Study guide
7.3 Commercial Load Calculations & Voltage Drop
Washington Journeyman Electrician 01 General Journey Level
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Structure & Open-Book Code Navigation
1.1 Washington 01 Electrician Licensing Pathway & Exam Structure 1.2 National Electrical Code Architecture & Fast Lookup Strategies 1.3 Open-Book Exam Rules, Reference Preparation & Pacing
2 Chapter 2: Electrical Theory & Fundamental Math
2.1 Ohm's Law, Joule's Law & Circuit Analysis 2.2 AC Fundamentals, Reactance & Power Factor 2.3 Three-Phase Power Calculations: Wye & Delta Configurations
3 Chapter 3: General Installation Requirements & Conductor Sizing
3.1 Installation Requirements & Working Space Clearances 3.2 Conductor Sizing & Table 310.16 Ampacity 3.3 Temperature Correction Factors & Raceway Derating
4 Chapter 4: Wiring Methods, Raceways & Enclosure Calculations
4.1 Common Wiring Methods & Cable Assemblies 4.2 Conduit & Tubing Installation and Fill Calculations 4.3 Box Fill & Pull Box Sizing Calculations 4.4 Flexible Raceways, ENT, Wireways, Cable Trays, Specialty Cables & Plenum Rules
5 Chapter 5: Branch Circuits, Feeders & Overcurrent Protection
5.1 Branch Circuit Ratings, Receptacle Placement & Lighting 5.2 GFCI, AFCI & Special Protection Requirements 5.3 Overcurrent Protection & Feeder Tap Rules 5.4 Grounded Conductors, Feeders, Outside Circuits & Surge Protection (Articles 200, 215, 225, 280, 285) 5.5 Overcurrent Device Location, Fuses, Circuit Breakers & Transformer Secondary Conductors (Article 240)
6 Chapter 6: Grounding & Bonding (Article 250)
6.1 Grounding vs. Bonding: Core Principles & Definitions 6.2 Grounding Electrode Systems & GEC Sizing 6.3 Main Bonding Jumpers & Equipment Grounding Conductor Sizing
7 Chapter 7: Services, Feeders & Load Calculations
7.1 Electrical Services & Service Equipment (Article 230) 7.2 Dwelling Unit Load Calculations: Standard & Optional Methods 7.3 Commercial Load Calculations & Voltage Drop
8 Chapter 8: Equipment for General Use & Equipment Over 1000 Volts (Articles 400-490)
8.1 Flexible Cords, Fixture Wires, Switches, Receptacles & Panelboards (Articles 400-408) 8.2 Luminaires, Appliances, Space Heating & Other Equipment (Articles 410-427, 455-480) 8.3 Equipment Over 1000 Volts (Article 490 and Related Rules)
9 Chapter 9: Motors, HVAC Equipment, Generators & Transformers (Articles 430-450)
9.1 Motor Branch Circuit Conductor Sizing & Overloads 9.2 Motor Short-Circuit Protection & Disconnecting Means 9.3 Transformers, Generators & Hermetic HVAC Equipment
10 Chapter 10: Hazardous Locations & Special Occupancies (Articles 500-590)
10.1 Hazardous (Classified) Locations (Articles 500–516) 10.2 Health Care Facilities, Places of Assembly & Theaters (Articles 517-540) 10.3 Agricultural Buildings, Mobile Homes, RV Parks, Marinas & Temporary Installations (Articles 545-590)
11 Chapter 11: Special Equipment (Articles 600-695)
11.1 Signs, Cranes, Elevators, EV Charging, Welders, IT Rooms & Industrial Machinery (Articles 600-670) 11.2 Swimming Pools, Spas, Hot Tubs & Fountains (Article 680) 11.3 Solar Photovoltaic Systems, Fuel Cells, Wind & Fire Pumps (Articles 690-695)
12 Chapter 12: Emergency Systems, Special Conditions & Communications (Articles 700-830)
12.1 Emergency, Legally Required & Optional Standby Systems (Articles 700-702) 12.2 Interconnected Power Sources, Energy Storage, Power-Limited Circuits, Fire Alarm & Communications (Articles 705-830)
