Study guide

2.1 Source Water Hydrology, Groundwater Protection & Raw Water Quality

Virginia Water/Wastewater Operator Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Virginia Licensing, Regulations & Administrative Standards

1.1 Virginia DPOR Board Structure, License Categories & Scope of Practice 1.2 Experience, Education, Substitutions & Examination Approval 1.3 Renewal, Reinstatement, CPE Requirements & Discipline 1.4 Virginia Drinking Water & Wastewater Environmental Governance 1.5 Facility Classification & Minimum Operator Attendance 1.6 The ABC/WPI Exam Blueprint, References & Test-Day Rules 1.7 License Maintenance, Reporting Duties & Professional Conduct

2 Chapter 2: Source Water & Drinking Water Treatment Unit Processes

2.1 Source Water Hydrology, Groundwater Protection & Raw Water Quality 2.2 Coagulation, Flocculation & Sedimentation Processes 2.3 Filtration Technologies & Media Management 2.4 Disinfection Chemistry, CT Calculations & Disinfection Byproducts 2.5 Corrosion Control, Softening & Fluoridation Chemistry 2.6 Pretreatment: Screening, Presedimentation, Aeration & Preoxidation 2.7 Filter Backwash, Surface Wash, Air Scour & Filter Surveillance 2.8 Membrane Systems: MF, UF, NF and RO Operation & Integrity Testing 2.9 Water Treatment Residuals: Handling, Thickening & Disposal 2.10 Chemical Feed Systems: Metering Pumps, Dry Feeders & Calibration 2.11 Process Monitoring, Trend Interpretation & Plant Optimization 2.12 Iron and Manganese, Taste-and-Odor Control, GAC & PFAS

3 Chapter 3: Wastewater Treatment, Biological Processes & Biosolids

3.1 Preliminary Treatment & Primary Clarification 3.2 Activated Sludge Dynamics & Secondary Process Control 3.3 Attached Growth Systems & Advanced Biological Processes 3.4 Biological & Chemical Nutrient Removal (BNR/ENR) 3.5 Solids Thickening, Digestion & Biosolids Management 3.6 Wastewater Characteristics, Influent Loading & Industrial Pretreatment 3.7 Secondary Clarifier Operation & Sludge Blanket Control 3.8 Lagoons, Stabilization Ponds & Natural Treatment Systems 3.9 Tertiary Filtration, Effluent Polishing & Water Reuse 3.10 Wastewater Disinfection & Dechlorination Systems 3.11 Aeration Systems, Blowers, Diffusers & Dissolved Oxygen Control 3.12 Digester Gas Handling, Cogeneration & Gas System Safety 3.13 Biosolids Land Application, Part 503 & Virginia Permitting

4 Chapter 4: Distribution Networks, Collection Systems & Hydraulic Systems

4.1 Water Distribution Networks, Storage & Pressure Management 4.2 Cross-Connection Control & Backflow Prevention Assemblies 4.3 Wastewater Collection Systems, Lift Stations & Inflow/Infiltration 4.4 Centrifugal & Positive Displacement Pumps 4.5 Motors, Drives, Control Systems & SCADA 4.6 Storage Tank Inspection, Meters, Services & Distribution Appurtenances 4.7 Main Disinfection, Flushing & Distribution Water Quality Management 4.8 Sewer Cleaning, CCTV Inspection & Collection System Rehabilitation 4.9 Maintenance Programs, Asset Management & Pump Efficiency Testing 4.10 Odor Control, Standby Power & Ancillary Plant Equipment

5 Chapter 5: Laboratory Analysis, Environmental Safety & Applied Math

5.1 Water & Wastewater Laboratory Analysis & QA/QC Protocols 5.2 Confined Space Entry, Chemical Safety & OSHA/VOSH Compliance 5.3 Hydraulic, Dosage & Pounds Formula Math 5.4 Wastewater Process & Loading Rate Mathematics 5.5 Drinking Water Microbiology & the Revised Total Coliform Rule 5.6 Wastewater Laboratory Analysis: Nutrients, Metals, WET & Regulatory Testing 5.7 Instrument Calibration, Online Analyzers & Data Validation 5.8 Process Control Testing: Jar Tests, Settleometer & Microscopic Examination 5.9 Chemical Receiving, Storage, Spill Response & Hazardous Waste 5.10 Electrical Safety, Fall Protection, Excavation & Traffic Control 5.11 PPE, Respiratory Protection & Biological Hazards 5.12 Advanced Applied Math: Mass Balance, Blending & Efficiency

