5.5 Overcurrent Device Location, Fuses, Circuit Breakers & Transformer Secondary Conductors (Article 240)

Washington Journeyman Electrician 01 General Journey Level

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Structure & Open-Book Code Navigation

1.1 Washington 01 Electrician Licensing Pathway & Exam Structure 1.2 National Electrical Code Architecture & Fast Lookup Strategies 1.3 Open-Book Exam Rules, Reference Preparation & Pacing

2 Chapter 2: Electrical Theory & Fundamental Math

2.1 Ohm's Law, Joule's Law & Circuit Analysis 2.2 AC Fundamentals, Reactance & Power Factor 2.3 Three-Phase Power Calculations: Wye & Delta Configurations

3 Chapter 3: General Installation Requirements & Conductor Sizing

3.1 Installation Requirements & Working Space Clearances 3.2 Conductor Sizing & Table 310.16 Ampacity 3.3 Temperature Correction Factors & Raceway Derating

4 Chapter 4: Wiring Methods, Raceways & Enclosure Calculations

4.1 Common Wiring Methods & Cable Assemblies 4.2 Conduit & Tubing Installation and Fill Calculations 4.3 Box Fill & Pull Box Sizing Calculations 4.4 Flexible Raceways, ENT, Wireways, Cable Trays, Specialty Cables & Plenum Rules

5 Chapter 5: Branch Circuits, Feeders & Overcurrent Protection

5.1 Branch Circuit Ratings, Receptacle Placement & Lighting 5.2 GFCI, AFCI & Special Protection Requirements 5.3 Overcurrent Protection & Feeder Tap Rules 5.4 Grounded Conductors, Feeders, Outside Circuits & Surge Protection (Articles 200, 215, 225, 280, 285) 5.5 Overcurrent Device Location, Fuses, Circuit Breakers & Transformer Secondary Conductors (Article 240)

6 Chapter 6: Grounding & Bonding (Article 250)

6.1 Grounding vs. Bonding: Core Principles & Definitions 6.2 Grounding Electrode Systems & GEC Sizing 6.3 Main Bonding Jumpers & Equipment Grounding Conductor Sizing

7 Chapter 7: Services, Feeders & Load Calculations

7.1 Electrical Services & Service Equipment (Article 230) 7.2 Dwelling Unit Load Calculations: Standard & Optional Methods 7.3 Commercial Load Calculations & Voltage Drop

8 Chapter 8: Equipment for General Use & Equipment Over 1000 Volts (Articles 400-490)

8.1 Flexible Cords, Fixture Wires, Switches, Receptacles & Panelboards (Articles 400-408) 8.2 Luminaires, Appliances, Space Heating & Other Equipment (Articles 410-427, 455-480) 8.3 Equipment Over 1000 Volts (Article 490 and Related Rules)

9 Chapter 9: Motors, HVAC Equipment, Generators & Transformers (Articles 430-450)

9.1 Motor Branch Circuit Conductor Sizing & Overloads 9.2 Motor Short-Circuit Protection & Disconnecting Means 9.3 Transformers, Generators & Hermetic HVAC Equipment

10 Chapter 10: Hazardous Locations & Special Occupancies (Articles 500-590)

10.1 Hazardous (Classified) Locations (Articles 500–516) 10.2 Health Care Facilities, Places of Assembly & Theaters (Articles 517-540) 10.3 Agricultural Buildings, Mobile Homes, RV Parks, Marinas & Temporary Installations (Articles 545-590)

11 Chapter 11: Special Equipment (Articles 600-695)

11.1 Signs, Cranes, Elevators, EV Charging, Welders, IT Rooms & Industrial Machinery (Articles 600-670) 11.2 Swimming Pools, Spas, Hot Tubs & Fountains (Article 680) 11.3 Solar Photovoltaic Systems, Fuel Cells, Wind & Fire Pumps (Articles 690-695)

12 Chapter 12: Emergency Systems, Special Conditions & Communications (Articles 700-830)

12.1 Emergency, Legally Required & Optional Standby Systems (Articles 700-702) 12.2 Interconnected Power Sources, Energy Storage, Power-Limited Circuits, Fire Alarm & Communications (Articles 705-830)