13 Chapter 13: Washington Electrical Laws & Administrative Code (RCW 19.28 & WAC 296-46B)
13.1 Certificates of Competency, Specialty Scopes & Renewal 13.2 Trainees, Supervision Ratios, Apprenticeship & Qualifying Experience 13.3 Electrical Contractors, Administrators, Bonds & Exemptions 13.4 Permits, Inspections, Class A & Class B Work, and Plan Review 13.5 Civil Penalties, Appeals, Exam Rules & Certificate Discipline 13.6 WAC 296-46B Amendments: Adoption, General Rules, Services, Grounding & Wiring (NEC Chapters 1-4) 13.7 WAC 296-46B Amendments: Special Occupancies, Special Equipment, Emergency Systems & Communications (NEC Chapters 5-8)
7.3 Commercial Load Calculations & Voltage Drop
Key Takeaways Explain This Topic AI
Commercial general lighting uses the Table 220.12 unit loads by occupancy; in the 2020 NEC those unit loads already include the 125 percent continuous-load multiplier, so it is not applied again (Table 220.12, Note 1).
Non-dwelling general receptacle loads are calculated at 180 VA per strap/yoke under NEC 220.14(I), with demand factors applied under Table 220.44 (the first 10 kVA at 100%, and all remainder over 10 kVA at 50%).
Commercial multi-motor feeders are sized under NEC 430.24 at 125% of the highest-rated motor full-load current (FLC) plus 100% of all other motors, using standard NEC Chapter 4 tables rather than motor nameplate ratings.
NEC Informational Notes recommend limiting voltage drop to 3% on branch circuits, 3% on feeders, and 5% total across the entire electrical distribution system to maintain equipment efficiency and prevent overheating.
When phase conductors are upsized to mitigate voltage drop, NEC 250.122(B) mandates that the equipment grounding conductor must be proportionally upsized based on the circular mil increase of the ungrounded phase conductors.
Last updated: September 2026
Commercial Load Calculations & Voltage Drop
Exam Focus: Commercial load calculations and voltage drop formulas are core competencies tested on the Washington 01 General Journey Level Electrician examination. Licensing candidates must master the continuous duty multiplier (125%) for commercial lighting under NEC 210.20(A) and 215.2(A)(1), receptacle strap calculations and Table 220.44 demand factors, multi-motor feeder rules under NEC 430.24, and both single-phase ( 2 K I L / C M 2KIL/CM 2 K I L / CM ) and three-phase ( 3 K I L / C M \sqrt{3}KIL/CM 3 K I L / CM ) voltage drop calculations. Remember: when you increase phase conductor size for voltage drop, you must also upsize the equipment grounding conductor under NEC 250.122(B).
1. Commercial Lighting & Specific Branch-Circuit Loads (NEC 220.12 & 220.14)
Commercial occupancies differ fundamentally from dwelling units: commercial loads operate for long hours, general lighting is classified as continuous, and receptacles are calculated on an individual strap/yoke basis.
General Lighting Loads by Occupancy (NEC Table 220.12)
The 2020 NEC rebuilt Table 220.12 around energy-code lighting densities. Representative values:
- Occupancy (2020 Table 220.12) Unit Load (VA / sq ft)
- Office (including banks) 1.3
- Courthouse 1.4
- Hospital 1.6
- Hotel and motel (including guest rooms) 1.7
- Manufacturing facility 2.2
- Warehouse 1.2
- Parking garage 0.3
Note 1 to Table 220.12: the 125% multiplier for continuous loads (210.20(A)) is already included in these unit loads. Do not multiply the general lighting load from this table by 1.25 again. Dwelling units are no longer in the table; they use 3 VA per sq ft under 220.14(J).
