Study guide
12.2 Interconnected Power Sources, Energy Storage, Power-Limited Circuits, Fire Alarm & Communications (Articles 705-830)
Washington Journeyman Electrician 01 General Journey Level
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Structure & Open-Book Code Navigation
1.1 Washington 01 Electrician Licensing Pathway & Exam Structure 1.2 National Electrical Code Architecture & Fast Lookup Strategies 1.3 Open-Book Exam Rules, Reference Preparation & Pacing
2 Chapter 2: Electrical Theory & Fundamental Math
2.1 Ohm's Law, Joule's Law & Circuit Analysis 2.2 AC Fundamentals, Reactance & Power Factor 2.3 Three-Phase Power Calculations: Wye & Delta Configurations
3 Chapter 3: General Installation Requirements & Conductor Sizing
3.1 Installation Requirements & Working Space Clearances 3.2 Conductor Sizing & Table 310.16 Ampacity 3.3 Temperature Correction Factors & Raceway Derating
4 Chapter 4: Wiring Methods, Raceways & Enclosure Calculations
4.1 Common Wiring Methods & Cable Assemblies 4.2 Conduit & Tubing Installation and Fill Calculations 4.3 Box Fill & Pull Box Sizing Calculations 4.4 Flexible Raceways, ENT, Wireways, Cable Trays, Specialty Cables & Plenum Rules
5 Chapter 5: Branch Circuits, Feeders & Overcurrent Protection
5.1 Branch Circuit Ratings, Receptacle Placement & Lighting 5.2 GFCI, AFCI & Special Protection Requirements 5.3 Overcurrent Protection & Feeder Tap Rules 5.4 Grounded Conductors, Feeders, Outside Circuits & Surge Protection (Articles 200, 215, 225, 280, 285) 5.5 Overcurrent Device Location, Fuses, Circuit Breakers & Transformer Secondary Conductors (Article 240)
6 Chapter 6: Grounding & Bonding (Article 250)
6.1 Grounding vs. Bonding: Core Principles & Definitions 6.2 Grounding Electrode Systems & GEC Sizing 6.3 Main Bonding Jumpers & Equipment Grounding Conductor Sizing
7 Chapter 7: Services, Feeders & Load Calculations
7.1 Electrical Services & Service Equipment (Article 230) 7.2 Dwelling Unit Load Calculations: Standard & Optional Methods 7.3 Commercial Load Calculations & Voltage Drop
8 Chapter 8: Equipment for General Use & Equipment Over 1000 Volts (Articles 400-490)
8.1 Flexible Cords, Fixture Wires, Switches, Receptacles & Panelboards (Articles 400-408) 8.2 Luminaires, Appliances, Space Heating & Other Equipment (Articles 410-427, 455-480) 8.3 Equipment Over 1000 Volts (Article 490 and Related Rules)
9 Chapter 9: Motors, HVAC Equipment, Generators & Transformers (Articles 430-450)
9.1 Motor Branch Circuit Conductor Sizing & Overloads 9.2 Motor Short-Circuit Protection & Disconnecting Means 9.3 Transformers, Generators & Hermetic HVAC Equipment
10 Chapter 10: Hazardous Locations & Special Occupancies (Articles 500-590)
10.1 Hazardous (Classified) Locations (Articles 500–516) 10.2 Health Care Facilities, Places of Assembly & Theaters (Articles 517-540) 10.3 Agricultural Buildings, Mobile Homes, RV Parks, Marinas & Temporary Installations (Articles 545-590)
11 Chapter 11: Special Equipment (Articles 600-695)
11.1 Signs, Cranes, Elevators, EV Charging, Welders, IT Rooms & Industrial Machinery (Articles 600-670) 11.2 Swimming Pools, Spas, Hot Tubs & Fountains (Article 680) 11.3 Solar Photovoltaic Systems, Fuel Cells, Wind & Fire Pumps (Articles 690-695)
12 Chapter 12: Emergency Systems, Special Conditions & Communications (Articles 700-830)
12.1 Emergency, Legally Required & Optional Standby Systems (Articles 700-702) 12.2 Interconnected Power Sources, Energy Storage, Power-Limited Circuits, Fire Alarm & Communications (Articles 705-830)
13 Chapter 13: Washington Electrical Laws & Administrative Code (RCW 19.28 & WAC 296-46B)
13.1 Certificates of Competency, Specialty Scopes & Renewal 13.2 Trainees, Supervision Ratios, Apprenticeship & Qualifying Experience 13.3 Electrical Contractors, Administrators, Bonds & Exemptions 13.4 Permits, Inspections, Class A & Class B Work, and Plan Review 13.5 Civil Penalties, Appeals, Exam Rules & Certificate Discipline 13.6 WAC 296-46B Amendments: Adoption, General Rules, Services, Grounding & Wiring (NEC Chapters 1-4) 13.7 WAC 296-46B Amendments: Special Occupancies, Special Equipment, Emergency Systems & Communications (NEC Chapters 5-8)
12.2 Interconnected Power Sources, Energy Storage, Power-Limited Circuits, Fire Alarm & Communications (Articles 705-830)
Key Takeaways Explain This Topic AI
Under the 120 percent rule, 125 percent of the inverter output current plus the rating of the device protecting the busbar may not exceed 120 percent of the busbar rating, with the backfed breaker at the opposite end from the main supply (NEC 705.12).
