Study guide
2.2 AC Fundamentals, Reactance & Power Factor
Washington Journeyman Electrician 01 General Journey Level
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Structure & Open-Book Code Navigation
1.1 Washington 01 Electrician Licensing Pathway & Exam Structure 1.2 National Electrical Code Architecture & Fast Lookup Strategies 1.3 Open-Book Exam Rules, Reference Preparation & Pacing
2 Chapter 2: Electrical Theory & Fundamental Math
2.1 Ohm's Law, Joule's Law & Circuit Analysis 2.2 AC Fundamentals, Reactance & Power Factor 2.3 Three-Phase Power Calculations: Wye & Delta Configurations
3 Chapter 3: General Installation Requirements & Conductor Sizing
3.1 Installation Requirements & Working Space Clearances 3.2 Conductor Sizing & Table 310.16 Ampacity 3.3 Temperature Correction Factors & Raceway Derating
4 Chapter 4: Wiring Methods, Raceways & Enclosure Calculations
4.1 Common Wiring Methods & Cable Assemblies 4.2 Conduit & Tubing Installation and Fill Calculations 4.3 Box Fill & Pull Box Sizing Calculations 4.4 Flexible Raceways, ENT, Wireways, Cable Trays, Specialty Cables & Plenum Rules
5 Chapter 5: Branch Circuits, Feeders & Overcurrent Protection
5.1 Branch Circuit Ratings, Receptacle Placement & Lighting 5.2 GFCI, AFCI & Special Protection Requirements 5.3 Overcurrent Protection & Feeder Tap Rules 5.4 Grounded Conductors, Feeders, Outside Circuits & Surge Protection (Articles 200, 215, 225, 280, 285) 5.5 Overcurrent Device Location, Fuses, Circuit Breakers & Transformer Secondary Conductors (Article 240)
6 Chapter 6: Grounding & Bonding (Article 250)
6.1 Grounding vs. Bonding: Core Principles & Definitions 6.2 Grounding Electrode Systems & GEC Sizing 6.3 Main Bonding Jumpers & Equipment Grounding Conductor Sizing
7 Chapter 7: Services, Feeders & Load Calculations
7.1 Electrical Services & Service Equipment (Article 230) 7.2 Dwelling Unit Load Calculations: Standard & Optional Methods 7.3 Commercial Load Calculations & Voltage Drop
8 Chapter 8: Equipment for General Use & Equipment Over 1000 Volts (Articles 400-490)
8.1 Flexible Cords, Fixture Wires, Switches, Receptacles & Panelboards (Articles 400-408) 8.2 Luminaires, Appliances, Space Heating & Other Equipment (Articles 410-427, 455-480) 8.3 Equipment Over 1000 Volts (Article 490 and Related Rules)
9 Chapter 9: Motors, HVAC Equipment, Generators & Transformers (Articles 430-450)
9.1 Motor Branch Circuit Conductor Sizing & Overloads 9.2 Motor Short-Circuit Protection & Disconnecting Means 9.3 Transformers, Generators & Hermetic HVAC Equipment
10 Chapter 10: Hazardous Locations & Special Occupancies (Articles 500-590)
10.1 Hazardous (Classified) Locations (Articles 500–516) 10.2 Health Care Facilities, Places of Assembly & Theaters (Articles 517-540) 10.3 Agricultural Buildings, Mobile Homes, RV Parks, Marinas & Temporary Installations (Articles 545-590)
11 Chapter 11: Special Equipment (Articles 600-695)
11.1 Signs, Cranes, Elevators, EV Charging, Welders, IT Rooms & Industrial Machinery (Articles 600-670) 11.2 Swimming Pools, Spas, Hot Tubs & Fountains (Article 680) 11.3 Solar Photovoltaic Systems, Fuel Cells, Wind & Fire Pumps (Articles 690-695)
12 Chapter 12: Emergency Systems, Special Conditions & Communications (Articles 700-830)
12.1 Emergency, Legally Required & Optional Standby Systems (Articles 700-702) 12.2 Interconnected Power Sources, Energy Storage, Power-Limited Circuits, Fire Alarm & Communications (Articles 705-830)
13 Chapter 13: Washington Electrical Laws & Administrative Code (RCW 19.28 & WAC 296-46B)
13.1 Certificates of Competency, Specialty Scopes & Renewal 13.2 Trainees, Supervision Ratios, Apprenticeship & Qualifying Experience 13.3 Electrical Contractors, Administrators, Bonds & Exemptions 13.4 Permits, Inspections, Class A & Class B Work, and Plan Review 13.5 Civil Penalties, Appeals, Exam Rules & Certificate Discipline 13.6 WAC 296-46B Amendments: Adoption, General Rules, Services, Grounding & Wiring (NEC Chapters 1-4) 13.7 WAC 296-46B Amendments: Special Occupancies, Special Equipment, Emergency Systems & Communications (NEC Chapters 5-8)
2.2 AC Fundamentals, Reactance & Power Factor
Key Takeaways Explain This Topic AI
In alternating current (AC) power systems, nominal voltages represent Root-Mean-Square (RMS) effective heating values, where V_rms = 0.7071 × V_peak and V_peak = 1.4142 × V_rms.