The Continuous Load Factor (NEC 210.20(A) & 215.2(A)(1))
Under Article 100, a continuous load is a load where the maximum current is expected to continue for 3 hours or more .
Commercial lighting, office ambient illumination, and store display cases are standard continuous loads. (The Table 220.12 unit loads already include the 125% factor; apply 125% to other continuous loads such as show windows, signs, and lighting calculated fixture by fixture.)
Conductor Sizing Rule: Feeder and branch-circuit conductors supplying continuous loads must have an allowable ampacity not less than 125% of the continuous load plus 100% of the noncontinuous load: I feeder ≥ ( I continuous × 1.25 ) + I noncontinuous I_{\text{feeder}} \ge (I_{\text{continuous}} \times 1.25) + I_{\text{noncontinuous}} I feeder ≥ ( I continuous × 1.25 ) + I noncontinuous
Overcurrent Device Rule: The overcurrent protective device (breaker or fuse) must be rated at not less than 125% of the continuous load plus 100% of the noncontinuous load, unless the assembly is listed for operation at 100% of its rating (100%-rated breakers).
Commercial Show Window Lighting (NEC 220.14(G))
For show window lighting, calculate not less than 200 VA per linear foot of show window, measured horizontally along its base.
Commercial Electric Sign Outlets (NEC 220.14(F) & 600.5(A))
Each commercial occupancy accessible to pedestrians must have at least one dedicated 20-ampere branch circuit for an electric sign or outline lighting.
The load for this sign circuit must be calculated at not less than 1,200 VA (or the actual nameplate rating if higher).
Sign lighting usually runs 3 hours or more, so it is commonly treated as a continuous load (1,200 VA x 1.25 = 1,500 VA when sizing the circuit).
2. Commercial Receptacle Loads & Demand Factors (NEC 220.14(I) & Table 220.44)
Unlike dwelling units where receptacles are included in the 3 VA/sq ft floor area calculation, commercial receptacles are calculated based on physical yokes and straps. +-----------------------------------------------------------------------------+
- | RECEPTACLE YOKE SIZING RULES |
- | |
- | [ Single Receptacle ] [ Duplex Receptacle ] [ Triplex / Quad ] |
- | Single Strap Single Strap Single Strap |
- | 180 VA 180 VA 180 VA |
- | |
- | [ Two Duplex Receptacles in a 2-Gang Box (Two Separate Straps) ] |
- | Strap 1 = 180 VA + Strap 2 = 180 VA = 360 VA Total |
- +-----------------------------------------------------------------------------+
- Receptacle Outlet Rating (NEC 220.14(I))
Receptacle outlets are calculated at not less than 180 VA for each single or multiple receptacle mounted on one yoke or strap.
A standard duplex receptacle is mounted on one yoke → \rightarrow → calculated at 180 VA .
A 2-gang box containing two duplex receptacles contains two yokes → \rightarrow → calculated at 360 VA ( 2 × 180 VA 2 \times 180\text{ VA} 2 × 180 VA ).
Banks and Office Buildings (NEC 220.14(K))
For banks and office buildings, the receptacle load is the larger of 180 VA per strap or 1 VA per square foot .
Multioutlet Assemblies / Plugmold (NEC 220.14(H))
Where appliances are unlikely to be used simultaneously: 180 VA for each 5-foot length (or fraction thereof).
Where appliances are likely to be used simultaneously (commercial test benches, assembly lines, trade show booths): 180 VA for each 1-foot length (or fraction thereof).
Table 220.44 Demand Factors for Non-Dwelling Receptacles
Commercial receptacle loads calculated at 180 VA per strap may be reduced using the demand factors in NEC Table 220.44 :
- Portion of Receptacle Load Demand Factor
- First 10 kVA (10,000 VA) or less 100%
- Portion over 10 kVA (over 10,000 VA) 50%
Worked Calculation: An office building contains 120 duplex receptacles.