6 Chapter 6: Regulatory Compliance, Reporting & Plant Administration

6.1 Safe Drinking Water Act Compliance: MCLs, Monitoring & Violations 6.2 Public Notification, Consumer Confidence Reports & Customer Complaints 6.3 VPDES Permit Compliance, DMRs & Overflow Reporting 6.4 Operating Records, Logbooks, Reports & Data Integrity 6.5 Emergency Response Planning & AWIA Risk and Resilience 6.6 Facility Security, SCADA Cybersecurity & Vulnerability Assessment 6.7 Budgeting, Procurement, Inventory & Capital Planning 6.8 Supervision, Training, SOP Development & Resource Optimization

2.1 Source Water Hydrology, Groundwater Protection & Raw Water Quality

Key Takeaways Explain This Topic AI

Unconfined aquifers have a water table at atmospheric pressure, whereas confined (artesian) aquifers are bounded by impermeable confining layers (aquitards) and maintain piezometric heads above the top of the aquifer.

Drawdown is the exact vertical difference between static water level (SWL) and pumping water level (PWL); specific capacity equals pumping rate in gallons per minute divided by drawdown in feet (gpm/ft).

The cone of depression defines a 3D hydraulic gradient slope sloping toward the wellbore, governing the well's radius of influence and recharge capture zone.

Sanitary well construction mandates a pressure-grouted neat cement annular seal extending at least 20 feet below grade and minimum horizontal sanitary setbacks (50 feet from non-sewage sources, 100 feet from sewage/septic sources per VDH regulations).

Raw water quality indicators—turbidity (NTU), true vs. apparent color (PCU), pH, total alkalinity (mg/L as CaCO3), total hardness, natural organic matter (NOM/TOC), and total dissolved solids (TDS)—determine treatment train selection and chemical dosages.

Last updated: August 2026

Source Water Hydrology & Hydrogeology

Water treatment begins with understanding the origin, movement, and quality of raw water sources. The hydrologic cycle continuously circulates water through evaporation, transpiration, condensation, precipitation, surface runoff, infiltration, and groundwater percolation. Drinking water utilities extract water from two primary source classifications: surface water (rivers, streams, lakes, and impoundments) and groundwater (unconfined, confined, and karst aquifers).

Surface Water Hydrology & Reservoir Dynamics

Surface water supplies are characterized by open exposure to the atmosphere and terrestrial runoff. Their yield depends on watershed area, precipitation patterns, topography, vegetation, and land use. Rivers and streams exhibit rapid fluctuations in flow rate, turbidity, temperature, microbial pathogen density, and chemical composition following storm events.

In deep lakes and reservoirs, seasonal thermal changes induce vertical water column stratification:

Epilimnion : The warm, less dense upper layer in direct contact with sunlight and atmospheric oxygen, maintaining high dissolved oxygen (DO) and active photosynthetic biological communities.

Metalimnion (Thermocline) : The transitional middle zone where temperature drops rapidly with increasing depth (at a rate > 1 ∘ C > 1^\circ\text{C} > 1 ∘ C per meter of depth).

Hypolimnion : The cold, dense, isolated bottom layer cut off from atmospheric re-aeration and sunlight.

During prolonged summer stratification, biological respiration and the decay of settling organic matter consume oxygen in the hypolimnion, driving it into anoxic (anaerobic) conditions. Under low redox potentials, insoluble oxidized minerals in bottom sediments are chemically reduced into soluble forms: Insoluble F e 3 + (ferric iron) → anaerobic reduction Soluble F e 2 + (ferrous iron) \text{Insoluble } Fe^{3+} \text{ (ferric iron)} \xrightarrow{\text{anaerobic reduction}} \text{Soluble } Fe^{2+} \text{ (ferrous iron)} Insoluble F e 3 + (ferric iron) anaerobic reduction ​ Soluble F e 2 + (ferrous iron) Insoluble M n 4 + (manganic manganese) → anaerobic reduction Soluble M n 2 + (manganous manganese) \text{Insoluble } Mn^{4+} \text{ (manganic manganese)} \xrightarrow{\text{anaerobic reduction}} \text{Soluble } Mn^{2+} \text{ (manganous manganese)} Insoluble M n 4 + (manganic manganese) anaerobic reduction ​ Soluble M n 2 + (manganous manganese) Sulfate ( S O 4 2 − ) → bacterial reduction Hydrogen Sulfide ( H 2 S ) \text{Sulfate } (SO_4^{2-}) \xrightarrow{\text{bacterial reduction}} \text{Hydrogen Sulfide } (H_2S) Sulfate ( S O 4 2 − ​ ) bacterial reduction ​ Hydrogen Sulfide ( H 2 ​ S )