Inductive reactance (X_L = 2πfL) causes current to lag voltage by 90 degrees ('ELI'), while capacitive reactance (X_C = 1 / (2πfC)) causes current to lead voltage by 90 degrees ('ICE').
Total circuit impedance Z accounts for both pure resistance and net reactance in quadrature: Z = √(R² + (X_L - X_C)²).
The AC power triangle geometrically relates True Power in kW (horizontal), Reactive Power in kVAR (vertical), and Apparent Power in kVA (hypotenuse): S = √(P² + Q²).
Power factor equals the ratio of True Power to Apparent Power (PF = kW / kVA = cos θ); low lagging power factor increases system line current without delivering productive mechanical or thermal work.
Last updated: September 2026
AC Fundamentals, Reactance & Power Factor
Key Concept: Unlike direct current, alternating current (AC) voltages and currents continuously change in magnitude and periodically reverse direction. Because inductors and capacitors react to these continuous changes by storing and releasing energy in magnetic and electrostatic fields, AC circuits must be analyzed using vector relationships, reactance, impedance, and the power triangle.
AC Sine Wave Architecture & Waveform Metrics
Commercial alternating current in North America is generated as a smooth sinusoidal wave by rotating synchronous alternators. The conductor loops rotate through stationary magnetic fields, producing an electromotive force proportional to the sine of the angle of rotation: v ( t ) = V peak sin ( 2 π f t ) v(t) = V_{\text{peak}} \sin(2\pi f t) v ( t ) = V peak sin ( 2 π f t )
Key Waveform Properties
Frequency ( f f f ): The number of complete cycles executed per second, measured in Hertz (Hz) . The standard utility frequency throughout the United States is 60 Hz .
Period ( T T T ): The time required to complete one full electrical cycle ( 360 ∘ 360^\circ 36 0 ∘ or 2 π 2\pi 2 π radians): T = 1 f = 1 60 Hz ≈ 0.01667 seconds = 16.67 milliseconds T = \frac{1}{f} = \frac{1}{60\text{ Hz}} \approx 0.01667\text{ seconds} = 16.67\text{ milliseconds} T = f 1 = 60 Hz 1 ≈ 0.01667 seconds = 16.67 milliseconds
Angular Velocity ( ω \omega ω ): The rate of rotation expressed in radians per second: ω = 2 π f = 2 × π × 60 ≈ 377 rad/s \omega = 2\pi f = 2 \times \pi \times 60 \approx 377\text{ rad/s} ω = 2 π f = 2 × π × 60 ≈ 377 rad/s Voltage
- ^
- +Vpk| ***
- | * *
- | * *
- 0 +-----+---------+---------+-----> Time (ms)
- | 0 ms 8.33 ms 16.67 ms
- | * *
- Vpk| * *
- | ***
- The Four Voltage Values in AC Circuits
Electricians must clearly differentiate between the four ways an AC voltage is expressed:
Peak Voltage ( V peak V_{\text{peak}} V peak or V max V_{\text{max}} V max ): The maximum instantaneous voltage reached at the crest of the sine wave ( 90 ∘ 90^\circ 9 0 ∘ and 270 ∘ 270^\circ 27 0 ∘ ).
