2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421)
Washington Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Administration, Licensing, & General Regulations
1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)
2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances
2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1
3 Chapter 3: Water Heaters & Storage Tanks
3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)
4 Chapter 4: Water Supply and Distribution Systems
4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)
5 Chapter 5: Backflow Prevention & Cross-Connection Control
5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)
6 Chapter 6: Sanitary Drainage Systems & Sizing
6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules
7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors
7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)
8 Chapter 8: Vents and Venting Fundamentals
8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)
9 Chapter 9: Vent Terminations, Traps, & Priming
9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)
10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards
10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)
11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis
11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations
12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing
12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4
13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics
13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)
14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy
14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist
2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421)
Key Takeaways Explain This Topic AI
UPC 405.2 prohibits trough urinals and urinals with an invisible seal.
Washington's 2015 amendment to UPC 412.1 limits urinals to 1 gallon per flush and prohibits continuous-flow urinals.
Nonwater urinals need a barrier liquid seal, an upstream fixture of at least 1 WSFU on the same drain, and a water supply rough-in (UPC 412.1.1).
Washington's 418.3 requires floor drains in toilet rooms with two or more water closets or a water closet plus a urinal (except dwelling units), and in commercial laundry rooms.
Kitchen and laundry sinks need at least 1-1/2-inch waste outlets and service sinks at least 2-inch outlets (UPC 420.4).
Last updated: September 2026
Urinals (UPC 405.2, 412, 413.2)
Prohibited urinals (405.2): Trough urinals and urinals with an invisible seal are prohibited.
Standards and water use (412.1, WA 2015 amendment): Urinals comply with ASME A112.19.2/CSA B45.1, ASME A112.19.19, or CSA B45.5/IAPMO Z124. The average water use may not exceed 1 gallon per flush , and continuous-flow urinals are prohibited.
Clearances (402.5): At least 12 inches from the centerline to a side wall or partition and 24 inches center to center.
Backflow (412.2): The water supply needs an approved vacuum breaker or other approved device under 603.5. A flushometer atmospheric vacuum breaker's critical level must be at least 6 inches above the highest part of the urinal (603.5.1).
Flushometers (413.2): A manually controlled flushometer valve may not flush more than one urinal.
Water supply sizing: Table 610.3 lists a 3/4-inch minimum branch for a flushometer-valve urinal and 1/2 inch for a flush-tank urinal.
Nonwater urinals (412.1.1)
A barrier liquid sealant maintains the trap seal.
The urinal must permit uninhibited flow to the drainage system and be maintained per the manufacturer's instructions.
At least one water-supplied fixture rated at least 1 WSFU must be installed upstream on the same drain line to rinse the drain.
A water distribution rough-in must be provided to the urinal location, so a backflow-protected flushing valve can be added later.
Floor Drains (UPC 418) and Floor Sinks (421)
418.2: A floor drain is a plumbing fixture. It needs an approved strainer whose waterway equals the area of the tailpiece and a watertight joint with the floor.
418.3 Location (Washington amendment): Floor drains are required in:
Toilet rooms containing two or more water closets, or one water closet and one urinal , except in a dwelling unit. The floor must slope toward the drain.
Laundry rooms in commercial buildings and common laundry facilities in multifamily buildings.
418.4 Food storage: Drains in storerooms, walk-in coolers and freezers, or refrigerated equipment must have indirect waste piping . Each area gets its own waste pipe with an indirect connection. Traps must be located where the seal will not freeze. Otherwise, slope the freezer floor to a floor drain outside the storage compartment.
418.5: Floors slope to floor drains.
421.2: A floor sink's waste outlet needs a removable, accessible strainer or grate.
1007.1: Floor drain traps subject to infrequent use need trap seal protection (see Section 9.3).
Sinks (UPC 420)
- Rule Requirement
- Kitchen and laundry sink waste outlet (420.4) At least 1-1/2 inches
- Service sink waste outlet (420.4) At least 2 inches
- Commercial pre-rinse spray valve (420.3) 1.6 gpm at 60 psi , with integral automatic shutoff
- Special-use sinks (406.2) Bonderized, galvanized sheet steel at least No. 16 gauge
- Dishwashers and Food Waste Disposers (UPC 414, 419)
414.3 (Washington amendment): A domestic dishwasher discharges indirectly through an air gap fitting (807.3). It may discharge into a waste receptor, a wye branch fitting on the kitchen sink tailpiece, or the dishwasher connection of a food waste disposer. Commercial dishwashing machines discharge indirectly through an air gap.
414.2: The water supply to a commercial dishwasher is protected by an air gap, an AVB, PVB, or SVB, or an ASSE 1004 device.
419.2: Use wye or other directional branch fittings in continuous wastes that receive disposer discharge. A dishwasher drain may not connect to a sink tailpiece, continuous waste, or trap on the discharge side of a disposer .
419.3: Disposers need a cold water supply protected by an air gap or backflow device.
Drinking Fountains, Eyewash, and Special Fixtures
Drinking fountains (415): Self-closing units that comply with NSF 61 (415.1). They may discharge directly or through an air break (415.3) and may not be installed in toilet rooms (415.4). Washington does not adopt 415.2, drinking fountain alternatives . Bottle-filler substitutions and fountain counts come from Building Code Chapter 29 (Section 2.4).
Emergency eyewash and showers (416): These comply with ISEA Z358.1, are not limited in flow rate , and must be on the same level as the hazard with an unobstructed, signed path. A drain is not required. If one is provided, its discharge must meet the chemical waste rules in 811.
Special fixtures (406.1): Baptisteries, ornamental ponds, aquaria, and fountains need AHJ approval before installation.
Prohibited fixtures (405.3): No fixed wooden or tile wash trays or sinks for domestic use in dwellings. No sheet-metal-lined wooden bathtubs. No dry or chemical toilets in a dwelling without Health Officer approval.
Faucets and Fixture Fittings (UPC 417)
417.1: Faucets comply with ASME A112.18.1/CSA B125.1, and those under NSF 61's scope must meet it.
417.3 and 417.4: Handheld showers and pull-out spouts need integral backflow protection or a separate device such as ASME A112.18.3 or ASSE 1014.
417.5 Hot on the left: With two handles, the left-hand control controls hot water when facing the outlet. Single-handle shower valves must match their markings.