13 Chapter 13: Washington Electrical Laws & Administrative Code (RCW 19.28 & WAC 296-46B)

13.1 Certificates of Competency, Specialty Scopes & Renewal 13.2 Trainees, Supervision Ratios, Apprenticeship & Qualifying Experience 13.3 Electrical Contractors, Administrators, Bonds & Exemptions 13.4 Permits, Inspections, Class A & Class B Work, and Plan Review 13.5 Civil Penalties, Appeals, Exam Rules & Certificate Discipline 13.6 WAC 296-46B Amendments: Adoption, General Rules, Services, Grounding & Wiring (NEC Chapters 1-4) 13.7 WAC 296-46B Amendments: Special Occupancies, Special Equipment, Emergency Systems & Communications (NEC Chapters 5-8)

5.5 Overcurrent Device Location, Fuses, Circuit Breakers & Transformer Secondary Conductors (Article 240)

Key Takeaways Explain This Topic AI

Overcurrent devices must be readily accessible, with the center of the operating handle grip no more than 6 ft 7 in. above the floor or working platform in its highest position (NEC 240.24(A)).

Overcurrent devices may not be located near easily ignitible material such as clothes closets, in dwelling unit bathrooms, or over the steps of a stairway (NEC 240.24(D)-(F)).

A slash-rated breaker such as 120/240 V may be used only on a solidly grounded system where the voltage to ground does not exceed the lower value and the voltage between conductors does not exceed the higher value (NEC 240.85).

Circuit breakers rated or adjustable to 1200 amperes or more need a documented arc energy reduction method (NEC 240.87); Washington requires test reports at inspection.

Transformer secondary conductors up to 10 ft long need an ampacity of at least the computed load and at least the rating of the device they terminate in (NEC 240.21(C)(2)).

Last updated: September 2026

Where overcurrent devices may go (240.24)

Rule 2020 NEC

Readily accessible , installed so the center of the operating handle grip in its highest position is no more than 2.0 m (6 ft 7 in.) above the floor or working platform (exceptions include busway plug-ins, supplementary devices, and devices next to the equipment they serve) 240.24(A)

Each occupant must have ready access to the overcurrent devices serving that occupancy, except where building management supervises the service 240.24(B)

  • Not exposed to physical damage 240.24(C)
  • Not in the vicinity of easily ignitible material, such as clothes closets 240.24(D)

Not in bathrooms of dwelling units, dormitory units, or guest rooms and suites of hotels and motels (supplementary devices excepted) 240.24(E)

Not over the steps of a stairway 240.24(F)

Washington amendments tighten these rules:

Panelboards may not be installed in clothes closets, toilet rooms, or shower rooms (WAC 296-46B-408).

Outdoor enclosures containing overcurrent devices must be at least 24 inches above grade unless pad-mounted or over paving (WAC 296-46B-240).

A panelboard being repaired or replaced in an existing location over steps may stay there (WAC 296-46B-240).

Adjustable-trip devices (240.6(B), (C))

If the long-time pickup setting has an external adjusting means, the device's ampere rating is the maximum setting possible .

If the setting is behind restricted access (a removable and sealable cover, a bolted equipment door, a locked door accessible only to qualified persons, or password protection), the rating may be the adjusted setting .

This matters because conductor protection (240.4) and equipment grounding conductor sizing (Table 250.122) are based on the device's rating.

Plug fuses (240.50-240.54)

Plug fuses may be used only where the voltage between conductors does not exceed 125 V , or on systems with a grounded neutral where the voltage to ground does not exceed 150 V (240.50(A)).

Edison-base fuses may be used only as replacements in existing installations where there is no evidence of overfusing or tampering (240.51(B)).

Type S fuses and adapters are classified at not over 125 V and 0 to 15 A, 16 to 20 A, and 21 to 30 A . Adapters are designed so they can't be removed once installed, which prevents overfusing (240.53, 240.54).

Cartridge fuses (240.60, 240.61)

300-volt-type cartridge fuses may be used on single-phase line-to-neutral circuits supplied from a solidly grounded system where the line-to-neutral voltage does not exceed 300 V.

