8.3 Equipment Over 1000 Volts (Article 490 and Related Rules)
Washington Journeyman Electrician 01 General Journey Level
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Structure & Open-Book Code Navigation
1.1 Washington 01 Electrician Licensing Pathway & Exam Structure 1.2 National Electrical Code Architecture & Fast Lookup Strategies 1.3 Open-Book Exam Rules, Reference Preparation & Pacing
2 Chapter 2: Electrical Theory & Fundamental Math
2.1 Ohm's Law, Joule's Law & Circuit Analysis 2.2 AC Fundamentals, Reactance & Power Factor 2.3 Three-Phase Power Calculations: Wye & Delta Configurations
3 Chapter 3: General Installation Requirements & Conductor Sizing
3.1 Installation Requirements & Working Space Clearances 3.2 Conductor Sizing & Table 310.16 Ampacity 3.3 Temperature Correction Factors & Raceway Derating
4 Chapter 4: Wiring Methods, Raceways & Enclosure Calculations
4.1 Common Wiring Methods & Cable Assemblies 4.2 Conduit & Tubing Installation and Fill Calculations 4.3 Box Fill & Pull Box Sizing Calculations 4.4 Flexible Raceways, ENT, Wireways, Cable Trays, Specialty Cables & Plenum Rules
5 Chapter 5: Branch Circuits, Feeders & Overcurrent Protection
5.1 Branch Circuit Ratings, Receptacle Placement & Lighting 5.2 GFCI, AFCI & Special Protection Requirements 5.3 Overcurrent Protection & Feeder Tap Rules 5.4 Grounded Conductors, Feeders, Outside Circuits & Surge Protection (Articles 200, 215, 225, 280, 285) 5.5 Overcurrent Device Location, Fuses, Circuit Breakers & Transformer Secondary Conductors (Article 240)
6 Chapter 6: Grounding & Bonding (Article 250)
6.1 Grounding vs. Bonding: Core Principles & Definitions 6.2 Grounding Electrode Systems & GEC Sizing 6.3 Main Bonding Jumpers & Equipment Grounding Conductor Sizing
7 Chapter 7: Services, Feeders & Load Calculations
7.1 Electrical Services & Service Equipment (Article 230) 7.2 Dwelling Unit Load Calculations: Standard & Optional Methods 7.3 Commercial Load Calculations & Voltage Drop
8 Chapter 8: Equipment for General Use & Equipment Over 1000 Volts (Articles 400-490)
8.1 Flexible Cords, Fixture Wires, Switches, Receptacles & Panelboards (Articles 400-408) 8.2 Luminaires, Appliances, Space Heating & Other Equipment (Articles 410-427, 455-480) 8.3 Equipment Over 1000 Volts (Article 490 and Related Rules)
9 Chapter 9: Motors, HVAC Equipment, Generators & Transformers (Articles 430-450)
9.1 Motor Branch Circuit Conductor Sizing & Overloads 9.2 Motor Short-Circuit Protection & Disconnecting Means 9.3 Transformers, Generators & Hermetic HVAC Equipment
10 Chapter 10: Hazardous Locations & Special Occupancies (Articles 500-590)
10.1 Hazardous (Classified) Locations (Articles 500–516) 10.2 Health Care Facilities, Places of Assembly & Theaters (Articles 517-540) 10.3 Agricultural Buildings, Mobile Homes, RV Parks, Marinas & Temporary Installations (Articles 545-590)
11 Chapter 11: Special Equipment (Articles 600-695)
11.1 Signs, Cranes, Elevators, EV Charging, Welders, IT Rooms & Industrial Machinery (Articles 600-670) 11.2 Swimming Pools, Spas, Hot Tubs & Fountains (Article 680) 11.3 Solar Photovoltaic Systems, Fuel Cells, Wind & Fire Pumps (Articles 690-695)
12 Chapter 12: Emergency Systems, Special Conditions & Communications (Articles 700-830)
12.1 Emergency, Legally Required & Optional Standby Systems (Articles 700-702) 12.2 Interconnected Power Sources, Energy Storage, Power-Limited Circuits, Fire Alarm & Communications (Articles 705-830)
13 Chapter 13: Washington Electrical Laws & Administrative Code (RCW 19.28 & WAC 296-46B)
13.1 Certificates of Competency, Specialty Scopes & Renewal 13.2 Trainees, Supervision Ratios, Apprenticeship & Qualifying Experience 13.3 Electrical Contractors, Administrators, Bonds & Exemptions 13.4 Permits, Inspections, Class A & Class B Work, and Plan Review 13.5 Civil Penalties, Appeals, Exam Rules & Certificate Discipline 13.6 WAC 296-46B Amendments: Adoption, General Rules, Services, Grounding & Wiring (NEC Chapters 1-4) 13.7 WAC 296-46B Amendments: Special Occupancies, Special Equipment, Emergency Systems & Communications (NEC Chapters 5-8)
8.3 Equipment Over 1000 Volts (Article 490 and Related Rules)
Key Takeaways Explain This Topic AI
Article 490 covers equipment operating at more than 1000 volts nominal, such as circuit breakers, power fuses, load interrupters, metal-enclosed switchgear, mobile equipment, and electrode-type boilers.
Outdoor high-voltage installations must be enclosed by a fence at least 7 ft high, or 6 ft of fence fabric plus at least 1 ft of three or more strands of barbed wire (NEC 110.31).
At 1001 to 2500 volts to ground, the minimum working space depth is 3 ft for Condition 1, 4 ft for Condition 2, and 5 ft for Condition 3 (NEC Table 110.34(A)).
Isolating switches that are not interlocked with a circuit-interrupting device must carry a sign warning against opening them under load (NEC 490.22).