Utility-interactive inverters must automatically disconnect when the utility source is lost and stay off until it is restored (NEC 705.40).
Overcurrent protection for Class 1 circuit conductors may not exceed 7 amperes for 18 AWG or 10 amperes for 16 AWG (NEC 725.43).
The branch circuit for fire alarm equipment may supply no other loads, must be marked 'FIRE ALARM CIRCUIT' with red identification, and may not be supplied through a GFCI or AFCI (NEC 760.41(B)).
At one- and two-family dwellings, the communications bonding conductor or grounding electrode conductor should be no longer than 20 feet (NEC 800.100).
Last updated: September 2026
Interconnected electric power production sources (Article 705)
Article 705 covers any power source that runs in parallel with the utility or another primary source: PV, wind, fuel cells, generators, and energy storage.
Rule 2020 NEC
A permanent plaque or directory at the service equipment and at each power source location shows every power source on the premises and where its disconnect is 705.10
Supply-side connections (between the service disconnect and the meter) must meet 705.11, with conductor sizing, overcurrent protection, and a disconnect like service equipment. Washington requires the service wiring methods of WAC 296-46B-230(7) for these conductors (WAC 296-46B-705). 705.11
Load-side connections must meet the busbar and conductor rules of 705.12 705.12
The source disconnect must be manually operable, readily accessible, externally operable, and show whether it is open or closed 705.20
Loss of utility: interactive inverters must automatically de-energize their output when the primary source is lost and may not reconnect until it is restored (anti-islanding) 705.40
Load-side busbar options (705.12(B))
For a panelboard busbar fed by both the utility (through its main breaker) and an inverter (through a backfed breaker), one of these must be true:
100 percent rule: 125 percent of the inverter output current, plus the rating of the device protecting the busbar, does not exceed the busbar ampere rating .
120 percent rule: 125 percent of the inverter output current, plus the rating of the device protecting the busbar, does not exceed 120 percent of the busbar rating. The backfed breaker must be at the opposite end of the busbar from the main supply, and a permanent warning label must read "POWER SOURCE OUTPUT CONNECTION - DO NOT RELOCATE THIS OVERCURRENT DEVICE."
Sum rule: the sum of all overcurrent device ratings on the busbar, excluding the one protecting the busbar, does not exceed the busbar rating.
Worked example (120 percent rule): a 200 A busbar has a 200 A main breaker. The inverter output is 32 A continuous.
Maximum allowed: 200 A x 1.20 = 240 A.
240 A - 200 A main = 40 A available.
The inverter needs 32 A x 1.25 = 40 A, so a 40 A backfed breaker at the opposite end fits exactly.
Energy storage, stand-alone systems, and microgrids (Articles 706, 710, 712)
Energy storage systems (706): must be listed. They need a disconnecting means that is readily accessible and within sight of the system, or lockable with its location marked. They also need working space, ventilation, and marking of the maximum voltage and available fault current.
Stand-alone systems (710) and DC microgrids (712) operate without the utility and follow similar source, disconnect, and labeling rules.
Washington requires a design review on site when these sources are interconnected or stand-alone (WAC 296-46B-705, -710).
Class 1, Class 2, and Class 3 circuits (Article 725, 2020 NEC)
- Class Typical source limits Examples
- Class 1 power-limited 30 V and 1000 VA maximum Motor control circuits fed by a limited transformer
- Class 1 remote-control and signaling Up to 600 V Relay and contactor control circuits
Class 2 Limited by a listed Class 2 power source (see Chapter 9 Tables 11(A) and (B)) so it poses no fire hazard and limited shock hazard Thermostats, doorbells, many LED drivers
Class 3 Listed Class 3 source; higher voltage than Class 2 but still power-limited Some signaling and sound systems
Key rules:
Class 1 overcurrent protection (725.43): based on conductor ampacity. For 18 AWG, no more than 7 A ; for 16 AWG, no more than 10 A .