Peak-to-Peak Voltage ( V p − p V_{p-p} V p − p ): The total vertical voltage span from the positive peak to the negative trough: V p − p = 2 × V peak V_{p-p} = 2 \times V_{\text{peak}} V p − p = 2 × V peak
Effective or RMS Voltage ( V rms V_{\text{rms}} V rms ): Root-Mean-Square voltage is the true practical measure of AC electrical work. One ampere of AC RMS current produces the exact same heating effect in a pure resistor as one ampere of steady DC current. All standard AC voltmeters, panel labels, and NEC ratings refer to RMS values unless explicitly designated otherwise: V rms = V peak 2 ≈ 0.7071 × V peak V_{\text{rms}} = \frac{V_{\text{peak}}}{\sqrt{2}} \approx 0.7071 \times V_{\text{peak}} V rms = 2 V peak ≈ 0.7071 × V peak V peak = 2 × V rms ≈ 1.4142 × V rms V_{\text{peak}} = \sqrt{2} \times V_{\text{rms}} \approx 1.4142 \times V_{\text{rms}} V peak = 2 × V rms ≈ 1.4142 × V rms
Average Voltage ( V avg V_{\text{avg}} V avg ): The mathematical average of all instantaneous values over one half-cycle ( 180 ∘ 180^\circ 18 0 ∘ ): V avg = 2 π × V peak ≈ 0.637 × V peak ≈ 0.900 × V rms V_{\text{avg}} = \frac{2}{\pi} \times V_{\text{peak}} \approx 0.637 \times V_{\text{peak}} \approx 0.900 \times V_{\text{rms}} V avg = π 2 × V peak ≈ 0.637 × V peak ≈ 0.900 × V rms
Nominal System Voltages and Peak Values
Nominal RMS System Voltage Peak Voltage ( V peak = V rms × 1.4142 V_{\text{peak}} = V_{\text{rms}} \times 1.4142 V peak = V rms × 1.4142 ) Peak-to-Peak Voltage ( V p − p = 2 × V peak V_{p-p} = 2 \times V_{\text{peak}} V p − p = 2 × V peak ) Half-Cycle Average ( V avg = V peak × 0.637 V_{\text{avg}} = V_{\text{peak}} \times 0.637 V avg = V peak × 0.637 )
120 V (Branch Circuit) 169.7 V 169.7\text{ V} 169.7 V 339.4 V 339.4\text{ V} 339.4 V 108.1 V 108.1\text{ V} 108.1 V
208 V (3-Phase Wye) 294.2 V 294.2\text{ V} 294.2 V 588.3 V 588.3\text{ V} 588.3 V 187.4 V 187.4\text{ V} 187.4 V
240 V (Single Phase) 339.4 V 339.4\text{ V} 339.4 V 678.8 V 678.8\text{ V} 678.8 V 216.2 V 216.2\text{ V} 216.2 V
277 V (Lighting Circuit) 391.7 V 391.7\text{ V} 391.7 V 783.5 V 783.5\text{ V} 783.5 V 249.5 V 249.5\text{ V} 249.5 V
480 V (Industrial Power) 678.8 V 678.8\text{ V} 678.8 V 1357.6 V 1357.6\text{ V} 1357.6 V 432.4 V 432.4\text{ V} 432.4 V
Exam Application: Conductor insulation ratings (such as 600V THHN/THWN-2) must withstand peak dielectric stresses of the waveform, not just the RMS value.
Pure Elements and Phase Relationships: "ELI the ICE man"
In pure direct current, resistance is the sole factor limiting current. In AC systems, inductors and capacitors continuously interact with alternating waveforms, shifting the phase relationship between current and voltage:
Purely Resistive Circuit: Current and voltage reach their positive peaks, zero crossings, and negative peaks at the exact same instant. The phase angle ( θ \theta θ ) is 0 ∘ 0^\circ 0 ∘ .
Purely Inductive Circuit: An inductor (coil) consists of turns of wire that establish a magnetic field. When alternating current flows, the expanding and collapsing magnetic field induces a Counter-Electromotive Force (CEMF) per Lenz's Law that opposes the change in current. As a result, current is delayed: Current lags voltage by 90 ∘ 90^\circ 9 0 ∘ .
Purely Capacitive Circuit: A capacitor consists of two conductive plates separated by a dielectric insulator. When connected to AC, current flows at its maximum rate when the plates are uncharged and voltage across the plates is zero. As charge builds, voltage rises and current slows to zero. Therefore: Current leads voltage by 90 ∘ 90^\circ 9 0 ∘ .
The Mnemonic: "ELI the ICE man"
E - L - I: In an inductive circuit ( L ), Voltage ( E ) leads Current ( I ).
