2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408)
Washington Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Administration, Licensing, & General Regulations
1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)
2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances
2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1
3 Chapter 3: Water Heaters & Storage Tanks
3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)
4 Chapter 4: Water Supply and Distribution Systems
4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)
5 Chapter 5: Backflow Prevention & Cross-Connection Control
5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)
6 Chapter 6: Sanitary Drainage Systems & Sizing
6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules
7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors
7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)
8 Chapter 8: Vents and Venting Fundamentals
8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)
9 Chapter 9: Vent Terminations, Traps, & Priming
9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)
10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards
10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)
11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis
11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations
12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing
12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4
13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics
13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)
14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy
14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist
2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408)
Key Takeaways Explain This Topic AI
Washington amends UPC 408.6 so a shower compartment needs at least 900 square inches and must hold a 30-inch circle up to 70 inches above the drain.
A shower dam or threshold must be 2 to 9 inches deep from its top to the top of the drain, and the receptor floor slopes 1/4 to 1/2 inch per foot (UPC 408.5).
Shower pan liners extend at least 3 inches above the finished dam, pitch 1/4 inch per foot to weep holes, and are tested by filling to the rough threshold (UPC 408.7).
Shower and tub-shower valves must meet ASSE 1016 with handle stops set to a 120°F maximum; the water heater thermostat does not count (UPC 408.3).
Minimum waste outlets are 1-1/4 inches for lavatories, 1-1/2 inches for bathtubs, and 2 inches for showers (UPC 407.5, 409.2, 408.4).
Last updated: September 2026
Why Bathing Fixtures Matter on the Exam
Showers and tubs combine water, heat, and hidden waterproofing. That combination produces many code dimensions: compartment size, threshold depth, liner height, pan slope, drain size, and temperature limits. Washington amends several of these rules, so read this section against the 2015 UPC plus WAC 51-56.
- Showers (UPC 408)
- Size, water use, and drain
Item Rule
Compartment size (WA 408.6) At least 900 square inches of finished interior that can also hold a 30-inch circle . Measure at the top of the threshold, and maintain the area and circle to 70 inches above the drain.
Exceptions Showers designed to ICC/ANSI A117.1, and receptors at least 30 × 60 inches
Allowed protrusions Valves, showerheads, soap dishes, shelves, grab bars; fold-down seats in accessible showers may enter the circle
Showerhead flow (408.2) 2.5 gpm at 80 psi in the 2015 code and 2015 Washington amendment; emergency showers are exempt
Waste outlet (408.4) At least 2 inches ; the strainer waterway must equal the tailpiece area
Washington exception to 408.4 When a tub is replaced by a shower in a dwelling unit, a 2-inch waste is not readily available, and the AHJ approves, the outlet, tailpiece, trap, and trap arm may be 1-1/2 inches if only one showerhead is installed
Washington difference: The unamended 2015 UPC requires 1,024 square inches . Washington reduces the area to 900 square inches but keeps the 30-inch circle. A 30 × 30-inch shower (900 sq in) passes in Washington. A 24 × 44-inch shower (1,056 sq in) still fails because it cannot hold a 30-inch circle.
Thresholds and doors (408.5)
A finished dam, curb, or threshold must be at least 1 inch lower than the sides and back of the receptor.
The threshold must be at least 2 inches and not more than 9 inches deep , measured from the top of the dam to the top of the drain.
The receptor floor slopes to the drain at not less than 1/4 inch and not more than 1/2 inch per foot .
The receptor has an integral nailing flange extending at least 1 inch above the top of the sides.
Thresholds must accommodate a 22-inch door , and shower doors must leave at least a 22-inch unobstructed opening for egress.
Section 408.9 places controls and heads so the head does not discharge directly at the entrance. That way the bather can adjust the valve before stepping in. Section 408.10 requires the riser from the valve to the head to be securely attached.
Site-built shower pans (408.7)
Lining height: Line the subfloor and rough walls to at least 3 inches above the top of the finished dam or threshold . Also line built-in seats to 3 inches above their horizontal surfaces.
Pitch: Slope the lining 1/4 inch per foot to the weep holes of the subdrain, over a smooth, solidly formed subbase.
Jambs: Carry the lining up the rough jambs and over the rough threshold, and fasten it on the outside face.
No fasteners low: Do not nail or perforate the lining at any point less than 1 inch above the finished dam or threshold .
Subdrain: Use an approved subdrain set flush with the subbase. It needs a clamping ring and weep holes into the waste line, and the weep holes must be protected from clogging.
- Liner material Requirement
- Plasticized PVC sheet (408.7.1) ASTM D4551; solvent cemented joints
- Chlorinated polyethylene (CPE) sheet (408.7.2) ASTM D4068
- Sheet lead (408.7.3) At least 4 lb per square foot , asphalt coated, joined by burning
- Sheet copper (408.7.4) ASTM B152, at least 12 oz per square foot ; brazed or soldered
Hot-mopped felt At least three layers of 15-pound asphalt-impregnated felt; corners reinforced with webbing lapped 4 inches
Shower pan test (408.7.5): Fill the receptor with water to the level of the rough threshold . Place the test plug so that both the upper and under sides of the subpan are tested where it is clamped to the drain.
Public shower floors (408.8): Floors must be nonskid, and one bather's wastewater must not pass over areas used by other bathers. Gutters slope at least 2% , with drains no more than 8 feet from sidewalls and no more than 16 feet apart.
Scald and Temperature Limits
Fixture Device Maximum
Shower and tub-shower (408.3) Pressure-balance, thermostatic, or combination valve per ASSE 1016 or ASME A112.18.1/CSA B125.1 Handle position stops set to 120°F
- Gang showers on one tempered supply (408.3) Mixing valve per ASSE 1069 120°F
- Bathtub and whirlpool filler (409.4) Device per ASSE 1070 or CSA B125.3 120°F
- Public lavatory (407.3) Device per ASSE 1070 or CSA B125.3 120°F
- Bidet (410.3) Device per ASSE 1070 or CSA B125.3 110°F
In every case the code states that the water heater thermostat is not an acceptable control . The shower and tub-shower valve must be at the point of use and protect against both scald and thermal shock at the showerhead's rated flow.
Bathtubs and Whirlpool Tubs (UPC 409)
409.2: The waste outlet and tailpiece are at least 1-1/2 inches , with a stopper or strainer.
409.3 and 404.1: The overflow connects on the house (inlet) side of the trap . It must be arranged so standing water does not rise in it when the stopper is closed.
409.5: The filler is protected by an air gap or a listed fixture fitting (417).
409.6 Whirlpools: The access opening must allow removal and replacement of the pump. Crawl-space pump access must be within 20 feet of an access door or crawl hole. The pump sits above the crown weir of the trap , and pump and piping are self-draining.
Lavatories and Bidets (UPC 407, 410)
407.5: The waste outlet and tailpiece are at least 1-1/4 inches , with a stopper or strainer. Overflows follow 404.1.
407.2 (2015 WA amendment): Lavatory and kitchen faucets and replacement aerators are limited to 2.5 gpm . Public lavatory faucets other than metering type are limited to 0.5 gpm . Metering faucets deliver no more than 0.25 gallon per cycle (407.2.2).
407.4 (WA amendment): Lavatories in restrooms for the general public need self-closing metering valves . Exceptions apply where designed for persons with disabilities and in day care centers for children under 6.
410.2: Protect the bidet water supply with an air gap or an approved AVB, PVB, or SVB.