Study guide

5.3 Overcurrent Protection & Feeder Tap Rules

Washington Journeyman Electrician 01 General Journey Level

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Structure & Open-Book Code Navigation

1.1 Washington 01 Electrician Licensing Pathway & Exam Structure 1.2 National Electrical Code Architecture & Fast Lookup Strategies 1.3 Open-Book Exam Rules, Reference Preparation & Pacing

2 Chapter 2: Electrical Theory & Fundamental Math

2.1 Ohm's Law, Joule's Law & Circuit Analysis 2.2 AC Fundamentals, Reactance & Power Factor 2.3 Three-Phase Power Calculations: Wye & Delta Configurations

3 Chapter 3: General Installation Requirements & Conductor Sizing

3.1 Installation Requirements & Working Space Clearances 3.2 Conductor Sizing & Table 310.16 Ampacity 3.3 Temperature Correction Factors & Raceway Derating

4 Chapter 4: Wiring Methods, Raceways & Enclosure Calculations

4.1 Common Wiring Methods & Cable Assemblies 4.2 Conduit & Tubing Installation and Fill Calculations 4.3 Box Fill & Pull Box Sizing Calculations 4.4 Flexible Raceways, ENT, Wireways, Cable Trays, Specialty Cables & Plenum Rules

5 Chapter 5: Branch Circuits, Feeders & Overcurrent Protection

5.1 Branch Circuit Ratings, Receptacle Placement & Lighting 5.2 GFCI, AFCI & Special Protection Requirements 5.3 Overcurrent Protection & Feeder Tap Rules 5.4 Grounded Conductors, Feeders, Outside Circuits & Surge Protection (Articles 200, 215, 225, 280, 285) 5.5 Overcurrent Device Location, Fuses, Circuit Breakers & Transformer Secondary Conductors (Article 240)

6 Chapter 6: Grounding & Bonding (Article 250)

6.1 Grounding vs. Bonding: Core Principles & Definitions 6.2 Grounding Electrode Systems & GEC Sizing 6.3 Main Bonding Jumpers & Equipment Grounding Conductor Sizing

7 Chapter 7: Services, Feeders & Load Calculations

7.1 Electrical Services & Service Equipment (Article 230) 7.2 Dwelling Unit Load Calculations: Standard & Optional Methods 7.3 Commercial Load Calculations & Voltage Drop

8 Chapter 8: Equipment for General Use & Equipment Over 1000 Volts (Articles 400-490)

8.1 Flexible Cords, Fixture Wires, Switches, Receptacles & Panelboards (Articles 400-408) 8.2 Luminaires, Appliances, Space Heating & Other Equipment (Articles 410-427, 455-480) 8.3 Equipment Over 1000 Volts (Article 490 and Related Rules)

9 Chapter 9: Motors, HVAC Equipment, Generators & Transformers (Articles 430-450)

9.1 Motor Branch Circuit Conductor Sizing & Overloads 9.2 Motor Short-Circuit Protection & Disconnecting Means 9.3 Transformers, Generators & Hermetic HVAC Equipment

10 Chapter 10: Hazardous Locations & Special Occupancies (Articles 500-590)

10.1 Hazardous (Classified) Locations (Articles 500–516) 10.2 Health Care Facilities, Places of Assembly & Theaters (Articles 517-540) 10.3 Agricultural Buildings, Mobile Homes, RV Parks, Marinas & Temporary Installations (Articles 545-590)

11 Chapter 11: Special Equipment (Articles 600-695)

11.1 Signs, Cranes, Elevators, EV Charging, Welders, IT Rooms & Industrial Machinery (Articles 600-670) 11.2 Swimming Pools, Spas, Hot Tubs & Fountains (Article 680) 11.3 Solar Photovoltaic Systems, Fuel Cells, Wind & Fire Pumps (Articles 690-695)

12 Chapter 12: Emergency Systems, Special Conditions & Communications (Articles 700-830)

12.1 Emergency, Legally Required & Optional Standby Systems (Articles 700-702) 12.2 Interconnected Power Sources, Energy Storage, Power-Limited Circuits, Fire Alarm & Communications (Articles 705-830)