I - C - E: In a capacitive circuit ( C ), Current ( I ) leads Voltage ( E ). Pure Inductive Circuit (ELI): Pure Capacitive Circuit (ICE):
Voltage leads Current by 90° Current leads Voltage by 90°
- +E (90°) +I (90°)
- ^ ^
- | |
- | |
- 0° -----+-----> +I 0° -----+-----> +E
- Reactance and Impedance Calculations
- Inductive Reactance ( X L X_L X L )
Inductive reactance is the opposition offered to alternating current flow by an inductor due to its magnetic counter-electromotive force. It is measured in Ohms ( Ω \Omega Ω ) : X L = 2 π f L X_L = 2\pi f L X L = 2 π f L
Where:
- f = frequency in Hertz (Hz) f = \text{frequency in Hertz (Hz)} f = frequency in Hertz (Hz)
- L = inductance in Henrys (H) L = \text{inductance in Henrys (H)} L = inductance in Henrys (H)
Observation: Inductive reactance is directly proportional to frequency. If frequency doubles, X L X_L X L doubles. At DC ( f = 0 f = 0 f = 0 ), X L = 0 Ω X_L = 0\ \Omega X L = 0 Ω (an ideal inductor acts as a dead short to steady DC).
Capacitive Reactance ( X C X_C X C )
Capacitive reactance is the opposition offered to alternating current flow by a capacitor due to the electrostatic counter-voltage developed across its dielectric plates. It is measured in Ohms ( Ω \Omega Ω ) : X C = 1 2 π f C X_C = \frac{1}{2\pi f C} X C = 2 π f C 1
Where:
- f = frequency in Hertz (Hz) f = \text{frequency in Hertz (Hz)} f = frequency in Hertz (Hz)
- C = capacitance in Farads (F) C = \text{capacitance in Farads (F)} C = capacitance in Farads (F)
Observation: Capacitive reactance is inversely proportional to frequency. As frequency increases, X C X_C X C decreases. At DC ( f = 0 f = 0 f = 0 ), X C = ∞ X_C = \infty X C = ∞ (a capacitor completely blocks steady DC).
Total Circuit Impedance ( Z Z Z )
Impedance is the total opposition to alternating current flow presented by a circuit containing resistance, inductance, and capacitance. Because resistance and net reactance act at right angles ( 90 ∘ 90^\circ 9 0 ∘ ) in the complex plane, they cannot be added algebraically; they must be combined using vector geometry (Pythagorean theorem): Z = R 2 + ( X L − X C ) 2 Z = \sqrt{R^2 + (X_L - X_C)^2} Z = R 2 + ( X L − X C ) 2
Where net reactance is X = X L − X C X = X_L - X_C X = X L − X C . The phase angle ( θ \theta θ ) between total voltage and total current is: θ = arctan ( X L − X C R ) \theta = \arctan\left(\frac{X_L - X_C}{R}\right) θ = arctan ( R X L − X C )
AC Ohm's Law
Once total impedance ( Z Z Z ) in ohms is determined, Ohm's Law applies directly in AC circuits: E = I × Z I = E Z Z = E I E = I \times Z \qquad I = \frac{E}{Z} \qquad Z = \frac{E}{I} E = I × Z I = Z E Z = I E
Step-by-Step Impedance Worked Example
A series circuit connected across a 120V, 60 Hz AC source consists of a resistor R = 12 Ω R = 12\ \Omega R = 12 Ω , an inductor with X L = 25 Ω X_L = 25\ \Omega X L = 25 Ω , and a capacitor with X C = 9 Ω X_C = 9\ \Omega X C = 9 Ω .
