Study guide

11.1 Signs, Cranes, Elevators, EV Charging, Welders, IT Rooms & Industrial Machinery (Articles 600-670)

Washington Journeyman Electrician 01 General Journey Level

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Structure & Open-Book Code Navigation

1.1 Washington 01 Electrician Licensing Pathway & Exam Structure 1.2 National Electrical Code Architecture & Fast Lookup Strategies 1.3 Open-Book Exam Rules, Reference Preparation & Pacing

2 Chapter 2: Electrical Theory & Fundamental Math

2.1 Ohm's Law, Joule's Law & Circuit Analysis 2.2 AC Fundamentals, Reactance & Power Factor 2.3 Three-Phase Power Calculations: Wye & Delta Configurations

3 Chapter 3: General Installation Requirements & Conductor Sizing

3.1 Installation Requirements & Working Space Clearances 3.2 Conductor Sizing & Table 310.16 Ampacity 3.3 Temperature Correction Factors & Raceway Derating

4 Chapter 4: Wiring Methods, Raceways & Enclosure Calculations

4.1 Common Wiring Methods & Cable Assemblies 4.2 Conduit & Tubing Installation and Fill Calculations 4.3 Box Fill & Pull Box Sizing Calculations 4.4 Flexible Raceways, ENT, Wireways, Cable Trays, Specialty Cables & Plenum Rules

5 Chapter 5: Branch Circuits, Feeders & Overcurrent Protection

5.1 Branch Circuit Ratings, Receptacle Placement & Lighting 5.2 GFCI, AFCI & Special Protection Requirements 5.3 Overcurrent Protection & Feeder Tap Rules 5.4 Grounded Conductors, Feeders, Outside Circuits & Surge Protection (Articles 200, 215, 225, 280, 285) 5.5 Overcurrent Device Location, Fuses, Circuit Breakers & Transformer Secondary Conductors (Article 240)

6 Chapter 6: Grounding & Bonding (Article 250)

6.1 Grounding vs. Bonding: Core Principles & Definitions 6.2 Grounding Electrode Systems & GEC Sizing 6.3 Main Bonding Jumpers & Equipment Grounding Conductor Sizing

7 Chapter 7: Services, Feeders & Load Calculations

7.1 Electrical Services & Service Equipment (Article 230) 7.2 Dwelling Unit Load Calculations: Standard & Optional Methods 7.3 Commercial Load Calculations & Voltage Drop

8 Chapter 8: Equipment for General Use & Equipment Over 1000 Volts (Articles 400-490)

8.1 Flexible Cords, Fixture Wires, Switches, Receptacles & Panelboards (Articles 400-408) 8.2 Luminaires, Appliances, Space Heating & Other Equipment (Articles 410-427, 455-480) 8.3 Equipment Over 1000 Volts (Article 490 and Related Rules)

9 Chapter 9: Motors, HVAC Equipment, Generators & Transformers (Articles 430-450)

9.1 Motor Branch Circuit Conductor Sizing & Overloads 9.2 Motor Short-Circuit Protection & Disconnecting Means 9.3 Transformers, Generators & Hermetic HVAC Equipment

10 Chapter 10: Hazardous Locations & Special Occupancies (Articles 500-590)

10.1 Hazardous (Classified) Locations (Articles 500–516) 10.2 Health Care Facilities, Places of Assembly & Theaters (Articles 517-540) 10.3 Agricultural Buildings, Mobile Homes, RV Parks, Marinas & Temporary Installations (Articles 545-590)

11 Chapter 11: Special Equipment (Articles 600-695)

11.1 Signs, Cranes, Elevators, EV Charging, Welders, IT Rooms & Industrial Machinery (Articles 600-670) 11.2 Swimming Pools, Spas, Hot Tubs & Fountains (Article 680) 11.3 Solar Photovoltaic Systems, Fuel Cells, Wind & Fire Pumps (Articles 690-695)

12 Chapter 12: Emergency Systems, Special Conditions & Communications (Articles 700-830)

12.1 Emergency, Legally Required & Optional Standby Systems (Articles 700-702) 12.2 Interconnected Power Sources, Energy Storage, Power-Limited Circuits, Fire Alarm & Communications (Articles 705-830)

