8.2 Water Distribution Design: Flow and Pressure Criteria, Fixture Supplies & Pipe Sizing

Virginia Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Virginia Licensing Law & Standards of Practice

1.1 Exam Format, Permitted References & Open-Book Strategy 1.2 Definitions, Licensure Requirement & Qualification for the Exam 1.3 Standards of Practice: Designations, Address Changes & License Use 1.4 Standards of Conduct, Prohibited Acts & Revocation of Licensure

2 Chapter 2: Renewal, USBC Administration & General Regulations

2.1 License Renewal, Continuing Education & Reinstatement 2.2 Virginia USBC Administration, Permits, Inspections & Required Tests 2.3 General Regulations: Materials, Protection, Support, Trenching & Structural Safety

3 Chapter 3: Plumbing Fixtures, Clearances & Temperature Control

3.1 Minimum Plumbing Facilities: Table 403.1, Calculations & Separate Facilities 3.2 Fixture Installation: Clearances, Compartments, Connections, Showers & Accessibility 3.3 Water Conservation, Temperature-Limiting Devices, Flushing Devices & Emergency Fixtures

4 Chapter 4: Fixture Traps, Trap Seals & Interceptors

4.1 Fixture Traps, Trap Seals & Trap Seal Protection 4.2 Grease Interceptors: Where Required, Sizing, Flow Control & Virginia's Disposer Rule 4.3 Oil Separators, Sand & Lint Interceptors, Other Interceptors & Corrosive Waste

5 Chapter 5: Sanitary Drainage Systems & Sizing

5.1 Drainage Principles & Drainage Fixture Units (Tables 709.1 and 709.2) 5.2 Horizontal Branches, Building Drains & Building Sewers: Slope, Sizing & Separation 5.3 Soil & Waste Stacks, Stack Offsets, Branch Connections & Relief Vents

6 Chapter 6: Drainage Fittings, Cleanouts, Indirect Waste & Sumps

6.1 Drainage Fittings, Changes of Direction, Joints & Prohibited Connections 6.2 Cleanouts: Locations, Spacing, Size, Clearance & Access 6.3 Indirect Waste, Air Gaps, Air Breaks, Waste Receptors & Condensate Disposal 6.4 Sumps, Sewage Pumps, Ejectors & Backwater Valves

7 Chapter 7: Vent Systems & Sizing

7.1 Vent Purpose, Terminals, Outdoor Extensions & Vent Connections 7.2 Trap-to-Vent Distance (Table 909.1) & Vent Pipe Sizing (906) 7.3 Common Vents, Wet Venting & Waste Stack Vents 7.4 Circuit Venting, Combination Waste & Vent, Island, Single-Stack & Air Admittance Valves

8 Chapter 8: Water Supply, Distribution Sizing, Hot Water & Water Heaters

8.1 Water Service, Pipe Materials, Joints, Valves, Pressure Control & Disinfection 8.2 Water Distribution Design: Flow and Pressure Criteria, Fixture Supplies & Pipe Sizing 8.3 Hot Water Supply: Delivery Distance, Temperature Control, Recirculation & Thermal Expansion 8.4 Water Heaters: Installation, Relief Valves, Discharge Piping & Drain Pans

9 Chapter 9: Backflow Prevention & Cross-Connection Control

9.1 Cross-Connections, Backsiphonage, Backpressure & Degree of Hazard 9.2 Air Gaps, Atmospheric Vacuum Breakers & Hose Connection Protection 9.3 Testable Assemblies: RP, Double Check, PVB & SVB; Location, Testing & Virginia Certification 9.4 Protecting Specific Connections: Beverage Dispensers, Boilers, Sprinklers, Irrigation & Equipment

10 Chapter 10: Storm Drainage Systems & Sizing (with Virginia Amendments)

10.1 Storm Drainage Basics: Disposal, Materials, Rainfall Rates & Roof Area 10.2 Sizing Leaders, Conductors, Horizontal Storm Drains & Gutters (Virginia Tables) 10.3 Secondary (Emergency) Roof Drains, Scuppers & Roof Ponding 10.4 Subsoil Drains, Building Subdrains, Storm Sumps, Controlled-Flow Roofs & Continuous Flow

8.2 Water Distribution Design: Flow and Pressure Criteria, Fixture Supplies & Pipe Sizing

Key Takeaways Explain This Topic AI

Table 604.3 minimum flow pressures: 8 psi for most faucets, 20 psi for shower and tub mixing valves and tank water closets, 25 psi for urinal flush valves, 35 psi for siphonic flushometer water closets and 45 psi for blowout flushometer water closets.