Additionally, cyanobacteria (blue-green algae) proliferate in nutrient-rich epilimnetic waters, producing organic taste-and-odor metabolites such as geosmin (earthy odor) and 2-methylisoborneol (MIB) (musty odor), which have human sensory detection thresholds below 10 ng/L 10\text{ ng/L} 10 ng/L ( 10 parts per trillion 10\text{ parts per trillion} 10 parts per trillion ).

During seasonal transitions in autumn and spring, the surface water cools or warms to 4 ∘ C 4^\circ\text{C} 4 ∘ C (maximum water density), destabilizing the water column. Wind-induced mixing creates reservoir turnover , abruptly distributing anoxic, mineral-rich, foul-smelling hypolimnetic water throughout the intake depth and requiring immediate treatment adjustments.

Groundwater Hydrogeology & Aquifer Dynamics

Groundwater resides in subsurface porous geological formations known as aquifers . The movement of groundwater through porous media is governed by Darcy's Law : Q = K ⋅ A ⋅ i = K ⋅ A ⋅ ( d h d L ) Q = K \cdot A \cdot i = K \cdot A \cdot \left(\frac{dh}{dL}\right) Q = K ⋅ A ⋅ i = K ⋅ A ⋅ ( d L d h ​ )

Where:

Q Q Q = Groundwater volumetric discharge rate ( ft 3 / day \text{ft}^3/\text{day} ft 3 / day or m 3 / day \text{m}^3/\text{day} m 3 / day )

  • K K K = Hydraulic conductivity of the media ( ft/day \text{ft/day} ft/day or m/day \text{m/day} m/day )
  • A A A = Cross-sectional area perpendicular to flow ( ft 2 \text{ft}^2 ft 2 or m 2 \text{m}^2 m 2 )

i = d h d L i = \frac{dh}{dL} i = d L d h ​ = Hydraulic gradient (head loss per unit flow length, dimensionless)

Geological formations are categorized based on their hydraulic properties:

Formation Type Definition Typical Materials Hydrological Significance

Unconfined Aquifer Aquifer where the upper boundary is the water table (phreatic surface) at atmospheric pressure. Sand, gravel, alluvium Directly recharged by local infiltration; highly vulnerable to surface contaminants.

Confined Aquifer Aquifer trapped between low-permeability confining units (aquitards) under hydrostatic pressure. Sandstone, fractured limestone bounded by clay/shale Piezometric surface rises above aquifer top; protected from immediate surface pollution.

Aquitard / Aquiclude Low-permeability geological stratum that restricts or prevents groundwater flow. Dense clay, massive shale, un-fractured crystalline rock Forms hydraulic barriers separating layered aquifer systems.

Karst Aquifer Soluble rock characterized by sinkholes, caves, and rapid conduit flow channels. Limestone, dolomite ( C a C O 3 , M g C O 3 CaCO_3, MgCO_3 C a C O 3 ​ , M g C O 3 ​ ) Extremely high flow velocities ( > 100 ft/hr > 100\text{ ft/hr} > 100 ft/hr ); behaves hydraulically like surface water.

Public Water Supply Well Anatomy & Mechanics

A properly constructed public water supply well must deliver a reliable yield while preventing surface water, shallow contaminants, and undesirable aquifers from entering the wellbore. Surface Pad / Sanitary Well Cap

  • [==============================]
  • || <-- Casing Vent (Screened)
  • +---------||---------+
  • | //// Grout //// | <-- Annular Grout Seal (>= 20 ft)
  • | | | |
  • Ground Surface =====|==|==============|==|=====
  • | | | |
  • | | Steel or | |
  • Unconsolidated | | PVC Casing | |
  • Formation | | | |
  • | | | |
  • | | | |
  • -------------------|--|--------------|--|-----
  • Static Water Level : :~~~~~~~~~~~~~~: : <-- SWL
  • | | | |
  • Confining Layer | | | |
  • ====================|==|==============|==|=====
  • Pumping Water Level : :--------------: : <-- PWL (during pumping)
  • | | | |
  • | | Submersible | |
  • | | Pump Bowl | |
  • | +==============+ |
  • Aquifer Formation | | Well Screen | | <-- Continuous Slot Screen
  • | | oooooooooooo | |
  • | | oooooooooooo | | <-- Gravel Pack in Annulus
  • +--+==============+--+
  • Well Components & Protective Barriers

Well Casing : Heavy-wall carbon steel or NSF/ANSI 61 certified PVC pipe that lines the drilled borehole, supporting the earth walls and preventing borehole collapse.