13 Chapter 13: Washington Electrical Laws & Administrative Code (RCW 19.28 & WAC 296-46B)

13.1 Certificates of Competency, Specialty Scopes & Renewal 13.2 Trainees, Supervision Ratios, Apprenticeship & Qualifying Experience 13.3 Electrical Contractors, Administrators, Bonds & Exemptions 13.4 Permits, Inspections, Class A & Class B Work, and Plan Review 13.5 Civil Penalties, Appeals, Exam Rules & Certificate Discipline 13.6 WAC 296-46B Amendments: Adoption, General Rules, Services, Grounding & Wiring (NEC Chapters 1-4) 13.7 WAC 296-46B Amendments: Special Occupancies, Special Equipment, Emergency Systems & Communications (NEC Chapters 5-8)

11.1 Signs, Cranes, Elevators, EV Charging, Welders, IT Rooms & Industrial Machinery (Articles 600-670)

Key Takeaways Explain This Topic AI

Each commercial building and occupancy accessible to pedestrians needs at least one sign outlet at each tenant entrance, supplied by a 20-ampere branch circuit that serves no other load (NEC 600.5(A)).

Branch circuits supplying neon sign installations may not be rated over 30 amperes; circuits for incandescent, fluorescent, and LED signs may not be rated over 20 amperes (NEC 600.5(B)).

The elevator main-line disconnect may not be opened or closed from any other part of the premises, except that a shunt trip may open it before sprinklers discharge water (NEC 620.51).

Each outlet installed to charge an electric vehicle must be on an individual branch circuit, and EV charging receptacles need GFCI protection (NEC 625.40, 625.54).

Supply conductors for several transformer arc welders are sized at 100 percent of the two largest, 85 percent of the third, 70 percent of the fourth, and 60 percent of the rest (NEC 630.11(B)).

Last updated: September 2026

Electric signs and outline lighting (Article 600)

Rule 2020 NEC

Required sign outlet: each commercial building and each commercial occupancy accessible to pedestrians needs at least one outlet at each entrance to each tenant space, on a branch circuit of at least 20 A that supplies no other load . Service hallways and corridors are not considered pedestrian entrances. 600.5(A)

The sign circuit is calculated at no less than 1,200 VA per required branch circuit 220.14(F)

Branch circuit rating limits: circuits supplying incandescent, fluorescent, and LED signs 20 A maximum; circuits supplying neon tubing installations 30 A maximum 600.5(B)

Disconnect: each sign or outline lighting system (except portable signs and those supplied only by a Class 2 source) needs an externally operable switch or breaker that opens all ungrounded conductors and controls no other load. It goes at the point where the supply enters the sign or its pole, or within sight of the sign. If any section that can be energized is out of the line of sight, the disconnect must be lockable open (110.25). 600.6(A)

Signs must be listed and marked with the manufacturer, input voltage, and current. Field-installed LED retrofit kits must be listed and the sign marked. 600.3, 600.4

Signs and outline lighting must be at least 14 ft above areas accessible to vehicles, unless protected from physical damage 600.9(A)

Washington (WAC 296-46B-600):

All signs and outline lighting, regardless of voltage, must be listed or field evaluated.

A portable outdoor sign needs a weatherproof GFCI receptacle within 6 ft , and extension cords may not supply it.

LED retrofits of listed signs may be done in place by an 01 general or 04 sign contractor using listed kits, with a required warning label.

Cranes and hoists (Article 610)

Runway conductor disconnect (610.31): readily accessible and operable from the ground or floor, lockable open, opens all ungrounded conductors, and within sight of the runway contact conductors.

Crane disconnect (610.32): a motor-circuit switch, breaker, or molded-case switch in the leads from the runway contact conductors, lockable open. It must be readily accessible from the crane cab or operating station unless an exception applies.

Crane motor conductors are sized with the special tables of 610.14, which account for short-time duty ratings.

Elevators, escalators, and similar equipment (Article 620)

Main-line disconnect (620.51): a single disconnecting means for each unit disconnects the main power supply to the motor and controller. It must be a fused motor-circuit switch or circuit breaker, lockable open.

No remote operation: the disconnect may not be opened or closed from any other part of the premises. The one allowance is sprinklers in the hoistway, machine room, or pit: the disconnect may then automatically open the power supply (shunt trip) before water is applied. The disconnect must be within sight of the motor controller.

Separate branch circuits: car lighting, receptacles, ventilation, and alarms need their own branch circuits (620.22). Machine room and machinery space lighting and receptacles need a separate branch circuit, with the lighting switch at the point of entry (620.23).