13 Chapter 13: Washington Electrical Laws & Administrative Code (RCW 19.28 & WAC 296-46B)

13.1 Certificates of Competency, Specialty Scopes & Renewal 13.2 Trainees, Supervision Ratios, Apprenticeship & Qualifying Experience 13.3 Electrical Contractors, Administrators, Bonds & Exemptions 13.4 Permits, Inspections, Class A & Class B Work, and Plan Review 13.5 Civil Penalties, Appeals, Exam Rules & Certificate Discipline 13.6 WAC 296-46B Amendments: Adoption, General Rules, Services, Grounding & Wiring (NEC Chapters 1-4) 13.7 WAC 296-46B Amendments: Special Occupancies, Special Equipment, Emergency Systems & Communications (NEC Chapters 5-8)

5.3 Overcurrent Protection & Feeder Tap Rules

Key Takeaways Explain This Topic AI

Standard ampere ratings for fuses and fixed-trip circuit breakers range from 15A to 6000A, with key lower ratings including 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, and 125 amperes (NEC Table 240.6(A)).

The Next Standard Device Size Up rule allows rounding up to the next standard OCPD size for conductors rated 800A or less, provided the circuit does not supply multioutlet cord-and-plug loads (NEC 240.4(B)).

Small conductor rules restrict overcurrent protection to 15A for 14 AWG copper, 20A for 12 AWG copper, and 30A for 10 AWG copper, regardless of higher 75°C or 90°C conductor ampacity tables (NEC 240.4(D)).

Under the 10-Foot Feeder Tap Rule, tap conductors must have an ampacity of at least 1/10 the rating of the feeder OCPD, meet the computed load, and be enclosed in a raceway (NEC 240.21(B)(1)).

Under the 25-Foot Feeder Tap Rule, tap conductors must have an ampacity of at least 1/3 the rating of the feeder OCPD, be protected from physical damage, and terminate in a single OCPD (NEC 240.21(B)(2)).

Last updated: September 2026

Overcurrent Protection & Feeder Tap Rules

Key Concept: Overcurrent protection is the primary safeguard preventing electrical conductors and equipment from overheating, catching fire, or sustaining catastrophic destruction under fault conditions. NEC Article 240 governs overcurrent protective devices (OCPDs), conductor protection thresholds, small conductor exceptions, and the critical feeder tap rules that allow branch and distribution circuits to tap larger feeder supplies without immediate overcurrent devices.

1. Overcurrent Fundamentals & Fault Categories (NEC Article 100 & 240)

An overcurrent is defined as any current in excess of the rated current of equipment or the ampacity of a conductor. It results from three distinct electrical phenomena: OVERCURRENT CATEGORIES

  • 1. OVERLOAD 2. SHORT CIRCUIT 3. GROUND FAULT
  • (Non-Fault Condition) (Fault: Line-to-Line) (Fault: Line-to-Ground)
  • ───────────────────── ───────────────────── ───────────────────────
  • Normal current path. Abnormal low-resistance path. Abnormal connection to
  • Equipment loaded beyond Massive instantaneous current equipment grounding
  • rating (e.g., motor stall). (hundreds or thousands of A). conductor, metal enclosure,

Thermal build-up over time. Magnetic trip / fast blow. or earth.

Inverse-Time Operation of Circuit Breakers

Standard thermal-magnetic circuit breakers operate on an inverse-time characteristic : as the magnitude of current increases, the time required for the device to open decreases:

Thermal Element (Bimetallic Strip): Responds to prolonged low-level overloads. The strip flexes as it heats up, unlatching the operating mechanism. A 200% overload may take 20 to 60 seconds to trip, allowing harmless motor starting inrush currents.

Magnetic Element (Solenoid / Electromagnet): Responds instantaneously to high-magnitude short circuits and ground faults. When fault current spikes above 5 to 10 times the breaker rating, the magnetic coil instantly pulls the trip lever, opening the contacts in less than 1 cycle (16 milliseconds) .

2. Standard Ampere Ratings (NEC Table 240.6(A))

Journeyman electricians must memorize the standard ampere ratings for fuses and fixed-trip inverse-time circuit breakers specified in Table 240.6(A) :

  • Standard Ampere Ratings (Amperes)
  • 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100
  • 110, 125, 150, 175, 200, 225, 250, 300, 350, 400
  • 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000
  • 2500, 3000, 4000, 5000, 6000

Additional Standard Fuse Ratings: Table 240.6(A) also recognizes 1, 3, 6, 10, and 601 amperes as standard fuse ratings.