Annular Grout Seal : The continuous void between the drilled borehole wall and the outer diameter of the casing. It must be pressure-grouted from the bottom up using neat cement grout (Class A Portland cement and clean water, 5 − 6 gal water per 94-lb sack 5-6\text{ gal water per 94-lb sack} 5 − 6 gal water per 94-lb sack ) or high-solids sodium bentonite slurry. The seal must extend at least 20 feet 20\text{ feet} 20 feet below the surface (or into the primary confining layer) to prevent surface runoff from channeling down the casing exterior.

Sanitary Well Cap & Casing Extension : The casing must extend at least 12 to 18 inches 12\text{ to }18\text{ inches} 12 to 18 inches above the finished ground grade or 100 -year 100\text{-year} 100 -year flood elevation. The top is sealed with a watertight sanitary gasketed cap equipped with a downward-facing, corrosion-resistant 24-mesh non-corrodible screen vent to allow air displacement without admitting insects, dirt, or vermin.

Pitless Adapter or Unit : A specialized mechanical connection installed below the frost line that allows horizontal discharge piping to penetrate the well casing through a watertight, pressurized O-ring seal while keeping the wellhead accessible from the surface.

Well Screen : A precision-fabricated, continuous-slot wire-wound screen installed in unconsolidated sand/gravel formations. The slot opening size is selected based on a laboratory sieve analysis of the aquifer formation to retain 90 % 90\% 90% of the surrounding gravel pack.

Artificial Gravel Pack : Sized, rounded, washed silica quartz gravel placed in the annular space between the screen and the borehole to stabilize the formation, prevent fine sand pumping, and lower entrance velocities.

Well Hydraulics, Pumping Tests & Operating Formulas

When a well pump operates, water is drawn from the aquifer into the screen, creating an outward-expanding hydraulic depression in the water table or potentiometric surface. Ground Surface

  • =============================================================
  • | | | |
  • | | | <-- Well Casing |
  • ------+---------------------+-+---------------------+-------
  • Static Water Level (SWL) | | |
  • \ | | / <-- Piezometric Surface
  • \ | | / (Idle)
  • \_ | | _/
  • \_ | | _/
  • \___ | | ___/
  • \____ | | ____/ <-- Cone of Depression
  • \_____ | | _____/
  • ---------------------------\+-+/----------------------------
  • Pumping Water Level (PWL) |X| <-- Pump
  • |X|
  • <---------------------------> | <--------------------------->
  • Radius of Influence (R) Radius of Influence (R)
  • Fundamental Hydraulic Definitions & Math

Static Water Level (SWL) : The vertical distance from a reference datum (usually top of well casing) to the water surface when the pump has been idle and the aquifer is fully recovered.

Pumping Water Level (PWL) : The vertical distance from the reference datum to the stabilized water surface while the well is pumping at a steady discharge rate Q Q Q .

Drawdown ( D D DD DD ) : The physical decline in water level caused by pumping: D D = PWL − SWL DD = \text{PWL} - \text{SWL} DD = PWL − SWL

Specific Capacity ( S C SC SC ) : The yield of the well per unit of drawdown, serving as the most vital diagnostic indicator of well performance and well screen efficiency: S C = Pumping Rate ( Q ) Drawdown ( D D ) = gpm ft of drawdown SC = \frac{\text{Pumping Rate } (Q)}{\text{Drawdown } (DD)} = \frac{\text{gpm}}{\text{ft of drawdown}} SC = Drawdown ( DD ) Pumping Rate ( Q ) ​ = ft of drawdown gpm ​

Specific Yield & Specific Retention : In an unconfined aquifer, total porosity η \eta η is divided into Specific Yield ( S y S_y S y ​ , water drained by gravity) and Specific Retention ( S r S_r S r ​ , water held against gravity by capillary forces): η = S y + S r \eta = S_y + S_r η = S y ​ + S r ​ .

Cone of Depression : The three-dimensional, inverted funnel-shaped depression in the water table surrounding a pumping well.

Radius of Influence ( R R R ) : The horizontal radial distance from the center of the wellbore to the outer edge of the cone of depression where drawdown is zero ( D D = 0 DD = 0 DD = 0 ).