Step 1: Calculate Net Reactance ( X X X ): X = X L − X C = 25 Ω − 9 Ω = 16 Ω (net inductive) X = X_L - X_C = 25\ \Omega - 9\ \Omega = 16\ \Omega\text{ (net inductive)} X = X L − X C = 25 Ω − 9 Ω = 16 Ω (net inductive)
Step 2: Calculate Total Impedance ( Z Z Z ): Z = R 2 + X 2 = 12 2 + 16 2 = 144 + 256 = 400 = 20 Ω Z = \sqrt{R^2 + X^2} = \sqrt{12^2 + 16^2} = \sqrt{144 + 256} = \sqrt{400} = 20\ \Omega Z = R 2 + X 2 = 1 2 2 + 1 6 2 = 144 + 256 = 400 = 20 Ω
Step 3: Calculate Circuit Current ( I I I ): I = E Z = 120 V 20 Ω = 6.0 A I = \frac{E}{Z} = \frac{120\text{ V}}{20\ \Omega} = 6.0\text{ A} I = Z E = 20 Ω 120 V = 6.0 A
Step 4: Calculate Component Voltage Drops:
Resistor drop: V R = I × R = 6.0 A × 12 Ω = 72.0 V V_R = I \times R = 6.0\text{ A} \times 12\ \Omega = 72.0\text{ V} V R = I × R = 6.0 A × 12 Ω = 72.0 V
Inductor drop: V L = I × X L = 6.0 A × 25 Ω = 150.0 V V_L = I \times X_L = 6.0\text{ A} \times 25\ \Omega = 150.0\text{ V} V L = I × X L = 6.0 A × 25 Ω = 150.0 V
Capacitor drop: V C = I × X C = 6.0 A × 9 Ω = 54.0 V V_C = I \times X_C = 6.0\text{ A} \times 9\ \Omega = 54.0\text{ V} V C = I × X C = 6.0 A × 9 Ω = 54.0 V
Verify total voltage via vector addition (KVL for AC): E = V R 2 + ( V L − V C ) 2 = 72 2 + ( 150 − 54 ) 2 = 72 2 + 96 2 = 5184 + 9216 = 14400 = 120 V E = \sqrt{V_R^2 + (V_L - V_C)^2} = \sqrt{72^2 + (150 - 54)^2} = \sqrt{72^2 + 96^2} = \sqrt{5184 + 9216} = \sqrt{14400} = 120\text{ V} E = V R 2 + ( V L − V C ) 2 = 7 2 2 + ( 150 − 54 ) 2 = 7 2 2 + 9 6 2 = 5184 + 9216 = 14400 = 120 V Note: Inductor voltage ( 150 V 150\text{ V} 150 V ) actually exceeds source voltage ( 120 V 120\text{ V} 120 V ). This is normal in reactive series circuits due to resonant energy exchange!
The AC Power Triangle: True, Apparent, and Reactive Power
In reactive AC circuits, voltage and current are displaced by phase angle θ \theta θ . As a result, not all current entering the circuit produces real mechanical or thermal work. We define three distinct types of power that form the Power Triangle : /| Apparent Power (S)
- / | in Volt-Amperes (VA or kVA)
- / | S = E x I
- / |
- / | Reactive Power (Q)
- / | in VAR or kVAR
- / | Q = E x I x sin(θ)
- / θ |
- +--------+
- True Power (P)
- in Watts (W or kW)
- P = E x I x cos(θ)
True Power / Real Power ( P P P ): Measured in Watts (W) or Kilowatts (kW) . True power represents actual useful work performed—turning a motor shaft, heating an oven element, or producing illumination. It is consumed entirely by resistance: P = E × I × cos θ P = E \times I \times \cos\theta P = E × I × cos θ
Reactive Power ( Q Q Q ): Measured in Volt-Amperes Reactive (VAR) or Kilovolt-Amperes Reactive (kVAR) . Reactive power represents the "bouncing" energy stored in magnetic fields (inductors) and electrostatic fields (capacitors) that alternates back and forth between source and load every half-cycle without performing useful work: Q = E × I × sin θ Q = E \times I \times \sin\theta Q = E × I × sin θ
Apparent Power ( S S S ): Measured in Volt-Amperes (VA) or Kilovolt-Amperes (kVA) . Apparent power represents the total capacity that generators, transformers, switchgear, and feeder conductors must deliver to satisfy both the true and reactive power demands: S = E × I S = E \times I S = E × I S = P 2 + Q 2 S = \sqrt{P^2 + Q^2} S = P 2 + Q 2
Power Factor (PF) & Phase Angle Relationships
Power Factor (PF) is the ratio of real working power to the total apparent power delivered by the system: P F = True Power Apparent Power = P S = Watts Volt-Amperes = kW kVA = cos θ PF = \frac{\text{True Power}}{\text{Apparent Power}} = \frac{P}{S} = \frac{\text{Watts}}{\text{Volt-Amperes}} = \frac{\text{kW}}{\text{kVA}} = \cos\theta PF = Apparent Power True Power = S P = Volt-Amperes Watts = kVA kW = cos θ
Power factor is expressed either as a decimal between 0 and 1.0 (e.g., 0.85) or as a percentage (e.g., 85%).