Fuseholders must reject fuses of a lower voltage rating or higher ampere rating than the fuseholder's class (noninterchangeable).

Markings (240.60(C)): ampere rating, voltage rating, interrupting rating where other than 10,000 A , "current limiting" where applicable, and the manufacturer's name or trademark.

Circuit breakers (240.80-240.87)

  • Topic Rule
  • Trip-free Breakers trip free of the operating handle and cannot be held closed against a fault (240.80)

Indicating Must clearly show open (off) and closed (on). When the handle operates vertically, up is on (240.81)

Interrupting rating marking Required where the rating is other than 5,000 A (240.83(C))

Used as switches Breakers used to switch 120 V and 277 V fluorescent lighting must be listed and marked SWD or HID ; high-intensity discharge lighting needs HID (240.83(D))

Straight vs. slash voltage ratings A straight-rated breaker (for example 240 V or 480 V) may be used where the voltage between any two conductors does not exceed its rating. A slash-rated breaker (120/240 V or 480Y/277 V) is limited to solidly grounded systems where the voltage to ground does not exceed the lower number and the voltage between conductors does not exceed the higher number (240.85). A 480Y/277 V breaker may not be used on a 480 V corner-grounded or ungrounded delta system.

Series ratings A downstream breaker may be applied above its own interrupting rating only as part of a tested, listed series combination . The end-use equipment must be field-marked "CAUTION - SERIES COMBINATION SYSTEM RATED ___ AMPERES" (240.86)

Arc energy reduction Breakers rated or adjustable to 1200 A or more must have a documented method to reduce clearing time. Options include zone-selective interlocking, differential relaying, an energy-reducing maintenance switch with a local status indicator, an active arc-flash mitigation system, an instantaneous trip or override set below the available arcing current, or an approved equivalent. The 2020 NEC also requires performance testing when the system is installed (240.87)

240.67 imposes similar arc-energy documentation for fuses rated 1200 A or more . Washington requires the arcing-current calculations and signed performance test reports for these fuses and breakers to be available to the inspector before the equipment is energized (WAC 296-46B-240).

Transformer secondary conductors (240.21(C))

240.4(F): transformer secondary conductors are not considered protected by the primary overcurrent device. The exceptions are single-phase transformers with a two-wire (single-voltage) secondary and three-phase delta-delta transformers with three-wire secondaries, when the primary protection complies with 450.3 and does not exceed the secondary conductor ampacity multiplied by the secondary-to-primary voltage ratio.

Otherwise, secondary conductors must meet one of these rules:

Rule Length Main conditions

240.21(C)(2) 10 ft or less Ampacity at least the computed load and at least the rating of the equipment or overcurrent device at the termination. The conductors may not extend beyond the equipment they supply and are enclosed in a raceway. For field installations where the conductors leave the enclosure or vault, the primary device rating times the primary-to-secondary voltage ratio, divided by 10, may not exceed the conductor ampacity.

240.21(C)(3) 25 ft or less Industrial installations only, with qualified maintenance and supervision. Ampacity at least the transformer's secondary current rating, the sum of the downstream overcurrent device ratings not over the conductor ampacity, all devices grouped, and conductors protected in a raceway or other approved means.

240.21(C)(4) Unlimited Outside secondary conductors, protected from damage, terminating in a single breaker or set of fuses at the building disconnect

240.21(C)(5) 25 ft total, primary plus secondary Secondary conductors from a feeder-tapped transformer (240.21(B)(3))

240.21(C)(6) 25 ft or less Secondary ampacity at least one-third of (primary OCPD rating times the primary-to-secondary voltage ratio); terminate in a single breaker or set of fuses sized to the conductor ampacity; protected from physical damage

Worked example: 240.21(C)(6)

A 480 V to 208Y/120 V transformer has a 100 A primary breaker. The voltage ratio is 480 / 208 = 2.31.

  • 100 A x 2.31 = 231 A of secondary-equivalent protection
  • 231 / 3 = 77 A minimum secondary conductor ampacity for a run of 25 ft or less

The run must end in a single breaker or set of fuses no larger than the conductors' ampacity (240.4 allows the next standard size where applicable).