Class 1 conductors may share a raceway, cable, or enclosure with power supply conductors only when they are functionally associated with the equipment those power conductors supply (725.48(B)(1)).
Class 2 and 3 separation (725.136): Class 2 and Class 3 conductors may not be placed in any cable, cable tray, compartment, enclosure, box, or raceway with electric light, power, Class 1, or non-power-limited fire alarm conductors, unless separated by a barrier or as otherwise permitted.
Support (725.143): Class 2 and 3 cables may not be strapped, taped, or attached to the outside of a conduit or raceway as a means of support. 300.11(C)(2) allows the exception where the raceway carries the power for the equipment the Class 2 circuit controls.
Cable types: CL2P or CL3P (plenum), CL2R or CL3R (riser), CL2 or CL3 (general), and CL2X or CL3X (limited use). A higher-rated cable may substitute for a lower one.
The 2023 NEC reorganized this material into Articles 722, 724, and 725. The 2020 numbering above matches the exam's code edition.
Fire alarm systems (Article 760)
Dedicated branch circuit (760.41(B), 760.121(B)):
The branch circuit supplying fire alarm equipment may supply no other loads .
The location of its overcurrent device must be permanently identified at the fire alarm control unit.
The circuit disconnect must have red identification , be accessible only to qualified personnel, and be marked "FIRE ALARM CIRCUIT."
The branch circuit may not be supplied through a GFCI or AFCI .
Circuit identification (760.30): fire alarm circuits must be identified at terminal and junction locations so they won't be disturbed by accident during testing or servicing.
Cable types: FPLP (plenum), FPLR (riser), and FPL (general) for power-limited fire alarm circuits.
Washington: fire alarm device and junction boxes must be substantially red inside and outside , and power-limited fire alarm conductors must be marked in boxes (WAC 296-46B-760). A red receptacle with a red cover that supplies only a fire alarm system in a garage or unfinished basement needs no GFCI (WAC 296-46B-210).
Optical fiber (Article 770)
Optical fiber cables are nonconductive (OFN types) or conductive (OFC types). Conductive types contain non-current-carrying metal such as a strength member or armor.
Conductive optical fiber cable members must be bonded or grounded where they enter a building.
Nonconductive optical fiber cables may share a raceway or enclosure with power conductors only under the conditions of 770.133.
Communications systems (Chapter 8, Articles 800-840)
In the 2020 NEC, Article 800 was added for the general requirements shared by communications systems. It is followed by 805 (communications circuits), 810 (radio and television equipment), 820 (CATV), 830 (network-powered broadband), and 840 (premises-powered broadband).
Rule 2020 NEC
Independence: under NEC 90.3, Chapter 8 is not subject to Chapters 1-7 unless specifically referenced. Washington reverses this: Chapters 1-7 supplement and modify Chapter 8, and Chapter 8 prevails only where it states a different specific rule (WAC 296-46B-800). 90.3
Bonding conductor or grounding electrode conductor for primary protectors and cable shields: copper or other corrosion-resistant material, insulated, not smaller than 14 AWG , run as straight as practicable, connected to the intersystem bonding termination 800.100
At one- and two-family dwellings , that bonding conductor or grounding electrode conductor may be no longer than 20 ft . If that isn't practicable, install a separate electrode and bond it to the power grounding electrode system with at least 6 AWG copper. 800.100
Intersystem bonding termination: accessible at the service equipment or metering equipment, with capacity for at least three intersystem bonding conductors 250.94
Communications wires must be kept at least 6 ft from lightning protection conductors where practicable 800.53
Communications cables may not share a raceway, box, or enclosure with power conductors unless separated by a barrier or as permitted 805.133
Antennas (810): mast and discharge unit bonding conductor at least 10 AWG copper 810.21
CATV (820): the coaxial cable's outer conductive shield is bonded or grounded as close as practicable to the point of entrance 820.93
Washington telecommunications rules (WAC 296-46B-300, -800, -901):
Telecommunications cables must be supported at intervals of no more than 5 ft .
The demarcation point may be no more than 12 in. inside the end user's occupied space.
A permit is required for projects of more than 10 outlets , all backbone work, and fire-barrier penetrations.