Lagging versus Leading Power Factor
Lagging Power Factor: Occurs when load current lags voltage. This is caused by inductive loads, which dominate commercial and industrial facilities: induction motors, transformers, welding equipment, and magnetic ballasts.
Leading Power Factor: Occurs when load current leads voltage. This is caused by capacitive loads: power factor correction capacitor banks, lightly loaded underground transmission cables, and overexcited synchronous motors.
The Operational Penalty of Low Power Factor
Consider an industrial facility drawing 100 kW 100\text{ kW} 100 kW of true power at 480V single-phase:
At 1.0 (Unity) Power Factor: S = 100 kW 1.0 = 100 kVA ⟹ I = 100 , 000 VA 480 V = 208.3 A S = \frac{100\text{ kW}}{1.0} = 100\text{ kVA} \implies I = \frac{100,000\text{ VA}}{480\text{ V}} = 208.3\text{ A} S = 1.0 100 kW = 100 kVA ⟹ I = 480 V 100 , 000 VA = 208.3 A
At 0.60 Lagging Power Factor: S = 100 kW 0.60 = 166.7 kVA ⟹ I = 166 , 667 VA 480 V = 347.2 A S = \frac{100\text{ kW}}{0.60} = 166.7\text{ kVA} \implies I = \frac{166,667\text{ VA}}{480\text{ V}} = 347.2\text{ A} S = 0.60 100 kW = 166.7 kVA ⟹ I = 480 V 166 , 667 VA = 347.2 A
Notice that at 0.60 PF, the facility performs the exact same 100 kW 100\text{ kW} 100 kW of useful work , but the supply conductors must carry 347.2 A 347.2\text{ A} 347.2 A instead of 208.3 A 208.3\text{ A} 208.3 A —an increase of 138.9 A 138.9\text{ A} 138.9 A (67% more current!).
Severe Consequences of Low Power Factor
Conductor Sizing: Feeders, transformers, and switchboards must be substantially oversized to handle non-working reactive current.
Conductor Thermal Losses: Line heating increases with I 2 R I^2 R I 2 R . Operating at 0.60 PF increases feeder heat losses by ( 347.2 208.3 ) 2 = 2.78 (\frac{347.2}{208.3})^2 = 2.78 ( 208.3 347.2 ) 2 = 2.78 times (a 178% increase in wasted energy!).
Voltage Regulation: Higher line currents cause excessive voltage drop across distribution feeders.
Utility Penalties: Electric utilities install kVAR/kVA demand meters and levy heavy financial surcharges on commercial customers with power factors below 0.90 or 0.95.
Step-by-Step Power Factor Correction Calculation
To correct poor power factor caused by inductive loads, electricians install shunt capacitor banks in parallel with the load. Because capacitive reactive power ( Q C Q_C Q C ) leads by 90 ∘ 90^\circ 9 0 ∘ while inductive reactive power ( Q L Q_L Q L ) lags by 90 ∘ 90^\circ 9 0 ∘ , they directly cancel each other out ( Q net = Q L − Q C Q_{\text{net}} = Q_L - Q_C Q net = Q L − Q C ). Inductive Load
- (P = 120 kW, PF = 0.65)
- +----------------------+
- [ 480 V ] ---+ +--- [ Ground/Neutral ]
- +---[ Capacitor Bank ]-+
- (Supplies kVAR)
- Practical Worked Problem
A 480V, single-phase industrial plant operates at an active load of 120 kW 120\text{ kW} 120 kW with an existing lagging power factor of 0.65 0.65 0.65 . Plant management wants to install a capacitor bank to improve the power factor to 0.95 0.95 0.95 lagging to eliminate utility billing penalties. Determine:
The existing Apparent Power ( S 1 S_1 S 1 ) and line current ( I 1 I_1 I 1 ).
The existing Reactive Power ( Q 1 Q_1 Q 1 ).
The target Apparent Power ( S 2 S_2 S 2 ) and target Reactive Power ( Q 2 Q_2 Q 2 ).
The required capacitor rating in kVAR .
The line current reduction achieved.