Washington requires customer-owned cables over 1,000 volts to be permanently marked with phase, operating voltage, and circuit number at each termination and accessible point (WAC 296-46B-110).
Last updated: September 2026
Why this section matters
Most journey level work is at 1000 V or less. The exam still expects you to find the high-voltage rules quickly. They are spread across Article 110 Part III , Article 300 Part II , Article 311 (medium-voltage cable, new in 2020), Article 250 Part X , and Article 490 .
Article 490 at a glance
- Part Covers
- I General Scope: equipment operating over 1000 V, nominal
II Equipment, specific provisions Circuit breakers, power fuses and fuseholders, distribution cutouts and fuse links, oil-filled cutouts, load interrupters, isolating means, voltage regulators, minimum air separation between live parts
III Metal-enclosed power switchgear and industrial control assemblies Guarding of live parts, grounding, door stops, gas discharge, interlocks, accessibility of energized parts
- IV Mobile and portable equipment Enclosures, locking, power cable connections, grounding
- V Electrode-type boilers Supply system, branch circuit, pressure and temperature limit controls
Key provisions:
Circuit-interrupting devices (490.21): they must have an interrupting rating at least equal to the maximum available fault current and a voltage rating at least equal to the circuit's maximum voltage. Fuses that expel flame when they open must be arranged so they won't endanger people or property.
Isolating means (490.22): there must be a way to completely isolate equipment from all ungrounded conductors. Draw-out switchgear and removable truck panels count as isolating means. Isolating switches that are not interlocked with a circuit-interrupting device need a sign warning against opening them under load .
Metal-enclosed switchgear (Part III): energized parts are guarded, doors that could swing into energized parts need stops, and access to energized compartments is limited to qualified people.
Mobile and portable equipment (Part IV): energized switching and control parts are enclosed in grounded metal enclosures that can be locked, and power cable connections to mobile machines are enclosed.
Article 110 Part III: installations over 1000 volts
Enclosure (110.31): electrical installations in vaults, rooms, closets, or areas surrounded by a wall, screen, or fence and controlled by lock and key are accessible only to qualified persons. An outdoor fence must be at least 7 ft (2.1 m) high, or 6 ft (1.8 m) of fence fabric plus a 1 ft (300 mm) or higher extension with three or more strands of barbed wire .
Entrance (110.33):
At least one entrance at least 24 in. wide and 6-1/2 ft high to each working space.
Where switchgear or control panels exceed 6 ft in width, an entrance is needed at each end , unless there is a continuous, unobstructed path of exit travel or the working space depth is doubled.
Working space depth (Table 110.34(A)):
- Nominal voltage to ground Condition 1 Condition 2 Condition 3
- 1001 to 2500 V 3 ft 4 ft 5 ft
- 2501 to 9000 V 4 ft 5 ft 6 ft
- 9001 to 25,000 V 5 ft 6 ft 9 ft
- 25,001 V to 75 kV 6 ft 8 ft 10 ft
- Above 75 kV 8 ft 10 ft 12 ft
The conditions mean the same thing as in 110.26 (Section 3.1):
Condition 1: exposed live parts on one side and nothing live or grounded on the other.
Condition 2: exposed live parts on one side and grounded parts (including concrete, brick, or tile) on the other.
Condition 3: exposed live parts on both sides.
Locked rooms and warning signs (110.34(C)): entrances to rooms or enclosures containing exposed live parts over 1000 V must be kept locked unless under a qualified person's observation, with warning signs reading "DANGER - HIGH VOLTAGE - KEEP OUT."
Illumination (110.34(D)): working spaces need adequate lighting that can't be controlled only by automatic means, and the lighting may not be placed where people changing lamps are exposed to live parts.
Foreign piping (110.34(F)): pipes or ducts foreign to the electrical installation that need periodic maintenance, or could damage the equipment if they failed, may not be in the vicinity of service equipment, metal-enclosed power switchgear, or industrial control assemblies unless protection is provided.
Wiring methods and cable over 1000 volts
Aboveground (300.37): permitted methods include RMC, IMC, EMT, RTRC, PVC, cable tray, busways, cablebus, other identified raceways, and exposed runs of metal-clad cable suitable for the use.
Underground (Table 300.50), over 1000 V through 22 kV: at least 30 in. of cover for direct-buried cable; 18 in. for nonmetallic raceway listed for direct burial without concrete encasement; 6 in. for RMC or IMC.
Medium-voltage cable (Article 311, 2001 to 35,000 V): in the 2020 NEC, medium-voltage conductors and cable moved out of Article 310 into Article 311, which covers shielding, insulation, and ampacity for Type MV cable.
Grounding over 1 kV (250.180 to 250.194): covers solidly grounded neutral systems, multigrounded neutrals, and impedance-grounded systems.
Washington amendments that apply here
Cable marking (WAC 296-46B-110): every customer-owned cable operating over 1,000 V must be legibly and permanently marked at each termination point and each point where it is accessible , showing phase, operating voltage, and circuit number if applicable.
Service conductors over 1,000 V inside buildings (WAC 296-46B-235): limited to galvanized RMC, galvanized IMC, Schedule 80 PVC , metal-clad cable exposed for its entire length, cablebus, or busways, unless customer-owned overcurrent protection is provided outside the building.
Concentric neutrals (WAC 296-46B-250): on existing multigrounded systems, a cable's concentric shield may continue to be used as the neutral for extensions and repairs. This requires testing and an engineer's certification. New installations need a separate listed neutral.
Classified locations: only the AHJ or a Washington-registered PE may classify a hazardous location (WAC 296-46B-500), which also applies to high-voltage equipment rooms.