7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710)
Washington Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Administration, Licensing, & General Regulations
1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)
2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances
2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1
3 Chapter 3: Water Heaters & Storage Tanks
3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)
4 Chapter 4: Water Supply and Distribution Systems
4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)
5 Chapter 5: Backflow Prevention & Cross-Connection Control
5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)
6 Chapter 6: Sanitary Drainage Systems & Sizing
6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules
7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors
7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)
8 Chapter 8: Vents and Venting Fundamentals
8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)
9 Chapter 9: Vent Terminations, Traps, & Priming
9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)
10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards
10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)
11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis
11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations
12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing
12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4
13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics
13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)
14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy
14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist
7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710)
Key Takeaways Explain This Topic AI
A sewage ejector receiving water closets or urinals must discharge at least 20 gpm (UPC 710.3).
In a single dwelling unit, the ejector must pass a 1-1/2-inch solid ball and have discharge piping of at least 2 inches; elsewhere a 2-inch ball and 3-inch piping (UPC 710.3).
Ejector discharge piping needs an accessible backwater or swing check valve with the gate or ball valve on its discharge side, and connects to a horizontal drain from the top through a wye (UPC 710.4).
Sumps in public-use occupancies need dual pumps that alternate in normal use, plus an audio and visual alarm (UPC 710.9).
A sump vent may never be smaller than 1-1/2 inches, and an air-operated ejector vent may not combine with other vents (UPC 710.10).
Last updated: September 2026
When a Sump Is Required
Section 709.1 prefers gravity drainage wherever practicable. When fixtures are below the crown level of the main sewer , 710.2 requires them to drain by gravity into an approved watertight sump or receiving tank . From there the waste is lifted into the building drain or sewer by an approved ejector, pump, or equivalent mechanical device.
Section 710.7 requires the drainage and vent piping serving sumps and lifting devices to follow the same rules as gravity systems . That includes trapping, venting, sizing, and cleanouts (707.11 addresses cleanouts for pressure drainage).
Sewage Ejectors and Pumps Receiving Water Closets or Urinals (UPC 710.3)
- Requirement Single dwelling unit Other than single dwelling unit
- Minimum discharge capacity 20 gpm 20 gpm
- Solid ball the pump must pass 1-1/2 inches 2 inches
- Minimum discharge pipe size 2 inches 3 inches
- Valves on each discharge Backwater valve and gate valve Backwater valve and gate valve
- Discharge Line (UPC 710.4)
Use approved pressure-rated material .
Provide an accessible backwater or swing check valve and a gate or ball valve . The gate or ball valve goes on the discharge side of the check valve , so the check can be isolated and serviced.
Where the discharge connects to a horizontal gravity drain, it must enter from the top through a wye branch .
710.5: The building drain or sewer receiving pump discharge is sized at 2 DFU per gpm of flow. A 30 gpm ejector therefore adds 60 DFU to the drain it discharges into.
Sump and Receiving Tank Construction (710.8)
Watertight , made of concrete, metal, or other approved material. Poured concrete must be reinforced and designed to recognized standards. Metal must be thick enough for its purpose and protected against corrosion inside and out.
Controls and Alarms (UPC 710.9)
Sumps and receiving tanks discharge automatically .
In a public use occupancy: dual pumps or ejectors that alternate in normal use and operate independently in case of overload or failure.
An audio and visual alarm , readily accessible, signals pump failure or overload.
The lowest inlet must be at least 2 inches above the high-water or "starting" level of the sump.
Covers and Vents (UPC 710.10)
Covers must be substantial, with a bolt-and-gasket manhole or equivalent opening for inspection, repair, and cleaning.
The vent comes off the top and extends separately through the roof or, where permitted, combines with other vents.
The vent must keep the sump at atmospheric pressure. It may not be smaller than Table 703.2 requires for the fixtures discharging into the sump, and never less than 1-1/2 inches .
Once the sump vent combines with the vents of the fixtures discharging into it, the combined vent need not exceed the size required for all those fixtures.
A vent from an air-operated sewage ejector may not combine with other vents.
Other Lifting Devices
Air tanks (710.11): Equal in cubic capacity to the ejectors they serve, with air pressure of at least 2 pounds per foot of height the sewage is raised. Water-operated ejectors are prohibited.
Grinder pumps (710.12) are permitted. Their discharge piping is sized per the manufacturer's instructions but is at least 1-1/4 inches , with a check valve and fullway shutoff valve in the discharge line.
Macerating toilet systems and pumped waste systems (710.13) may replace a sewage pump system where approved by the AHJ . They must comply with ASME A112.3.4/CSA B45.9 and be installed per the manufacturer's instructions:
The sump is watertight and gastight.
Discharge piping is sized per the manufacturer's instructions, but at least 3/4 inch , with a check valve and fullway shutoff valve in the line or inside the unit.
Fixtures discharging into the macerator are vented per the code, and the sump is vented per the manufacturer's instructions. That vent may connect to the fixture venting.
Access to Mechanical Devices (UPC 710.6)
Backwater valves, gate and ball valves, unions, motors, compressors, air tanks, and other devices required by 710 must be accessible for inspection and repair. Unless continuously exposed, they go in a masonry pit with an adequately sized removable cover .
Worked Scenario: Basement Bathroom in a House
A basement bathroom (water closet, lavatory, shower) sits below the sewer crown.
Sump: watertight, with a gasketed, bolted cover.
Ejector: single-dwelling pump rated for at least 20 gpm that passes a 1-1/2-inch solid.
Discharge: 2-inch pressure-rated pipe, with a check valve and then a gate or ball valve downstream of it. It enters the horizontal building drain from the top through a wye .
Venting: the fixtures are vented as in a gravity system. The sump vent is at least 1-1/2 inches and may combine with the fixture vents.
Drain sizing: add 2 DFU per gpm of pump discharge to the drain that receives it.
Upper floors: they stay on gravity drainage. Any gravity-drained fixtures on a floor below the next upstream manhole cover still need a backwater valve (710.1; Section 6.4).