Total connected load: 120 yokes × 180 VA = 21 , 600 VA 120 \text{ yokes} \times 180\text{ VA} = 21,600\text{ VA} 120 yokes × 180 VA = 21 , 600 VA .
First 10,000 VA @ 100% = 10,000 VA .
Remainder: 21 , 600 VA − 10 , 000 VA = 11 , 600 VA × 0.50 = 21,600\text{ VA} - 10,000\text{ VA} = 11,600\text{ VA} \times 0.50 = 21 , 600 VA − 10 , 000 VA = 11 , 600 VA × 0.50 = 5,800 VA .
Total calculated demand load: 10 , 000 VA + 5 , 800 VA = 15 , 800 VA 10,000\text{ VA} + 5,800\text{ VA} = \mathbf{15,800\text{ VA}} 10 , 000 VA + 5 , 800 VA = 15 , 800 VA .
3. Commercial Multi-Motor Feeder Sizing (NEC 430.24)
Feeders supplying two or more motors are sized at 125% of the largest motor's full-load current plus 100% of the others, giving continuous-duty margin for the largest motor (430.24).
The Mandatory 125% Formula (NEC 430.24)
Conductors supplying several motors must have an ampacity not less than: I feeder ≥ ( 1.25 × I FLC, largest motor ) + ∑ I FLC, remaining motors I_{\text{feeder}} \ge (1.25 \times I_{\text{FLC, largest motor}}) + \sum I_{\text{FLC, remaining motors}} I feeder ≥ ( 1.25 × I FLC, largest motor ) + ∑ I FLC, remaining motors
Critical Testing Rule: Tables vs. Nameplate
Under NEC 430.6(A)(1) , you must never use the motor nameplate Full-Load Amperes (FLA) to size conductors or overcurrent protective devices! You must look up the Full-Load Current (FLC) in the official NEC Chapter 4 tables:
- NEC Table 430.248: Single-phase AC motors
- NEC Table 430.250: Three-phase AC motors
Example: A 480V 3-phase feeder powers three motors: 30 HP, 15 HP, and 10 HP.
From Table 430.250 (460V/480V 3-phase):
- 30 HP motor: FLC = 40 Amperes \text{FLC} = 40\text{ Amperes} FLC = 40 Amperes (Largest motor)
- 15 HP motor: FLC = 21 Amperes \text{FLC} = 21\text{ Amperes} FLC = 21 Amperes
- 10 HP motor: FLC = 14 Amperes \text{FLC} = 14\text{ Amperes} FLC = 14 Amperes
Sizing calculation: I feeder = ( 1.25 × 40 A ) + 21 A + 14 A = 50 A + 21 A + 14 A = 85 Amperes I_{\text{feeder}} = (1.25 \times 40\text{A}) + 21\text{A} + 14\text{A} = 50\text{A} + 21\text{A} + 14\text{A} = \mathbf{85\text{ Amperes}} I feeder = ( 1.25 × 40 A ) + 21 A + 14 A = 50 A + 21 A + 14 A = 85 Amperes
From Table 310.16 (75°C Copper), select 4 AWG Cu (rated 85 Amperes).
4. Voltage Drop Fundamentals & Code Recommendations
While the NEC is primarily a safety code, excessive voltage drop impairs safety: it causes motors to draw higher running current and overheat, contactors to chatter and burn, electronic controls to lock up, and lighting to dim drastically.
NEC Informational Note Thresholds
Branch Circuits (NEC 210.19(A) Informational Note No. 4): Branch-circuit conductors should be sized to prevent a voltage drop exceeding 3% at the farthest outlet of power, heating, or lighting loads.
Feeders (NEC 215.2(A)(1) Informational Note No. 2): Feeder conductors should be sized to prevent a voltage drop exceeding 3% .
