5.4 Grounded Conductors, Feeders, Outside Circuits & Surge Protection (Articles 200, 215, 225, 280, 285)

Washington Journeyman Electrician 01 General Journey Level

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Structure & Open-Book Code Navigation

1.1 Washington 01 Electrician Licensing Pathway & Exam Structure 1.2 National Electrical Code Architecture & Fast Lookup Strategies 1.3 Open-Book Exam Rules, Reference Preparation & Pacing

2 Chapter 2: Electrical Theory & Fundamental Math

2.1 Ohm's Law, Joule's Law & Circuit Analysis 2.2 AC Fundamentals, Reactance & Power Factor 2.3 Three-Phase Power Calculations: Wye & Delta Configurations

3 Chapter 3: General Installation Requirements & Conductor Sizing

3.1 Installation Requirements & Working Space Clearances 3.2 Conductor Sizing & Table 310.16 Ampacity 3.3 Temperature Correction Factors & Raceway Derating

4 Chapter 4: Wiring Methods, Raceways & Enclosure Calculations

4.1 Common Wiring Methods & Cable Assemblies 4.2 Conduit & Tubing Installation and Fill Calculations 4.3 Box Fill & Pull Box Sizing Calculations 4.4 Flexible Raceways, ENT, Wireways, Cable Trays, Specialty Cables & Plenum Rules

5 Chapter 5: Branch Circuits, Feeders & Overcurrent Protection

5.1 Branch Circuit Ratings, Receptacle Placement & Lighting 5.2 GFCI, AFCI & Special Protection Requirements 5.3 Overcurrent Protection & Feeder Tap Rules 5.4 Grounded Conductors, Feeders, Outside Circuits & Surge Protection (Articles 200, 215, 225, 280, 285) 5.5 Overcurrent Device Location, Fuses, Circuit Breakers & Transformer Secondary Conductors (Article 240)

6 Chapter 6: Grounding & Bonding (Article 250)

6.1 Grounding vs. Bonding: Core Principles & Definitions 6.2 Grounding Electrode Systems & GEC Sizing 6.3 Main Bonding Jumpers & Equipment Grounding Conductor Sizing

7 Chapter 7: Services, Feeders & Load Calculations

7.1 Electrical Services & Service Equipment (Article 230) 7.2 Dwelling Unit Load Calculations: Standard & Optional Methods 7.3 Commercial Load Calculations & Voltage Drop

8 Chapter 8: Equipment for General Use & Equipment Over 1000 Volts (Articles 400-490)

8.1 Flexible Cords, Fixture Wires, Switches, Receptacles & Panelboards (Articles 400-408) 8.2 Luminaires, Appliances, Space Heating & Other Equipment (Articles 410-427, 455-480) 8.3 Equipment Over 1000 Volts (Article 490 and Related Rules)

9 Chapter 9: Motors, HVAC Equipment, Generators & Transformers (Articles 430-450)

9.1 Motor Branch Circuit Conductor Sizing & Overloads 9.2 Motor Short-Circuit Protection & Disconnecting Means 9.3 Transformers, Generators & Hermetic HVAC Equipment

10 Chapter 10: Hazardous Locations & Special Occupancies (Articles 500-590)

10.1 Hazardous (Classified) Locations (Articles 500–516) 10.2 Health Care Facilities, Places of Assembly & Theaters (Articles 517-540) 10.3 Agricultural Buildings, Mobile Homes, RV Parks, Marinas & Temporary Installations (Articles 545-590)

11 Chapter 11: Special Equipment (Articles 600-695)

11.1 Signs, Cranes, Elevators, EV Charging, Welders, IT Rooms & Industrial Machinery (Articles 600-670) 11.2 Swimming Pools, Spas, Hot Tubs & Fountains (Article 680) 11.3 Solar Photovoltaic Systems, Fuel Cells, Wind & Fire Pumps (Articles 690-695)

12 Chapter 12: Emergency Systems, Special Conditions & Communications (Articles 700-830)

12.1 Emergency, Legally Required & Optional Standby Systems (Articles 700-702) 12.2 Interconnected Power Sources, Energy Storage, Power-Limited Circuits, Fire Alarm & Communications (Articles 705-830)

13 Chapter 13: Washington Electrical Laws & Administrative Code (RCW 19.28 & WAC 296-46B)

13.1 Certificates of Competency, Specialty Scopes & Renewal 13.2 Trainees, Supervision Ratios, Apprenticeship & Qualifying Experience 13.3 Electrical Contractors, Administrators, Bonds & Exemptions 13.4 Permits, Inspections, Class A & Class B Work, and Plan Review 13.5 Civil Penalties, Appeals, Exam Rules & Certificate Discipline 13.6 WAC 296-46B Amendments: Adoption, General Rules, Services, Grounding & Wiring (NEC Chapters 1-4) 13.7 WAC 296-46B Amendments: Special Occupancies, Special Equipment, Emergency Systems & Communications (NEC Chapters 5-8)

5.4 Grounded Conductors, Feeders, Outside Circuits & Surge Protection (Articles 200, 215, 225, 280, 285)

Key Takeaways Explain This Topic AI

Grounded conductors 6 AWG and smaller must have a continuous white or gray finish or three continuous white or gray stripes; 4 AWG and larger may instead be marked white or gray at each termination (NEC 200.6).

A white or gray conductor re-identified for a switch loop may be used only as the supply to the switch, never as the return to the outlet (NEC 200.7(C)(1)).

Feeder conductors must have an ampacity of at least the noncontinuous load plus 125 percent of the continuous load before any adjustment or correction factors are applied (NEC 215.2(A)(1)).

A building supplied by a feeder needs a disconnecting means for all ungrounded conductors, located outside or inside nearest the point of entrance, with no more than six disconnects (NEC 225.31, 225.33).