Well Interference : When multiple production wells operate in close proximity, their cones of depression overlap, causing compounded drawdown, reduced specific capacities, and increased energy consumption.

Well Diagnostic Math Example

A municipal well has a static water level of 42.0 ft 42.0\text{ ft} 42.0 ft below top of casing. After pumping continuously at 600 gpm 600\text{ gpm} 600 gpm for 24 hours, the pumping water level stabilizes at 87.0 ft 87.0\text{ ft} 87.0 ft .

Calculate Drawdown ( D D DD DD ) : D D = 87.0 ft − 42.0 ft = 45.0 ft DD = 87.0\text{ ft} - 42.0\text{ ft} = 45.0\text{ ft} DD = 87.0 ft − 42.0 ft = 45.0 ft

Calculate Specific Capacity ( S C SC SC ) : S C = 600 gpm 45.0 ft = 13.33 gpm/ft SC = \frac{600\text{ gpm}}{45.0\text{ ft}} = 13.33\text{ gpm/ft} SC = 45.0 ft 600 gpm ​ = 13.33 gpm/ft

Operational Insight : If a future test at 600 gpm 600\text{ gpm} 600 gpm yields a drawdown of 60.0 ft 60.0\text{ ft} 60.0 ft ( S C = 10.0 gpm/ft SC = 10.0\text{ gpm/ft} SC = 10.0 gpm/ft ), the 25 % 25\% 25% loss in specific capacity alerts the operator to well screen encrustation (iron/manganese deposits or calcium carbonate scaling), biofouling from iron bacteria ( Gallionella ), gravel pack siltation, or a declining regional aquifer water table.

Raw Water Quality Parameters & Analytical Methods

Water operators must evaluate raw water parameters to establish baseline treatment targets and detect rapid environmental changes.

Parameter Analytical Method / Units Water Quality Significance Operational Impact

Turbidity Nephelometry ( 90 ∘ 90^\circ 9 0 ∘ scattered light) / NTU Suspended clay, silt, algae, and micro-particles; shields pathogens from disinfectants. Determines primary coagulant dose and filter run durations.

Apparent Color Visual comparison with Platinum-Cobalt standards / PCU Unfiltered sample color caused by both dissolved substances and suspended matter. Baseline visual aesthetic check.

True Color Spectrophotometry at 455 nm 455\text{ nm} 455 nm or visual comparator after 0.45 μ m 0.45\,\mu\text{m} 0.45 μ m filtration or centrifugation / PCU Dissolved colloidal vegetable extracts, tannins, lignins, humic/fulvic acids. Indicates Natural Organic Matter (NOM); drives coagulant demand and DBP precursor formation.

pH Electrometric (glass electrode) / Standard Units ( 0 − 14 0-14 0 − 14 ) − log ⁡ 10 [ H + ] -\log_{10}[H^+] − lo g 10 ​ [ H + ] ; controls chemical equilibrium, coagulant solubility, and chlorine speciation. Alum optimal pH: 5.8 − 7.5 5.8-7.5 5.8 − 7.5 ; Ferric optimal pH: 4.0 − 11.0 4.0-11.0 4.0 − 11.0 .

Total Alkalinity Titration with 0.02 N H 2 S O 4 0.02\text{ N } H_2SO_4 0.02 N H 2 ​ S O 4 ​ to p H 4.5 pH\,4.5 p H 4.5 endpoint / mg/L as C a C O 3 CaCO_3 C a C O 3 ​ Acid-neutralizing capacity; primarily bicarbonate ( H C O 3 − HCO_3^- H C O 3 − ​ ), carbonate ( C O 3 2 − CO_3^{2-} C O 3 2 − ​ ), and hydroxide ( O H − OH^- O H − ). Coagulant hydrolysis consumes alkalinity; prevents pH depression during metal salt addition.

Total Hardness EDTA Titrimetric Method / mg/L as C a C O 3 CaCO_3 C a C O 3 ​ Sum of polyvalent cations, primarily Calcium ( C a 2 + Ca^{2+} C a 2 + ) and Magnesium ( M g 2 + Mg^{2+} M g 2 + ). Soft: 0 − 60 0-60 0 − 60 ; Mod. Hard: 61 − 120 61-120 61 − 120 ; Hard: 121 − 180 121-180 121 − 180 ; Very Hard: > 180 mg/L > 180\text{ mg/L} > 180 mg/L . Determines softening requirement.