Solution Steps
Step 1: Calculate Initial Apparent Power ( S 1 S_1 S 1 ) and Line Current ( I 1 I_1 I 1 ): S 1 = P P F 1 = 120 kW 0.65 ≈ 184.62 kVA S_1 = \frac{P}{PF_1} = \frac{120\text{ kW}}{0.65} \approx 184.62\text{ kVA} S 1 = P F 1 P = 0.65 120 kW ≈ 184.62 kVA I 1 = S 1 V = 184 , 620 VA 480 V ≈ 384.6 A I_1 = \frac{S_1}{V} = \frac{184,620\text{ VA}}{480\text{ V}} \approx 384.6\text{ A} I 1 = V S 1 = 480 V 184 , 620 VA ≈ 384.6 A
Step 2: Calculate Initial Reactive Power ( Q 1 Q_1 Q 1 ):
Initial phase angle: θ 1 = arccos ( 0.65 ) ≈ 49.46 ∘ \theta_1 = \arccos(0.65) \approx 49.46^\circ θ 1 = arccos ( 0.65 ) ≈ 49.4 6 ∘
Using trigonometry: Q 1 = P × tan ( θ 1 ) Q_1 = P \times \tan(\theta_1) Q 1 = P × tan ( θ 1 ) tan ( 49.46 ∘ ) ≈ 1.1691 \tan(49.46^\circ) \approx 1.1691 tan ( 49.4 6 ∘ ) ≈ 1.1691 Q 1 = 120 kW × 1.1691 ≈ 140.29 kVAR Q_1 = 120\text{ kW} \times 1.1691 \approx 140.29\text{ kVAR} Q 1 = 120 kW × 1.1691 ≈ 140.29 kVAR
Step 3: Calculate Target Apparent Power ( S 2 S_2 S 2 ) and Target Reactive Power ( Q 2 Q_2 Q 2 ):
At desired P F 2 = 0.95 PF_2 = 0.95 P F 2 = 0.95 : S 2 = P P F 2 = 120 kW 0.95 ≈ 126.32 kVA S_2 = \frac{P}{PF_2} = \frac{120\text{ kW}}{0.95} \approx 126.32\text{ kVA} S 2 = P F 2 P = 0.95 120 kW ≈ 126.32 kVA
Target phase angle: θ 2 = arccos ( 0.95 ) ≈ 18.19 ∘ \theta_2 = \arccos(0.95) \approx 18.19^\circ θ 2 = arccos ( 0.95 ) ≈ 18.1 9 ∘ tan ( 18.19 ∘ ) ≈ 0.3287 \tan(18.19^\circ) \approx 0.3287 tan ( 18.1 9 ∘ ) ≈ 0.3287 Q 2 = P × tan ( θ 2 ) = 120 kW × 0.3287 ≈ 39.44 kVAR Q_2 = P \times \tan(\theta_2) = 120\text{ kW} \times 0.3287 \approx 39.44\text{ kVAR} Q 2 = P × tan ( θ 2 ) = 120 kW × 0.3287 ≈ 39.44 kVAR
Step 4: Calculate Required Capacitor Rating ( Q C Q_C Q C ): The capacitor must supply the difference between existing and target reactive power: Q C = Q 1 − Q 2 = 140.29 kVAR − 39.44 kVAR = 100.85 kVAR Q_C = Q_1 - Q_2 = 140.29\text{ kVAR} - 39.44\text{ kVAR} = 100.85\text{ kVAR} Q C = Q 1 − Q 2 = 140.29 kVAR − 39.44 kVAR = 100.85 kVAR
Result: Install a standard 100 kVAR 100\text{ kVAR} 100 kVAR shunt capacitor bank.
Step 5: Determine Line Current Reduction:
New line current at 0.95 PF: I 2 = S 2 V = 126 , 320 VA 480 V ≈ 263.2 A I_2 = \frac{S_2}{V} = \frac{126,320\text{ VA}}{480\text{ V}} \approx 263.2\text{ A} I 2 = V S 2 = 480 V 126 , 320 VA ≈ 263.2 A
Current reduction: Δ I = 384.6 A − 263.2 A = 121.4 A \Delta I = 384.6\text{ A} - 263.2\text{ A} = 121.4\text{ A} Δ I = 384.6 A − 263.2 A = 121.4 A
Summary: Adding the capacitor bank slashes feeder current by 121.4 A 121.4\text{ A} 121.4 A (a 31.6% reduction) without altering motor speeds, shaft output, or heating performance.