Exam Trap: Values such as 22A, 65A, 120A, 185A, and 275A are non-standard ratings . When sizing overcurrent devices for conductor protection, you must determine whether the code permits rounding up to the next standard rating or mandates rounding down.

3. The Next Standard Device Size Up Rule (NEC 240.4(B))

Under the general rule of NEC 240.4, conductors must be protected against overcurrent in accordance with their allowable ampacities specified in Table 310.16. However, conductor ampacity calculations frequently produce numbers that do not match standard OCPD sizes.

The Three Mandatory Conditions (NEC 240.4(B))

An electrician is permitted to use the next higher standard overcurrent device rating (above the allowable ampacity of the conductors being protected) if and only if all three of the following conditions are satisfied:

Not a Multioutlet Portable Branch Circuit: The conductors being protected are not part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads.

Non-Standard Conductor Ampacity: The allowable ampacity of the conductors does not correspond to a standard ampere rating listed in Table 240.6(A).

800-Ampere Ceiling: The next higher standard rating selected does not exceed 800 amperes .

Comprehensive Worked Example: Feeder Sizing Under 240.4(B)

Problem: A feeder supplies a subpanel with a calculated continuous load of 140A. The electrician installs 3/0 AWG THWN (75°C) copper conductors in conduit through an ambient temperature of 104°F (40°C).

Step 1: From NEC Table 310.16, 3/0 AWG copper has a base 75°C ampacity of 200 amperes (matching the 75°C equipment terminal rating).

Step 2: Apply the ambient temperature correction factor from Table 310.15(B)(1) for 104°F in the 75°C column: Factor = 0.88.

Step 3: Corrected ampacity: 200 A × 0.88 = 176 amperes 200\text{ A} \times 0.88 = 176\text{ amperes} 200 A × 0.88 = 176 amperes .

Step 4: Look up standard OCPD ratings in Table 240.6(A): standard sizes around 176A are 150A, 175A, and 200A .

Step 5: 176A is not a standard rating. Since this is a feeder (not a multioutlet branch circuit) and is under 800A, the electrician may apply NEC 240.4(B) and select the next standard size up: 200 amperes . (The breaker must also be at least 125% of the 140 A continuous load = 175 A, which 200 A satisfies.)

The Over 800-Ampere Restriction (NEC 240.4(C))

Where the conductor ampacity exceeds 800 amperes, the next higher standard rating rule is strictly prohibited . The overcurrent protective device rating must not exceed the allowable ampacity of the conductor :

Example: Four parallel runs of 500 kcmil copper in separate raceways. Table 310.16 at 75°C gives 380A per conductor. Total ampacity: 4 × 380 A = 1 , 520 amperes 4 \times 380\text{ A} = 1,520\text{ amperes} 4 × 380 A = 1 , 520 amperes .

Standard OCPD ratings in Table 240.6(A) are 1200A, 1600A, and 2000A .

Because 1,520A exceeds 800A, you cannot round up to 1600A. The maximum allowable standard OCPD is 1200 amperes , or the contractor must increase conductor sizes to at least 1600A total ampacity.

4. Small Conductor Ampacity Rules (NEC 240.4(D))

NEC 240.4(D) is one of the most frequently tested provisions on electrical journey-level exams. It establishes absolute maximum overcurrent protective device ratings for small copper and aluminum conductors, overriding the higher ampacities found in Table 310.16.

Conductor Size & Material Table 310.16 (60°C Ampacity) Table 310.16 (75°C Ampacity) Table 310.16 (90°C Ampacity) Absolute Maximum OCPD Rating (NEC 240.4(D))

  • 14 AWG Copper 15 A 20 A 25 A 15 Amperes
  • 12 AWG Copper 20 A 25 A 30 A 20 Amperes
  • 10 AWG Copper 30 A 35 A 40 A 30 Amperes
  • 12 AWG Aluminum 15 A 20 A 25 A 15 Amperes
  • 10 AWG Aluminum 25 A 30 A 35 A 25 Amperes
  • The 90°C Ampacity Derating Trap

Critical Distinction: Although Table 310.16 lists the 90°C ampacity of #12 AWG THHN copper as 30 amperes , an electrician cannot place #12 AWG copper on a 30A circuit breaker for general branch circuits. However, the electrician is permitted to use the full 30A value as the starting point for derating calculations :

Example: Four #12 AWG THHN copper current-carrying conductors in one conduit at 86°F.