GFCI: 125 V, single-phase, 15 A and 20 A receptacles in pits, in hoistways, and on car tops need GFCI protection (620.85).

Washington (WAC 296-46B-620): the main-line disconnect is inside the machine room door on the strike side , not more than 24 in. from the door to the handle, and 36 to 66 in. above the floor.

Electric vehicle power transfer (Article 625)

Rule 2020 NEC

Each outlet installed to charge electric vehicles must be supplied by an individual branch circuit with no other outlets 625.40

EV supply equipment is a continuous load: overcurrent protection at least 125 percent of the maximum load 625.41

EVSE rated over 60 A or over 150 V to ground needs a disconnect in a readily accessible location, lockable open 625.43

All receptacles installed for EV charging need GFCI protection for personnel 625.54

The coupling means of cord-connected EVSE is stored 18 in. to 4 ft above the floor indoors, and 24 in. to 4 ft outdoors 625.50

Washington: installation of EVSE on public works must be done by people certified through the Electric Vehicle Infrastructure Training Program or a similar nationally recognized program (RCW 19.28.285, 2025). Supervised apprentices are covered when their supervising journey level electrician holds the certification.

Electric welders (Article 630)

Transformer and rectifier arc welders (630.11):

One welder: supply conductor ampacity is at least the rated primary current multiplied by the Table 630.11(A) factor for the welder's duty cycle. For example, the factor is 1.00 at 100 percent duty cycle and smaller at lower duty cycles.

A group of welders: conductor ampacity is at least 100 percent of the two largest welders, 85 percent of the third, 70 percent of the fourth, and 60 percent of all the rest (630.11(B)), each based on its individual calculated value.

Overcurrent protection: each welder is protected at no more than 200 percent of its rated primary current (or I1max). The supply conductors are protected at no more than 200 percent of their ampacity (630.12).

Resistance welders (630.31): conductors are sized at no less than 70 percent of rated primary current for seam and automatically fed welders, and 50 percent for manually operated nonautomatic welders.

Worked example: a feeder serves four arc welders with calculated values of 40, 35, 30, and 30 A.

  • 40 + 35 (two largest at 100%) = 75 A
  • 0.85 x 30 (third) = 25.5 A
  • 0.70 x 30 (fourth) = 21 A
  • Minimum feeder ampacity = 75 + 25.5 + 21 = 121.5 A
  • Information technology equipment rooms (Article 645)

Article 645 is optional . It applies only if the room meets all the conditions of 645.4:

  • a disconnecting means complying with 645.10;
  • a dedicated HVAC system (or specific fire and smoke dampers);
  • listed IT equipment;
  • occupied only by people needed to operate and maintain the equipment;

separated by fire-resistance-rated walls, floors, and ceilings.

In exchange, it relaxes some wiring rules, such as allowing certain cables under raised floors. The remote disconnect controls (645.10) at approved, readily accessible locations must disconnect power to all electronic equipment in the room and shut down the dedicated HVAC system, unless the critical operations data system alternative applies.

Industrial machinery (Article 670)

Nameplate (670.3): the machine's nameplate lists the supply voltage, phase, frequency, full-load current, the maximum ampere rating of the short-circuit and ground-fault protective device, the short-circuit current rating , and the largest motor data.

Supply conductors (670.4(A)): ampacity at least 125 percent of the full-load current of all resistance heating loads, plus 125 percent of the full-load current of the highest-rated motor, plus the full-load currents of all other connected motors and apparatus that may run at the same time.

SCCR (670.5): the machine may not be installed where the available fault current exceeds its short-circuit current rating.

Other Chapter 6 articles to recognize

  • Article Covers
  • 604 Manufactured wiring systems
  • 605 Office furnishings (wired partitions)
  • 640 Audio signal equipment
  • 660 X-ray equipment
  • 665 Induction and dielectric heating
  • 668, 669 Electrolytic cells, electroplating
  • 675 Electrically driven or controlled irrigation machines
  • 680 Swimming pools, fountains, and similar installations (Section 11.2)
  • 682 Natural and artificially made bodies of water
  • 690, 691, 692, 694 Solar PV, large-scale PV, fuel cells, wind electric systems (Section 11.3)
  • 695 Fire pumps (Section 11.3)