5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490)

Washington Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Administration, Licensing, & General Regulations

1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)

2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances

2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1

3 Chapter 3: Water Heaters & Storage Tanks

3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)

4 Chapter 4: Water Supply and Distribution Systems

4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)

5 Chapter 5: Backflow Prevention & Cross-Connection Control

5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)

6 Chapter 6: Sanitary Drainage Systems & Sizing

6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules

7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors

7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)

8 Chapter 8: Vents and Venting Fundamentals

8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)

9 Chapter 9: Vent Terminations, Traps, & Priming

9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)

10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards

10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)

11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis

11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations

12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing

12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4

13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics

13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)

14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy

14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist

5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490)

Key Takeaways Explain This Topic AI

Backsiphonage is backflow caused by negative (sub-atmospheric) pressure in the supply piping; backpressure is backflow caused by downstream pressure exceeding the supply pressure.

UPC Table 603.2 classifies degree of hazard as pollution (low hazard) or contamination (high hazard).

UPC 602.2 prohibits connecting domestic water to any other source or used-water system unless a backflow preventer approved for the hazard is provided.

UPC 603.4.4 forbids direct connection between potable water and sewer-connected wastes under any condition, with or without backflow protection.

WAC 246-290-490 requires an air gap, RPBA, or RPDA for premises isolation of high health hazard premises such as hospitals, car washes, and mortuaries.

Last updated: September 2026

Why Backflow Is a Life-Safety Topic

Drinking water is kept safe by moving it only one way: from the source, through the meter, to the fixtures. Any cross-connection creates a possible path for contaminants to enter the potable system. A cross-connection is any link between potable piping and a nonpotable liquid, gas, or used water. The UPC's starting rules are absolute:

602.1: Potable piping may not be installed so that used, unclean, polluted, or contaminated water can enter it from a tank, receptor, equipment, or plumbing fixture.

602.2: No connection may be made between domestic water and piping carrying water from any other source, used water, or chemicals, gases, or substances unless a backflow prevention device approved for the potential hazard is provided and maintained.

602.4: A private water supply may not be connected to any other supply without the approval of the AHJ, health department, or other department having jurisdiction.

603.4.4: Direct connections between potable water piping and sewer-connected wastes are not permitted under any condition, with or without backflow protection. Potable water discharging to drainage must pass through an air gap of two pipe diameters, but not less than 1 inch . Alternatively, a vacuum breaker may be connected on the inlet side of a trap at least 6 inches above the flood rim, where it will never see backpressure.

The Two Mechanisms

  • Backsiphonage Backpressure
  • Cause Negative or sub-atmospheric pressure in the supply Downstream pressure higher than supply pressure

Typical triggers Main break, heavy fire-flow draw, draining a building's riser, undersized mains with high velocity Booster pumps, boilers, elevated tanks, thermal expansion, pressurized process equipment

Protective methods Air gap, AVB, PVB, SVB, DC, RP Only air gap, DC (low hazard), or RP

Why vacuum breakers fail under backpressure: A vacuum breaker works by admitting air when supply pressure drops. Under backpressure, the downstream pressure keeps its float or check closed toward the supply, and nothing prevents the flow reversal. That is why Table 603.2 lists AVBs, PVBs, and SVBs for backsiphonage only .

Atmospheric physics: Atmospheric pressure is 14.7 psia, which can lift water about 33.9 feet (14.7 × 2.31). A full vacuum in a riser can therefore pull contaminated water up from a basin that far below. A hose left in a bucket of chemicals is the classic example.

Degree of Hazard (UPC Table 603.2)

UPC term Common term Meaning Examples

Pollution (low hazard) Non-health hazard Impairs quality (taste, color, odor) but is not a health hazard Potable water in a closed loop without additives, aesthetic contaminants

Contamination (high hazard) Health hazard Could cause illness or death Boiler water with chemicals, irrigation with chemical injection, mortuary equipment, dental vacuum pumps, sewage

Washington's DOH rule uses the parallel terms "high health cross-connection hazard" and "low cross-connection hazard."

Washington amendments that change hazard assignments

603.5.10 Boilers: Potable connections to steam or hot water boilers require an air gap or an RP . The unamended UPC also allows a double check on untreated boilers.

603.5.12 Carbonators: The potable supply to carbonators requires a listed RP . Washington deletes the ASSE 1022 carbonated-beverage device line from Table 603.2. Downstream piping may not be copper or other CO₂-affected material.

603.5.6 Irrigation (no pumps, no chemicals): An AVB, PVB, SVB, or RP is acceptable. A DC is allowed only when approved by both the water purveyor and the AHJ.

Direct and Indirect Cross-Connections

A direct cross-connection is a piped connection to a nonpotable system, such as a boiler makeup line or a process tank feed. It can see both backpressure and backsiphonage .

An indirect cross-connection is an outlet that can become submerged, such as a hose in a bucket or a fill line below a tank's rim. It usually sees backsiphonage only , because an open vessel cannot pressurize the supply.

Two Layers of Protection in Washington

In-premises (point-of-use) protection: The UPC, as amended by WAC 51-56, governs devices inside the building at each hazard. Examples include vacuum breakers on hose bibbs, an RP on a boiler, and an air gap on a dishwasher.

Premises isolation (containment): The public water system purveyor must run a cross-connection program under WAC 246-290-490 . That program includes a device at the service connection sized to the premises' hazard.

WAC 246-290-490 Table 12, premises isolation:

  • Degree of hazard Approved preventer
  • High health cross-connection hazard AG, RPBA, or RPDA
  • Low cross-connection hazard AG, RPBA, RPDA, DCVA, or DCDA

Table 13 lists high-hazard premises that need an air gap or RPBA at the service. Examples include farms and dairies, beverage bottling plants, car washes , chemical plants, commercial laundries and dry cleaners, hospitals and medical and dental clinics , laboratories, metal plating, mortuaries , piers and docks, and irrigation systems with chemical addition. Severe hazards include wastewater treatment plants and radioactive or nuclear facilities. They need an air gap, or an RPBA combined with an in-plant air gap.