Adjustment factor for 4 conductors (Table 310.15(C)(1)) = 0.80 (80%).

Calculation: 30 A × 0.80 = 24 amperes 30\text{ A} \times 0.80 = 24\text{ amperes} 30 A × 0.80 = 24 amperes .

Because the derated ampacity of 24A still equals or exceeds 20A, the circuit can be protected by a standard 20A circuit breaker without any code violation.

Specific Equipment Exceptions (NEC 240.4(G))

The small conductor limitations in 240.4(D) do not apply to specialized equipment listed in Table 240.4(G), most notably:

Electric Motors (Article 430): A motor with a table full-load current of 8.0 A may be supplied by #14 AWG copper (8 A x 1.25 = 10 A). Under Table 430.52, an inverse-time breaker may be sized at 250% (8 x 2.5 = 20 A), which is larger than the 15 A limit of 240.4(D) for #14 copper. That is allowed because 240.4(G) sends motor circuits to Article 430.

Air Conditioning & Refrigeration Equipment (Article 440): OCPD sizing is dictated by the equipment nameplate maximum overcurrent protection rating (MOPR), which frequently pairs #12 AWG wire with a 30A or 35A breaker.

5. Location of Overcurrent Protection & Feeder Tap Rules (NEC 240.21)

Under NEC 240.21 , the general rule dictates that an overcurrent protective device must be installed at the point where the conductor receives its supply .

A tap conductor is defined under 240.2 as a conductor, other than a service conductor, that has overcurrent protection ahead of its point of supply that exceeds the value permitted for similar conductors protected under 240.4. Feeder tap rules permit smaller conductors to tap into a large feeder without an overcurrent device at the tap point, provided strict physical and ampacity conditions are met. THE FEEDER TAP RULES

  • Feeder Protected by 400A OCPD
  • ==============================+==============================
  • |
  • 10-Foot Tap (240.21(B)(1)) | 25-Foot Tap (240.21(B)(2))
  • Max Length: 10'-0" | - Max Length: 25'-0"
  • Min Ampacity: 1/10th | - Min Ampacity: 1/3rd
  • of Feeder (>= 40A) | of Feeder (>= 133.3A)
  • Enclosed in Raceway | - Physical Protection
  • Terminates in OCPD/Panel | - Terminates in Single OCPD
  • ▼
  • [ Subpanel / OCPD ]
  • 6. The 10-Foot Feeder Tap Rule (NEC 240.21(B)(1))

Tap conductors are permitted to be up to 10 feet (3 meters) in length without an overcurrent device at the point of supply if they satisfy all of the following five conditions:

Length Limitation: The total length of the tap conductor does not exceed 10 feet (3.0 m) .

Computed Load: The ampacity of the tap conductors is not less than the computed load on the circuits supplied.

Device Termination: The ampacity of the tap conductors is not less than the rating of the device supplied or the rating of the overcurrent protective device at the termination of the tap conductors.

The 10% Ampacity Rule: For field installations where the tap conductors leave the enclosure or vault in which the tap is made, the ampacity of the tap conductors is not less than one-tenth (1/10 or 10%) of the rating of the overcurrent protective device protecting the feeder conductors: Min Tap Ampacity (10-ft) ≥ Feeder OCPD Rating 10 \text{Min Tap Ampacity (10-ft)} \ge \frac{\text{Feeder OCPD Rating}}{10} Min Tap Ampacity (10-ft) ≥ 10 Feeder OCPD Rating ​

Raceway Enclosure: The tap conductors do not extend beyond the switchboard, switchgear, panelboard, disconnecting means, or control devices they supply, and are enclosed in an approved raceway from the point of the tap to the enclosure.

10-Foot Tap Worked Example

Problem: An 800A feeder supplies a distribution board. A contractor needs to tap this feeder with a 6-foot run of copper conductors to feed an enclosed 100A circuit breaker serving an auxiliary pump with a computed load of 84A. What is the minimum conductor ampacity and size required?

Check 1 (Length): 6 feet ≤ 10 \le 10 ≤ 10 feet. (Complies)

Check 2 (Load): Ampacity must be ≥ 84 A \ge 84\text{ A} ≥ 84 A .

Check 3 (Termination): Ampacity must be ≥ 100 A \ge 100\text{ A} ≥ 100 A (the OCPD rating at termination).

