Study guide
11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment
Washington Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Administration, Licensing, & General Regulations
1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)
2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances
2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1
3 Chapter 3: Water Heaters & Storage Tanks
3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)
4 Chapter 4: Water Supply and Distribution Systems
4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)
5 Chapter 5: Backflow Prevention & Cross-Connection Control
5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)
6 Chapter 6: Sanitary Drainage Systems & Sizing
6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules
7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors
7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)
8 Chapter 8: Vents and Venting Fundamentals
8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)
9 Chapter 9: Vent Terminations, Traps, & Priming
9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)
10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards
10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)
11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis
11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations
12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing
12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4
13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics
13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)
14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy
14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist
11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment
Key Takeaways Explain This Topic AI
In UPC Table 703.2, 1-1/2-inch horizontal drainage pipe carries only 1 DFU, so two lavatories on a horizontal branch require 2-inch pipe.
A drain segment receiving a water closet must be at least 3 inches, because Table 703.2 note 3 bars water closets from 2-inch pipe.
A 3-inch vertical stack may carry up to 48 DFU and four water closets, but a 3-inch horizontal drain only 35 DFU and three water closets (Table 703.2 note 4).
Public Table 702.1 values used on commercial drawings include 4 DFU for a 1.6 gpf water closet, 1 for a lavatory, 2 for a 1.0 gpf integral-trap urinal, and 3 for a mop basin.
A drain may not get smaller in the direction of flow; once a segment is 3 inches, everything downstream stays 3 inches or larger.
Last updated: September 2026
Step 1: DFU and Trap Size for Every Fixture (Table 702.1, Public)
- Fixture Minimum trap and trap arm Public DFU
- Water closet, 1.6 gpf flushometer valve 3 in 4.0
- Lavatory 1-1/4 in 1.0
- Urinal, integral trap, 1.0 gpf 2 in 2.0
- Floor drain 2 in 2.0
- Service or mop basin (2-inch trap) 2 in 3.0
- Drinking fountain 1-1/4 in 0.5
Restroom group total: 2 × 4.0 + 2 × 1.0 + 2.0 + 2.0 = 14.0 DFU , including 2 water closets .
Step 2: Build the Ledger (Second-Floor Branch, Horizontal)
The limits below come from Table 703.2 , horizontal column: 1-1/4 in = 1; 1-1/2 in = 1; 2 in = 8 (no water closets); 3 in = 35 (maximum 3 water closets); 4 in = 216.
Segment What joins Running DFU Water closets H/V Minimum size Why
A LAV-1 trap arm 1.0 0 H 1-1/4 in Trap arm at the Table 702.1 minimum; 1-1/4-inch arm carries up to 1 DFU (Table 702.2(1))
- B + LAV-2 2.0 0 H 2 in 1-1/2-inch horizontal is limited to 1 DFU; 2 inches carries 8
- C + urinal 4.0 0 H 2 in 4 is 8 or less; urinal trap is 2 inches
- D + floor drain 6.0 0 H 2 in 6 is 8 or less
- E + WC-1 10.0 1 H 3 in Water closets not allowed on 2-inch pipe (note 3)
- F + WC-2 14.0 2 H 3 in 14 is 35 or less, and 2 water closets is 3 or fewer
Checkpoint: Segment B is the classic trap. Many candidates write 1-1/2 inches for two lavatories. In the horizontal column, 1-1/2-inch pipe allows only 1 DFU , so the answer is 2 inches .
Step 3: The Stack (Vertical)
The limits below come from Table 703.2 , vertical column: 1-1/2 in = 2; 2 in = 16 (no water closets); 3 in = 48 (maximum 4 water closets); 4 in = 256. Vertical length limit for 3 inches: 212 feet.
Segment Load Water closets Minimum size Why
G (stack, 2nd floor to 1st floor) 14.0 2 3 in 14 is 48 or less; 2 water closets is 4 or fewer; stack well under 212 feet
Step 4: First-Floor Branch (Horizontal)
Segment Load Water closets Minimum size Why
H (restroom group + mop sink + drinking fountain) 14.0 + 3.0 + 0.5 = 17.5 2 3 in 17.5 is 35 or less; 2 water closets is 3 or fewer
Inside the branch, the mop sink's 2-inch trap arm and the drinking fountain's 1-1/4-inch trap arm are sized from Table 702.1. Any horizontal section carrying only those two fixtures (3.5 DFU) could be 2 inches. Downstream of the first water closet connection, the branch is 3 inches.
Step 5: Building Drain (Horizontal)
Segment Load Water closets Minimum size Why
J (stack + first-floor branch) 14.0 + 17.5 = 31.5 4 4 in 31.5 fits within 3-inch horizontal (35 DFU), but four water closets exceed the three allowed on a 3-inch horizontal (note 4).
Two more checks:
Slope: at 1/8 inch per foot (4-inch and larger, AHJ approval), the 4-inch capacity becomes 216 × 0.8 = 172 DFU, still far above 31.5.
Washington exception to note 4 (four 1.6 gpf water closets on a 3-inch horizontal) applies only to single-family dwelling additions or alterations with AHJ approval. It does not apply to this office building.
Step 6: Answer Common Question Forms
- Question Answer from the ledger
- "How many fixture units at segment D?" 6
- "Minimum size of segment B?" 2 inches
- "Minimum size of the stack?" 3 inches
- "Fixture units in the building drain?" 31.5
- "Minimum size of the building drain?" 4 inches
- Variations the Exam Can Throw at You
Private occupancy: Change the water closet value to 3.0 and recompute. A private restroom group of 2 water closets, 2 lavatories, and 1 tub/shower totals 3 + 3 + 1 + 1 + 2 = 10 DFU.
A 2-inch trap arm feeding 5 DFU: Table 702.2(1) limits a 2-inch trap to 4 DFU. An unlisted fixture rated by trap size cannot exceed that.
Continuous flow: A 10 gpm continuous discharge adds 20 DFU (702.3).
Battery of three or more clothes washers: use 6 DFU each for common piping (Table 702.1 note 5).
A 1-1/2-inch vertical waste serving two lavatories: allowed (vertical 2 DFU). Two kitchen sinks at 2 DFU each on 1-1/2-inch vertical pipe are not allowed (note 2: sinks may not exceed 1 fixture unit on this size).
Never reduce downstream. If segment E is 3 inches, segments F, G, and J cannot be smaller than 3 inches, even if their DFU alone would allow it.