Total Organic Carbon (TOC) High-temperature catalytic combustion or UV-persulfate oxidation / mg/L Direct quantification of all organically bound carbon in raw water. EPA Enhanced Coagulation precursor removal rule; primary driver of TTHM and HAA5 formation.

UV-254 Absorbance & SUVA Spectrophotometer at 254 nm 254\text{ nm} 254 nm wavelength / cm − 1 \text{cm}^{-1} cm − 1 Specific UV Absorbance: SUVA = UV 254 ( cm − 1 ) × 100 DOC ( mg/L ) \text{SUVA} = \frac{\text{UV}_{254}\,(\text{cm}^{-1}) \times 100}{\text{DOC}\,(\text{mg/L})} SUVA = DOC ( mg/L ) UV 254 ​ ( cm − 1 ) × 100 ​ . SUVA > 4.0 L/(mg ⋅ m) \text{SUVA} > 4.0\text{ L/(mg}\cdot\text{m)} SUVA > 4.0 L/(mg ⋅ m) indicates hydrophobic, aromatic, humic matter amenable to coagulation.

Total Dissolved Solids (TDS) Gravimetric drying at 180 ∘ C 180^\circ\text{C} 18 0 ∘ C or Electrical Conductivity (EC) / mg/L Total dissolved mineral salts and inorganic ions ( N a + , C a 2 + , C l − , S O 4 2 − Na^+, Ca^{2+}, Cl^-, SO_4^{2-} N a + , C a 2 + , C l − , S O 4 2 − ​ ). Secondary MCL: 500 mg/L 500\text{ mg/L} 500 mg/L ; high TDS increases water corrosivity and conductivity.

Virginia Department of Health (VDH) Source Standards & Sanitary Surveys

In Virginia, the Virginia Department of Health (VDH) Office of Drinking Water (ODW) enforces the Waterworks Regulations (12 VAC 5-590) to protect public water supplies.

Well Classification & Sanitary Setbacks in Virginia

VDH classifies public water supply wells based on construction depth and geological isolation:

Class I : Wells constructed in consolidated rock or deep protected confined aquifers with continuous casing and pressure-grouted annular space extending at least 100 feet 100\text{ feet} 100 feet deep.

Class II (A & B) : Wells constructed in intermediate geological strata with pressure-grouted casing extending at least 50 feet 50\text{ feet} 50 feet (Class IIA) or 20 feet 20\text{ feet} 20 feet (Class IIB).

VDH mandates strict horizontal separation distances (sanitary setbacks) from potential contamination sources within the dedicated wellhead protection property: PUBLIC WELLHEAD

  • (*)
  • |
  • +-----------------------+-----------------------+
  • | |
  • 50-Foot Radius 100-Foot Radius
  • [Clean Horizontal Zone] [Sanitary Protection Zone]
  • Property boundaries - Gravity sewer pipes (cast iron)
  • Stormwater retention ditches - Septic tanks & drain fields
  • Paved roadways / parking lots - Manure storage & livestock pens
  • Barnyards & non-sewage drains - Underground fuel/chemical storage

Critical Virginia Standards :

50-Foot Radius : Absolute dedicated ownership/control zone around the wellhead free from all structures and non-sewage contamination sources.

100-Foot Radius : Minimum horizontal setback from any septic tank, drainfield, sewer main, pit privy, or sewage conveyance pipe.

200 to 500-Foot Setbacks : Applied to major chemical storage, pesticide mixing facilities, solid waste landfills, and industrial waste lagoons.

Groundwater Under the Direct Influence of Surface Water (GWUDI)

Under EPA and VDH rules, any groundwater source displaying direct hydraulic connection to surface water is designated as GWUDI and must comply with all filtration and disinfection requirements of the Surface Water Treatment Rules.

Criteria Triggering a GWUDI Assessment :

Well constructed with shallow casing ( < 50 ft < 50\text{ ft} < 50 ft ) in unconfined alluvial sand/gravel or karst limestone terrain.

Well located within 200 feet 200\text{ feet} 200 feet of a lake, reservoir, river, or perennial stream.

Water quality measurements exhibiting rapid fluctuations in turbidity, water temperature, conductivity, or pH that correlate directly with local precipitation and surface stream stages.

Microscopic Particulate Analysis ( MPA ) identifying surface bio-indicators: diatoms, green algae, rotifers, insect parts, or protozoan parasites ( Giardia lamblia cysts or Cryptosporidium parvum oocysts).

Loading diagram... Groundwater Hydraulics & Cone of Depression