Total Overall System Drop: The total combined voltage drop on both the feeder and the branch circuit conductors should not exceed 5% overall from the service point to the final utilization equipment. +-----------------------------------------------------------------------------+
- | VOLTAGE DROP CODE THRESHOLDS |
- | |
- | [Service Entrance] |
- | | |
- | v |
- | [Feeder] -------------> Maximum 3% Feeder Voltage Drop |
- | | |
- | v |
- | [Subpanel] |
- | | |
- | v |
- | [Branch Circuit] --------> Maximum 3% Branch-Circuit Voltage Drop |
- | | |
- | v |
- | [Final Load] ============> MAXIMUM 5% COMBINED OVERALL SYSTEM DROP |
- +-----------------------------------------------------------------------------+
- Allowable Voltage Drop in Volts for Standard Systems
Nominal Voltage System Phase 3% Limit (Feeder or Branch) 5% Limit (Total System)
120 V Single-Phase 120 × 0.03 = 3.6 V 120 \times 0.03 = \mathbf{3.6\text{ V}} 120 × 0.03 = 3.6 V 120 × 0.05 = 6.0 V 120 \times 0.05 = \mathbf{6.0\text{ V}} 120 × 0.05 = 6.0 V
208 V Three-Phase 208 × 0.03 = 6.24 V 208 \times 0.03 = \mathbf{6.24\text{ V}} 208 × 0.03 = 6.24 V 208 × 0.05 = 10.4 V 208 \times 0.05 = \mathbf{10.4\text{ V}} 208 × 0.05 = 10.4 V
240 V Single-Phase 240 × 0.03 = 7.2 V 240 \times 0.03 = \mathbf{7.2\text{ V}} 240 × 0.03 = 7.2 V 240 × 0.05 = 12.0 V 240 \times 0.05 = \mathbf{12.0\text{ V}} 240 × 0.05 = 12.0 V
277 V Single-Phase 277 × 0.03 = 8.31 V 277 \times 0.03 = \mathbf{8.31\text{ V}} 277 × 0.03 = 8.31 V 277 × 0.05 = 13.85 V 277 \times 0.05 = \mathbf{13.85\text{ V}} 277 × 0.05 = 13.85 V
480 V Three-Phase 480 × 0.03 = 14.4 V 480 \times 0.03 = \mathbf{14.4\text{ V}} 480 × 0.03 = 14.4 V 480 × 0.05 = 24.0 V 480 \times 0.05 = \mathbf{24.0\text{ V}} 480 × 0.05 = 24.0 V
5. Mathematical Formulas for Voltage Drop
The standard formula derived from Ohm's Law ( V = I × R V = I \times R V = I × R ) accounts for conductor resistance, distance, and conductor cross-sectional area.
Core Variables
V D VD V D : Voltage drop in volts.
K K K : Conductor direct-current resistivity constant in ohms-circular mil per foot at ~75°C:
- Copper ( K K K ): 12.9 Ω ⋅ cmil/ft \Omega\cdot\text{cmil/ft} Ω ⋅ cmil/ft
- Aluminum ( K K K ): 21.2 Ω ⋅ cmil/ft \Omega\cdot\text{cmil/ft} Ω ⋅ cmil/ft
I I I : Circuit current in amperes.
L L L : One-way length of the conductor run in feet.
C M CM CM : Cross-sectional area of conductor in Circular Mils (from NEC Chapter 9, Table 8 ).