In the 2020 NEC, Article 285 covers surge-protective devices rated 1000 volts or less, and Article 280 covers surge arresters over 1000 volts.

Last updated: September 2026

Why this section matters

Articles 200 through 225 and 280 through 285 carry about three questions on the PSI outline. The branch-circuit rules (210) and load calculations (220) are in Sections 5.1, 5.2, 7.2, and 7.3. This section covers the rest: Article 200 (grounded conductors), 215 (feeders), 225 (outside branch circuits and feeders), and 280/285 (surge protection).

Identifying the grounded conductor (Article 200)

Conductor size Permitted identification (200.6)

6 AWG and smaller Continuous white or gray outer finish, or three continuous white or gray stripes along the length on insulation that is not green

4 AWG and larger Any of the above, or a distinctive white or gray marking encircling the conductor at each termination, applied at installation

Flexible cords Methods in 400.22

More than one system in the same enclosure (200.6(D)): when grounded conductors of different systems share a raceway, box, or enclosure (for example, a 208Y/120 V neutral and a 480Y/277 V neutral), each system's grounded conductor must be identifiable. Typically one system uses white and the other gray, or white with a colored stripe that is not green. The method must be documented or posted.

Using white or gray for something else (200.7): generally prohibited, with exceptions:

In a cable assembly, a white or gray conductor may be used as an ungrounded conductor if it is permanently re-identified (tape, paint, or other effective means) at every location where it is visible and accessible.

In a switch loop , the re-identified white or gray conductor may be used only for the supply to the switch , never as the return conductor from the switch to the outlet (200.7(C)(1)).

Terminals and polarity (200.9-200.11): the identified terminal for the grounded conductor is whitish or silver in color. On screw-shell lampholders the shell connects to the grounded conductor. No grounded conductor may be attached to a terminal in a way that reverses the designated polarity.

Feeders (Article 215)

Rule 2020 NEC

Feeder conductor ampacity before adjustment or correction is at least the noncontinuous load plus 125% of the continuous load ; after adjustment and correction it is at least the load served 215.2(A)(1)

If a feeder carries the whole load of service conductors rated 55 A or less , the feeder ampacity may not be less than the service conductors' ampacity 215.2(A)(3)

Feeder overcurrent device rated at least noncontinuous load plus 125% of continuous load, unless the assembly is listed for 100% operation 215.3

Ground-fault protection of equipment for feeder disconnects rated 1000 A or more on solidly grounded wye systems over 150 V to ground and not over 600 V phase-to-phase, unless provided on the supply side 215.10

Where premises have more than one nominal voltage system, each ungrounded feeder conductor must be identified by phase or line and system at every termination, connection, and splice point, and the method documented or posted 215.12(C)

Outside branch circuits and feeders (Article 225)

Article 225 covers overhead and underground circuits run outdoors between buildings or to outdoor equipment on the same premises.

Overhead clearances (225.18, 225.19): the same heights as overhead services in 230.24 (Section 7.1):

  • 10 ft above pedestrian areas at 150 V or less to ground;
  • 12 ft over residential property and driveways at 300 V or less to ground;
  • 15 ft over those areas above 300 V;
  • 18 ft over public streets, alleys, roads, and parking areas subject to truck traffic;

8 ft above roofs, with the same exceptions as services.

Washington adds a 3-ft roof clearance where the voltage between conductors is 300 V or less and the roof is guarded or isolated (WAC 296-46B-225).

Conductor size for overhead spans (225.6(A)): 10 AWG copper or 8 AWG aluminum for spans up to 50 ft; 8 AWG copper or 6 AWG aluminum for longer spans (600 V and less).

Supply and disconnects for a building:

A building or structure is generally supplied by only one feeder or branch circuit (225.30). Exceptions include fire pumps, emergency and standby systems, and large capacity needs with permission.

A disconnecting means must open all ungrounded conductors that supply or pass through the building (225.31(A)). It must be readily accessible , located outside or inside nearest the point of entrance of the conductors (225.31(B)).

No more than six disconnects per supply, grouped (225.33).

The disconnect must be suitable for use as service equipment , with limited exceptions (225.36).

Washington treats a disconnect on the building, or within sight and within 15 ft of it, as "in the building" and requires a half-inch-letter identification plate (WAC 296-46B-225).

Vegetation such as trees may not be used to support overhead conductor spans (225.26).

Grounding at the second building (250.32): each building needs its own grounding electrode system. A feeder to a separate building includes an equipment grounding conductor . The grounded (neutral) conductor is not bonded to the equipment grounding conductor at the second building's disconnect, except for certain existing installations with no parallel metallic paths.

Surge arresters and surge-protective devices (Articles 280, 285)

In the 2020 NEC:

Article 280 covers surge arresters over 1000 V (utility and medium-voltage equipment).

Article 285 covers surge-protective devices (SPDs) rated 1000 V or less . SPDs must be listed and marked with a short-circuit current rating, and may not be installed where the available fault current exceeds that rating.

SPD type Where it goes

Type 1 Permanently connected. Intended for the line side of the service disconnect overcurrent device, between the service transformer secondary and the service equipment; also permitted on the load side

Type 2 Permanently connected, on the load side of the service disconnect overcurrent device, including at branch panelboards

Type 3 Point-of-utilization devices on the load side of branch-circuit overcurrent protection; where the manufacturer's instructions call for it, at least 30 ft of conductor length from the service or separately derived system disconnect (285.25)

Type 4 Component SPDs, including those built into other equipment

SPD leads should be kept as short as practicable and avoid unnecessary bends, because lead length adds let-through voltage. Dwelling services must have a Type 1 or Type 2 SPD integral to or immediately adjacent to the service equipment (230.67, Section 7.1).