Table 604.5 minimum fixture supply sizes: lavatory, bidet, drinking fountain and flush-tank water closet 3/8 inch; most sinks, tubs and showers 1/2 inch; urinal flushometer valve 3/4 inch; and water closet flushometer valve 1 inch.

A fixture supply pipe must end no more than 30 inches from its connection to the fixture (604.5).

In Appendix E Table E103.3(2), a private flush-tank water closet is 2.2 wsfu, a public flushometer-valve water closet 10 wsfu, and a private lavatory 0.7 wsfu total.

From Table E103.3(3), 10 wsfu demands 14.6 gpm in a flush tank system but 27 gpm in a flushometer valve system; the two curves meet at about 1,000 wsfu (208 gpm).

Last updated: October 2026

Design criteria (IPC 604.1 to 604.4)

604.1 and 604.2: the design must follow accepted engineering practice, and sizing methods must be approved . Appendix E gives one method. The IPC appendices are informative unless a jurisdiction adopts them, so the building official decides which method is approved.

604.3: pipe must be sized so that, under peak demand , each fixture supply outlet receives at least the flow and pressure in Table 604.3 . Fixtures not listed use the manufacturer's values.

Table 604.3: required capacity at fixture supply outlets

  • Fixture supply outlet Flow rate (gpm) Flow pressure (psi)
  • Bathtub, balanced-pressure, thermostatic or combination valve 4 20
  • Bidet, thermostatic mixing valve 2 20
  • Combination fixture 4 8
  • Dishwasher, residential 2.75 8
  • Drinking fountain 0.75 8
  • Laundry tray 4 8
  • Lavatory, private 0.8 8
  • Lavatory, public 0.4 8
  • Shower 2.5 8
  • Shower with balanced-pressure, thermostatic or combination valve 2.5 20
  • Sillcock, hose bibb 5 8
  • Sink, residential 1.75 8
  • Sink, service 3 8
  • Urinal, valve 12 25
  • Water closet, blowout, flushometer valve 25 45
  • Water closet, siphonic, flushometer valve 25 35
  • Water closet, flushometer tank 1.6 20
  • Water closet, tank, close coupled 3 20
  • Water closet, tank, one piece 6 20

Table 604.3 sets the minimum supply at the outlet . Table 604.4 sets the maximum consumption of the fixture (for example, 1.6 gallons per flush or 2.5 gpm at 80 psi). Do not confuse the two.

Fixture supplies (IPC 604.5) and manifolds (IPC 604.10)

Table 604.5 minimum fixture supply pipe sizes:

  • Fixture Minimum size
  • Lavatory, bidet, drinking fountain 3/8 inch
  • Water closet, flush tank or flushometer tank 3/8 inch
  • Water closet, one piece 1/2 inch

Bathtub, shower, kitchen sink, laundry, domestic dishwasher, service sink, hose bibb, wall hydrant, urinal flush tank 1/2 inch

  • Sink, flushing rim; urinal, flushometer valve 3/4 inch
  • Water closet, flushometer valve 1 inch

The fixture supply pipe must end no more than 30 inches from the point of connection to the fixture. A reduced-size flexible connector between the supply and the fixture must be an approved type, and the supply pipe must extend to the floor or wall next to the fixture.

Footnote: in a parallel (manifold) system, where the distribution line is 50 feet or less and the pressure at the meter is at least 35 psi , each line may be one size smaller than the table.

604.10.1 manifold sizing (Table 604.10.1): a manifold is sized by total gpm. A 1/2-inch manifold handles 2 gpm at 4 feet per second and 5 gpm at 8 feet per second; 3/4 inch handles 6 and 11 gpm; 1 inch, 10 and 20 gpm. 604.10.2: valves at the manifold are identified by fixture. 604.10.3: manifolds with valves need access.