Single-Phase Formula
In a single-phase circuit, current travels out on the phase conductor and returns on the neutral or opposite phase leg, requiring a multiplier of 2 for round-trip distance: V D 1-phase = 2 × K × I × L C M VD_{\text{1-phase}} = \frac{2 \times K \times I \times L}{CM} V D 1-phase = CM 2 × K × I × L % V D = ( V D V nominal ) × 100 \%VD = \left(\frac{VD}{V_{\text{nominal}}}\right) \times 100 % V D = ( V nominal V D ) × 100
Three-Phase Formula
In a balanced three-phase circuit, the vector sum of currents in the conductors reduces the effective line-to-line impedance multiplier from 2 to 3 ≈ 1.732 \sqrt{3} \approx 1.732 3 ≈ 1.732 : V D 3-phase = 3 × K × I × L C M ≈ 1.732 × K × I × L C M VD_{\text{3-phase}} = \frac{\sqrt{3} \times K \times I \times L}{CM} \approx \frac{1.732 \times K \times I \times L}{CM} V D 3-phase = CM 3 × K × I × L ≈ CM 1.732 × K × I × L % V D = ( V D V line-to-line ) × 100 \%VD = \left(\frac{VD}{V_{\text{line-to-line}}}\right) \times 100 % V D = ( V line-to-line V D ) × 100
Rearranging to Select Conductor Size (Circular Mils)
To determine the minimum conductor size required to keep voltage drop within a specific voltage limit ( V D allowed VD_{\text{allowed}} V D allowed ):
Single-Phase: C M required = 2 × K × I × L V D allowed CM_{\text{required}} = \frac{2 \times K \times I \times L}{VD_{\text{allowed}}} C M required = V D allowed 2 × K × I × L
Three-Phase: C M required = 1.732 × K × I × L V D allowed CM_{\text{required}} = \frac{1.732 \times K \times I \times L}{VD_{\text{allowed}}} C M required = V D allowed 1.732 × K × I × L
6. Circular Mil Lookup Table (NEC Chapter 9, Table 8)
Conductor Size (AWG/kcmil) Area in Circular Mils ( C M CM CM ) Conductor Size (AWG/kcmil) Area in Circular Mils ( C M CM CM )
- 14 AWG 4,110 1 AWG 83,690
- 12 AWG 6,530 1/0 AWG 105,600
- 10 AWG 10,380 2/0 AWG 133,100
- 8 AWG 16,510 3/0 AWG 167,800
- 6 AWG 26,240 4/0 AWG 211,600
- 4 AWG 41,740 250 kcmil 250,000
- 3 AWG 52,620 350 kcmil 350,000
- 2 AWG 66,360 500 kcmil 500,000
- 7. Step-by-Step Worked Calculation Examples
- Example 1: Three-Phase Commercial Feeder Sizing & Voltage Drop
Scenario: A 480-volt, balanced 3-phase commercial panel located 400 feet from the service switchboard supplies a continuous lighting load of 96 amperes . The conductors are copper installed in steel conduit at 75°C.
Step 1: Check Minimum Ampacity for Continuous Load I min = 96 A × 1.25 = 120 Amperes I_{\text{min}} = 96\text{ A} \times 1.25 = 120\text{ Amperes} I min = 96 A × 1.25 = 120 Amperes
From Table 310.16 (75°C Cu), 1 AWG Cu is rated at 130 Amperes. (Ampacity is satisfied).
Step 2: Determine Maximum Permitted Voltage Drop Allowable 3% drop on 480V feeder: V D allowed = 480 V × 0.03 = 14.4 Volts VD_{\text{allowed}} = 480\text{ V} \times 0.03 = 14.4\text{ Volts} V D allowed = 480 V × 0.03 = 14.4 Volts
Step 3: Solve for Required Circular Mils C M = 1.732 × 12.9 × 96 A × 400 ft 14.4 V = 857 , 963.5 14.4 = 59 , 581 CM CM = \frac{1.732 \times 12.9 \times 96\text{ A} \times 400\text{ ft}}{14.4\text{ V}} = \frac{857,963.5}{14.4} = 59,581\text{ CM} CM = 14.4 V 1.732 × 12.9 × 96 A × 400 ft = 14.4 857 , 963.5 = 59 , 581 CM
Step 4: Select Conductor Size from Chapter 9, Table 8
1 AWG Cu has 83,690 CM .
Since 83 , 690 CM > 59 , 581 CM 83,690\text{ CM} > 59,581\text{ CM} 83 , 690 CM > 59 , 581 CM , 1 AWG Cu satisfies both ampacity and the 3% voltage drop limit!
