Study guide

10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington)

Washington Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Administration, Licensing, & General Regulations

1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)

2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances

2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1

3 Chapter 3: Water Heaters & Storage Tanks

3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)

4 Chapter 4: Water Supply and Distribution Systems

4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)

5 Chapter 5: Backflow Prevention & Cross-Connection Control

5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)

6 Chapter 6: Sanitary Drainage Systems & Sizing

6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules

7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors

7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)

8 Chapter 8: Vents and Venting Fundamentals

8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)

9 Chapter 9: Vent Terminations, Traps, & Priming

9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)

10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards

10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)

11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis

11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations

12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing

12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4

13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics

13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)

14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy

14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist

10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington)

Key Takeaways Explain This Topic AI

Washington does not adopt UPC Section 1502, Gray Water Systems; gray water may not be used for irrigation except as permitted by Department of Health rules.

Washington prohibits reclaimed water for toilet flushing or other indoor use in any residential property or dwelling unit where residents can access the plumbing for repairs or modifications (WA 1501.1.1).

Alternate water source piping must have a purple background (Pantone 512 or 522C) with uppercase lettering such as "CAUTION: NONPOTABLE RECLAIMED WATER, DO NOT DRINK" (UPC 601.3.3).

During a cross-connection test, the alternate water system stays depressurized for a period the AHJ sets, never less than 1 hour, while potable outlets are checked (UPC 1501.11.2.2).

If a cross-connection is found, Washington requires chlorinating the potable system at 50 ppm for 24 hours and a Washington-certified lab bacteriological test before recharging (WA 1501.11.2.3).

Last updated: September 2026

Scope

L&I lists UPC Chapter 15 in the Part 1 content. The chapter covers alternate water sources for nonpotable applications :

Reclaimed (recycled) water: treated wastewater delivered by a utility (1503).

Gray water: untreated wastewater from bathtubs, showers, lavatories, and clothes washers (1502).

On-site treated nonpotable water: gray water or other water treated on site for uses such as flushing (1504).

Rainwater catchment is in Chapter 16 (Section 10.2).

Washington Amendments to Chapter 15

Section Washington rule

1501.1.1 Allowable use Where approved or required by the AHJ, reclaimed, gray, and on-site treated water may replace potable water for the uses in the chapter. Reclaimed water may not be used to flush toilets or for other indoor use in any residential property or dwelling unit where residents can access the plumbing for repairs or modifications

1501.2 System design Designed by a registered design professional or a person who demonstrates competency as the AHJ requires. Components, piping, and fittings must be listed

1501.7 Water quality Meets the AHJ's quality requirements for the use, with EPA/625/R-04/108 as guidance. Gray water used to flush toilets or urinals must be oxidized, coagulated, filtered, and disinfected, consistently at Washington Class A reclaimed water quality or better

1501.13.1 Abandonment Disconnect, drain, plug, and cap abandoned systems. Their pipe, tubing, fittings, and valves may not be reused for potable water

1502.0 Gray water systems Not adopted. "Gray water shall not be used for irrigation except as permitted by the department of health rules"

1503.4 Reclaimed connections No connection to potable or other alternate water. Potable makeup water to a reclaimed storage tank only through an approved air gap

1504.1 and 1504.7 On-site treated Supplies water closets, urinals, trap primers for floor drains and floor sinks, and other AHJ-approved uses. Treatment for flushing or surface irrigation must oxidize, coagulate, filter, and disinfect to Class A reclaimed quality or better, and be AHJ-approved

Exam trap: Questions built on UPC 1502 gray water details (surge tanks, mulch basins, emitters, irrigation field sizing) describe provisions that Washington does not adopt . In Washington, gray water irrigation falls under Department of Health rules.

General Requirements Still in Effect (UPC 1501)

1501.3 Permit: A permit is required to build, install, or alter an alternate water source system.

1501.5 Maintenance: Inspect and maintain per Table 1501.5 and the manufacturer. The property owner keeps a maintenance log for permitted systems. The designer supplies an operation and maintenance manual.

1501.9: No mercury-containing controls may contact alternate water.

1501.10 Signs: Restrooms in commercial, industrial, and institutional buildings that flush with reclaimed or on-site treated water get signs with 1/2-inch letters . Equipment rooms get signs with 1-inch letters .

1501.12 Separation: Treated nonpotable pipes may share a trench with potable pipes at 12 inches minimum vertical and horizontal separation when both materials are approved for use within a building.

1501.14 Sizing: Size alternate water piping per Chapter 6 , like potable piping.

Identification (UPC 601.3)

  • System Background Lettering
  • Potable Green White

Nonpotable (general) Yellow Black uppercase: "CAUTION: NONPOTABLE WATER, DO NOT DRINK," with the liquid named and the flow direction shown

Alternate water sources Purple (Pantone 512, 522C, or equivalent) Uppercase, black: "CAUTION: NONPOTABLE GRAY WATER, DO NOT DRINK," "CAUTION: NONPOTABLE RECLAIMED WATER, DO NOT DRINK," "CAUTION: ON-SITE TREATED NONPOTABLE WATER, DO NOT DRINK," or "CAUTION: NONPOTABLE RAINWATER WATER, DO NOT DRINK"

Reclaimed water valves, except fixture supply controls, have locking features (1503.8). Hose bibbs on reclaimed systems are not allowed in areas accessible to the public . Public access uses a quick-disconnect different from potable, and bibbs are labeled (1503.9). Reclaimed pipes may share a potable trench at 12 inches vertical and horizontal separation; otherwise the horizontal separation increases to 60 inches , and potable is always above reclaimed (1503.11).

Cross-Connection Inspection and Testing (UPC 1501.11)

Supply test (1501.11.1): Test alternate water piping like potable piping (Section 1.2).

Initial and annual inspection and test (1501.11.2): Isolate potable and alternate systems and test each independently. A visual inspection checks meters, pumps, signs, exposed piping, and valve lock seals. Cross-connection testing is required annually by the AHJ unless site conditions do not require it, but never less than once every 4 years .

Cross-connection test (1501.11.2.2):

Pressurize the potable system. Shut down, depressurize, and drain the alternate system.

Keep the alternate system empty for the time the AHJ sets, never less than 1 hour .

Check the alternate system's drain and all outlets. Flow from an alternate outlet indicates a cross-connection. No flow from a potable outlet means it is connected to the alternate system.

Then reverse the procedure: depressurize the potable system and test the other way.

Discovery of a cross-connection (Washington 1501.11.2.3):

Shut down the reclaimed water piping at the meter and drain the riser.

Shut down the potable water at the meter.

Uncover and disconnect the cross-connection.

Retest the building.

Chlorinate the potable system at 50 ppm for 24 hours.

Flush, then have a bacteriological test performed by a laboratory certified for drinking water in Washington . Recharge only when the AHJ, the health authority, and the purveyor accept the results.