Study guide
7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)
Washington Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Administration, Licensing, & General Regulations
1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)
2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances
2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1
3 Chapter 3: Water Heaters & Storage Tanks
3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)
4 Chapter 4: Water Supply and Distribution Systems
4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)
5 Chapter 5: Backflow Prevention & Cross-Connection Control
5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)
6 Chapter 6: Sanitary Drainage Systems & Sizing
6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules
7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors
7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)
8 Chapter 8: Vents and Venting Fundamentals
8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)
9 Chapter 9: Vent Terminations, Traps, & Priming
9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)
10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards
10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)
11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis
11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations
12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing
12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4
13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics
13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)
14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy
14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist
7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)
Key Takeaways Explain This Topic AI
Each fixture discharging into a grease interceptor must be individually trapped and vented (UPC 1014.1.1).
The total capacity in gallons of fixtures draining to a hydromechanical grease interceptor may not exceed 2.5 times its certified gpm rating (UPC 1014.2.1).
UPC Table 1014.3.6 sizes gravity grease interceptors from 500 gallons for 8 DFU through 750 for 21, 1,000 for 35, and 1,250 for 90.
Toilets, urinals, and similar fixtures may not drain through a gravity grease interceptor (UPC 1014.3.2.1).
Sand interceptors must have a water seal of at least 6 inches, be vented, and have an outlet of at least 3 inches (UPC 1016.3, 1016.4).
Last updated: September 2026
When Interceptors Are Required (UPC 1009)
1009.1: The AHJ requires interceptors (clarifiers) where needed to handle wastes containing grease, flammable wastes, sand, solids, acid or alkaline substances , or other ingredients harmful to the drainage system, sewer, or sewage disposal.
1009.2: The AHJ approves size, type, and location. Only wastes that need treatment go into an interceptor.
1009.3: Interceptors for sand and heavy solids have a water seal of at least 6 inches and must be readily accessible for cleaning.
1009.4: Interceptors must not become air-bound where closed covers are used; each is properly vented.
1009.5: Covers must be readily accessible . Needing a ladder or removing bulky equipment to service an interceptor is an accessibility violation . The location appears on the approved plans.
1009.6: Interceptors are maintained by periodic removal of grease, scum, oil, and solids.
707.7: The cleanout for an interceptor is outside the interceptor.
Grease Interceptors (UPC 1014)
When the AHJ requires pretreatment, fixtures and equipment producing grease-laden waste in food-preparation areas discharge into an approved grease interceptor. It must meet ASME A112.14.3, ASME A112.14.4, CSA B481, PDI G-101, or PDI G-102, and be sized per 1014.2.1 or 1014.3.6.
- Rule Requirement
- 1014.1.1 Each fixture discharging into a grease interceptor is individually trapped and vented
1014.1.2 Collected grease may not go into drainage piping or a sewer. The AHJ may mandate added equipment and a maintenance program if an interceptor is neglected
1014.1.3 No food waste disposer or dishwasher may connect to or discharge into a grease interceptor. Commercial disposers may discharge directly to the building drainage system
Hydromechanical grease interceptors (HGI)
1014.2.1 Capacity: The total capacity in gallons of the fixtures discharging into an HGI may not exceed 2.5 times the interceptor's certified gpm flow rate (Table 1014.2.1).
1014.2.2: A vent is installed downstream of the HGI.
Fixture capacity method (Example 1014.2.1): gallons = length × width × depth (in inches) ÷ 231. Multiply by a 0.75 fill factor , then divide by the drain period ( 1 or 2 minutes ) to get gpm.
One 24 × 24 × 12-inch compartment holds 6,912 ÷ 231 ≈ 29.9 gallons. At a 0.75 fill, that is about 22.4 gallons, and two compartments about 44.9 gallons .
At a 1-minute drain period, the load is about 45 gpm , so the code example selects a 50 gpm unit. At a 2-minute drain period, the load is about 22.4 gpm , so a 25 gpm unit.
Table 1014.2.1 (gravity flow rates at 1/4 inch per foot): 2-inch pipe, 20 gpm full flow; 3-inch, 60 gpm; 4-inch, 125 gpm; 5-inch, 230 gpm; 6-inch, 375 gpm.
Gravity grease interceptors (GGI)
Serve the commercial kitchen; toilets, urinals, and similar fixtures may not drain through them (1014.3.2.1). Waste enters through the inlet pipe.
Scullery and pot sinks, dishwashers, soup kettles, and floor drains in grease areas may drain through the interceptor where the AHJ approves (1014.3.2).
Located as close as practical to the fixtures, accessible to pumping equipment. An IAPMO Z1001 interceptor may not be installed inside a building where food is handled (1014.3.4).
Each business establishment needing one has its own, unless the AHJ approves otherwise.
Table 1014.3.6, gravity grease interceptor sizing:
- DFU 8 21 35 90 172 216 307 342 428 576 720 2,112 2,640
- Volume (gallons) 500 750 1,000 1,250 1,500 2,000 2,500 3,000 4,000 5,000 7,500 10,000 15,000
When DFU are unknown, size from the maximum horizontal DFU of the inlet pipe in Table 703.2. For equipment with no DFU value, add the known flow in gpm multiplied by 30 minutes .
Code example 1014.3.6: three floor drains (2 DFU each = 6), a mop sink (3), and a food-prep sink (3) total 12 DFU . That exceeds 8, so the next row applies: a 750-gallon interceptor.
Abandoned gravity interceptors are pumped and filled like abandoned sewers (1014.3.7). FOG disposal systems must produce effluent of no more than 100 mg/L FOG, per ASME A112.14.6 (1015.4).
Other Interceptors
Section Use Key requirement
1010.1 Slaughterhouses, meat and fish packing, rendering, soap and hide-curing plants Approved grease interceptor
1011.1 Wash racks for vehicles and machinery Protected from storm water and drained to an approved interceptor
1012.1 Commercial and industrial laundries without integral strainers Interceptor with a removable basket that stops solids 1/2 inch or larger
1013.1 Bottling plants Interceptor that separates broken glass and solids
1016 Sand Wastes heavier than water Two-section baffled design. Outlet the same size as the inlet, minimum 3 inches . Inlet section at least 2 sq ft net free opening, plus 1 sq ft per 5 gpm over 20 gpm. At least 2 feet deep below the outlet invert. 6-inch seal , vented
1017 Oil and flammable liquid Repair garages, gas stations with grease racks or pits, and oily process wastes Separation or vapor compartment independently vented outdoors. A shared header must be at least 6 inches above the spill line of the lowest floor drain. Flammable vapor vent at least 2 inches . Rated units carry a stamped full-flow gpm rating and an overflow line to an underground tank