Let's check the actual voltage drop with 1 AWG: V D = 857 , 963.5 83 , 690 = 10.25 Volts VD = \frac{857,963.5}{83,690} = 10.25\text{ Volts} V D = 83 , 690 857 , 963.5 = 10.25 Volts % V D = ( 10.25 480 ) × 100 = 2.14 % \%VD = \left(\frac{10.25}{480}\right) \times 100 = \mathbf{2.14\%} % V D = ( 480 10.25 ) × 100 = 2.14% (well below the 3% ceiling).
Example 2: Upsizing Conductor and Adjusting Grounding (NEC 250.122(B))
Scenario: A 120-volt, 20-ampere branch circuit powers a parking lot LED light pole located 220 feet from the panel. The continuous load is 16 amperes . The circuit is wired with copper conductors.
Step 1: Sizing for Ampacity A 20A circuit requires 12 AWG Cu (rated 20A per 240.4(D), with 6,530 CM).
Step 2: Calculate Voltage Drop with 12 AWG V D = 2 × 12.9 × 16 A × 220 ft 6 , 530 CM = 90 , 816 6 , 530 = 13.91 Volts VD = \frac{2 \times 12.9 \times 16\text{ A} \times 220\text{ ft}}{6,530\text{ CM}} = \frac{90,816}{6,530} = 13.91\text{ Volts} V D = 6 , 530 CM 2 × 12.9 × 16 A × 220 ft = 6 , 530 90 , 816 = 13.91 Volts
% V D = ( 13.91 V 120 V ) × 100 = 11.59 % \%VD = \left(\frac{13.91\text{ V}}{120\text{ V}}\right) \times 100 = \mathbf{11.59\%} % V D = ( 120 V 13.91 V ) × 100 = 11.59% (Completely unacceptable!)
Step 3: Calculate Required CM for 3% Drop (3.6 Volts) C M required = 90 , 816 3.6 V = 25 , 227 CM CM_{\text{required}} = \frac{90,816}{3.6\text{ V}} = 25,227\text{ CM} C M required = 3.6 V 90 , 816 = 25 , 227 CM
From Chapter 9 Table 8:
8 AWG has 16,510 CM (too small).
6 AWG has 26,240 CM (sufficient).
The ungrounded phase and neutral conductors must be upsized to 6 AWG Cu .
Step 4: Mandatory Equipment Grounding Conductor Adjustment (NEC 250.122(B)) Under NEC 250.122(B) , where ungrounded conductors are increased in size for any reason (including voltage drop), wire-type equipment grounding conductors (EGC) must be increased in size proportionally to the increase in circular mil area of the ungrounded conductors. Proportionality Ratio = C M new ungrounded C M original ungrounded = 26 , 240 CM (6 AWG) 6 , 530 CM (12 AWG) = 4.018 \text{Proportionality Ratio} = \frac{CM_{\text{new ungrounded}}}{CM_{\text{original ungrounded}}} = \frac{26,240\text{ CM (6 AWG)}}{6,530\text{ CM (12 AWG)}} = 4.018 Proportionality Ratio = C M original ungrounded C M new ungrounded = 6 , 530 CM (12 AWG) 26 , 240 CM (6 AWG) = 4.018
The standard EGC for a 20A circuit from Table 250.122 is 12 AWG Cu (6,530 CM).
Apply the multiplier: C M new EGC = 6 , 530 CM × 4.018 = 26 , 238 CM CM_{\text{new EGC}} = 6,530\text{ CM} \times 4.018 = 26,238\text{ CM} C M new EGC = 6 , 530 CM × 4.018 = 26 , 238 CM
Consult Chapter 9 Table 8: 6 AWG Cu (26,240 CM) must be installed as the equipment grounding conductor!
Exam Trap: Never leave a 12 AWG equipment grounding conductor in a conduit where the circuit conductors were upsized to 6 AWG. Failing to upsize the EGC is a direct violation of NEC 250.122(B).