Check 4 (10% Rule): Min Ampacity = 800 A 10 = 80 amperes \text{Min Ampacity} = \frac{800\text{ A}}{10} = 80\text{ amperes} Min Ampacity = 10 800 A ​ = 80 amperes .

Controlling Factor: The largest of the three ampacity minimums governs: max ⁡ ( 84 A , 100 A , 80 A ) = 100 amperes \max(84\text{ A}, 100\text{ A}, 80\text{ A}) = 100\text{ amperes} max ( 84 A , 100 A , 80 A ) = 100 amperes .

Conductor Selection: From Table 310.16 at 75°C, #3 AWG copper (100A) or #1 AWG aluminum (100A) is required.

7. The 25-Foot Feeder Tap Rule (NEC 240.21(B)(2))

Where equipment must be located farther from the feeder tap point, the 25-foot tap rule permits runs up to 25 feet (7.5 meters) without an upstream OCPD if all four conditions are met:

Length Limitation: The total length of the tap conductor does not exceed 25 feet (7.5 m) .

The 1/3 Ampacity Rule: The ampacity of the tap conductors is not less than one-third (1/3 or 33.33%) of the rating of the overcurrent protective device protecting the feeder conductors: Min Tap Ampacity (25-ft) ≥ Feeder OCPD Rating 3 \text{Min Tap Ampacity (25-ft)} \ge \frac{\text{Feeder OCPD Rating}}{3} Min Tap Ampacity (25-ft) ≥ 3 Feeder OCPD Rating ​

Physical Protection: The tap conductors are protected from physical damage by being enclosed in an approved raceway or by other approved means (such as armored cable armor).

Single OCPD Termination: The tap conductors must terminate in a single circuit breaker or single set of fuses that limits the load to the tap conductor's allowable ampacity (or standard rating in accordance with 240.4).

25-Foot Tap Worked Example

Problem: A feeder protected by a 400A circuit breaker runs overhead in an industrial plant. A tap run of 18 feet in EMT drops down to feed a disconnect switch. What is the minimum allowable conductor ampacity and copper conductor size for the tap?

Check 1 (Length): 18 feet ≤ 25 \le 25 ≤ 25 feet. (Complies)

Check 2 (1/3 Rule): Min Ampacity = 400 A 3 = 133.33 amperes \text{Min Ampacity} = \frac{400\text{ A}}{3} = 133.33\text{ amperes} Min Ampacity = 3 400 A ​ = 133.33 amperes .

Conductor Selection: Look up Table 310.16 at 75°C:

#1 AWG copper is rated at 130A (insufficient, below 133.33A).

1/0 AWG copper is rated at 150A (satisfies the requirement).

Termination Requirement: The 1/0 AWG tap conductors must terminate in a single circuit breaker or set of fuses rated at not more than 150 amperes .

8. Outside Feeder Taps of Unlimited Length (NEC 240.21(B)(5))

Outside feeder tap rules permit conductors to tap a feeder without an overcurrent device at the tap point where the conductors are located entirely outdoors, except at the point of entrance to the building:

Length: The tap conductors may be of unlimited length outdoors.

Physical Protection: Must be suitably protected from physical damage.

Termination: Must terminate at a single circuit breaker or single set of fuses that limits the load to the tap conductor's allowable ampacity.

Disconnect Location: The overcurrent device must be installed in a readily accessible location either outside the building or inside nearest the point of entrance of the conductors.

Summary Comparison: Feeder Tap Rules

  • Parameter 10-Foot Tap Rule (240.21(B)(1)) 25-Foot Tap Rule (240.21(B)(2)) Outside Feeder Tap (240.21(B)(5))
  • Maximum Length 10 feet (3.0 m) 25 feet (7.5 m) Unlimited outdoors

Minimum Conductor Ampacity Greater of computed load, termination OCPD, or 1/10th (10%) of feeder OCPD At least 1/3rd (33.33%) of feeder OCPD rating Must equal or exceed the rating of termination OCPD

Physical Protection Must be enclosed in approved raceway Must be protected from physical damage in raceway/cable Protected from physical damage

Termination Type Switchboard, panelboard, or control enclosure Single circuit breaker or single set of fuses Single circuit breaker or single set of fuses

Primary Application Panelboard tie-ins, transformer primaries, gutters Industrial drops, remote machine disconnects Outdoor subpanel feeds between separate buildings