2 in/ft, 3 in/hr

  • 3 in 3,288 1,096 4,640 1,546 6,576 2,295
  • 4 in 7,520 2,506 10,600 3,533 15,040 5,010
  • 5 in 13,360 4,453 18,880 6,293 26,720 8,900
  • 6 in 21,400 7,133 30,200 10,066 42,800 13,700
  • 8 in 46,000 15,330 65,200 21,733 92,000 30,650
  • 10 in 82,800 27,600 116,800 38,950 171,600 55,200

The table continues to 15-inch pipe and 6 inches per hour. As with sanitary drains, a steeper slope raises capacity: a 4-inch drain at 1 inch per hour goes from 7,520 square feet at 1/8 inch per foot to 15,040 at 1/2 inch per foot.

Virginia Table 1106.6: semicircular gutters

Gutters are sized by projected roof area. Examples at a 1/16-inch-per-foot slope:

  • Gutter diameter 1 in/hr 2 in/hr 3 in/hr 4 in/hr
  • 5 in 2,500 1,250 834 625
  • 6 in 3,840 1,920 1,280 960
  • 8 in 7,960 3,980 2,655 1,990

Steeper gutter slopes (1/8, 1/4 and 1/2 inch per foot) have larger values.

Worked examples (Virginia tables)

Leader. An 8,000 sq ft roof in Richmond at 3.3 inches per hour. Equivalent area at 1 inch per hour: 8,000 × 3.3 = 26,400 sq ft. A 4-inch leader allows 18,400, which is too small. A 5-inch leader allows 34,600, which works.

Leader near the limit. A 5,500 sq ft roof. In Richmond: 5,500 × 3.3 = 18,150, so a 4-inch leader (18,400) works. In Norfolk: 5,500 × 3.4 = 18,700, more than 18,400, so a 5-inch leader is needed.

Horizontal storm drain. A 13,500 sq ft roof in Lynchburg at 3.2 inches per hour, drained at 1/4 inch per foot. Equivalent area: 13,500 × 3.2 = 43,200 sq ft. A 6-inch drain allows 30,200, which is too small. An 8-inch drain allows 65,200, which works.

Rectangular leader. A 3 × 4-inch leader in a 3-inch-per-hour area serves up to 4,400 sq ft (Table 1106.2(2)).

The model 2021 IPC tables (gpm)

Pipe size Vertical drain (gpm), model Table 1106.2 Horizontal at 1/8 in/ft (gpm) Horizontal at 1/4 in/ft (gpm) Leader (gpm), model Table 1106.3

  • 3 in 87 55 79 92
  • 4 in 180 115 163 192
  • 6 in 538 344 487 563
  • 8 in 1,117 714 1,010 1,208

Model 2021 IPC 1106.2 sizes storm drain piping from the flow rate through the roof drain , checked against the roof drain manufacturer's published rating. The model and Virginia methods can produce different answers . In example 3, the flow is 0.0104 × 13,500 × 3.2 ≈ 449 gpm, and model Table 1106.2 would allow a 6-inch drain at 1/4 inch per foot (487 gpm), while Virginia's Table 1106.3 requires 8 inches. On a Virginia job, follow the Virginia table.

Loading diagram... Sizing storm piping with Virginia's area tables