The fixture unit method (IPC Appendix E)

Hunter's probability method assigns each fixture water supply fixture units (wsfu) , then converts the total wsfu to a design flow in gpm. The method accounts for the fact that not all fixtures run at once.

Table E103.3(2): selected wsfu values (cold / hot / total)

  • Fixture Occupancy Supply control Cold Hot Total
  • Bathroom group Private Flush tank 2.7 1.5 3.6
  • Bathroom group Private Flushometer valve 6.0 3.0 8.0
  • Bathtub Private / Public Faucet 1.0 / 3.0 1.0 / 3.0 1.4 / 4.0
  • Kitchen sink Private / Hotel, restaurant Faucet 1.0 / 3.0 1.0 / 3.0 1.4 / 4.0
  • Lavatory Private / Public Faucet 0.5 / 1.5 0.5 / 1.5 0.7 / 2.0
  • Shower head Private / Public Mixing valve 1.0 / 3.0 1.0 / 3.0 1.4 / 4.0
  • Service sink Offices Faucet 2.25 2.25 3.0
  • Urinal Public 1-inch / 3/4-inch flushometer valve 10.0 / 5.0 — 10.0 / 5.0
  • Washing machine (8 lb) Private / Public Automatic 1.0 / 2.25 1.0 / 2.25 1.4 / 3.0
  • Water closet Private Flush tank 2.2 — 2.2
  • Water closet Private Flushometer valve 6.0 — 6.0
  • Water closet Public Flush tank 5.0 — 5.0
  • Water closet Public Flushometer valve 10.0 — 10.0
  • Water closet Public or private Flushometer tank 2.0 — 2.0

The total for a fixture with hot and cold supply is less than cold plus hot, because both are not drawn at full flow at the same time. Use the cold column to size cold-only piping, the hot column for hot piping, and the total for the service and main up to the water heater branch.

Table E103.3(3): estimating demand

  • Load (wsfu) Flush tank systems (gpm) Flushometer valve systems (gpm)
  • 5 9.4 15.0
  • 10 14.6 27.0
  • 20 19.6 35.0
  • 50 29.1 50.0
  • 100 43.5 67.5
  • 200 65.0 90.0
  • 500 124.0 143.0
  • 1,000 208.0 208.0

A flushometer valve opens fully and draws about 25 gpm for a few seconds (Table 604.3), so even a few flushometers need a large design flow. A flush tank refills slowly. As a system grows, the chance of many simultaneous draws evens out, and the two curves meet at about 1,000 wsfu.

The pressure budget

Appendix E sizes pipe by finding the pressure available for friction:

Start with the minimum available pressure at the source (604.6: design for the minimum).

Subtract elevation: 0.433 psi per foot of rise. One psi lifts water 2.31 feet.

Subtract fixed losses: the water meter, backflow preventer, PRV, softener and filters, using manufacturers' data at the design flow.

Subtract the pressure required at the most remote, highest outlet (Table 604.3, or the manufacturer's value).

Divide what remains by the developed length plus an allowance for fittings to get the allowable friction loss per 100 feet.

Choose pipe sizes from friction-loss charts for the design gpm of each section, and check velocity.

Example: the street has a minimum of 60 psi. The highest flushometer valve water closet (siphonic) is 25 feet above the main, and the meter and backflow assembly lose a combined 12 psi at design flow. Available for friction: 60 − (25 × 0.433 = 10.8) − 12 − 35 = 2.2 psi . That is very little, so the designer must either use larger pipe or add a booster system (604.7).

Velocity

Apart from the manifold table and the general water hammer rule (604.9), the IPC does not set a maximum velocity. The Copper Development Association recommends about 8 feet per second maximum for cold water, about 5 feet per second for hot water up to about 140°F, and 2 to 3 feet per second where water routinely exceeds 140°F, to limit erosion-corrosion and noise. A handy formula is: V = 0.408 × Q d 2 V = \frac{0.408 \times Q}{d^2} V = d 2 0.408 × Q ​

where V is velocity in feet per second, Q is flow in gpm, and d is the inside diameter in inches. Example: 10 gpm in tube with a 0.785-inch inside diameter: V = 0.408 × 10 ÷ 0.616 ≈ 6.6 feet per second .

Loading diagram... Sizing a water distribution system