11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations

Washington Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Administration, Licensing, & General Regulations

1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)

2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances

2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1

3 Chapter 3: Water Heaters & Storage Tanks

3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)

4 Chapter 4: Water Supply and Distribution Systems

4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)

5 Chapter 5: Backflow Prevention & Cross-Connection Control

5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)

6 Chapter 6: Sanitary Drainage Systems & Sizing

6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules

7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors

7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)

8 Chapter 8: Vents and Venting Fundamentals

8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)

9 Chapter 9: Vent Terminations, Traps, & Priming

9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)

10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards

10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)

11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis

11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations

12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing

12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4

13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics

13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)

14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy

14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist

11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations

Key Takeaways Explain This Topic AI

A sanitary tee may be used only for horizontal-to-vertical connections; horizontal-to-horizontal and vertical-to-horizontal turns need wyes or combination wye and one-eighth bends (UPC 706).

A water closet on 2-inch pipe, or more than three water closets on a 3-inch horizontal drain, violates Table 703.2 notes 3 and 4.

A trap arm longer than Table 1002.2 allows, or a water closet more than 6 feet from its vent, is a violation.

A vent taken off below the trap weir (except for water closets), or from the bottom of a horizontal drain, violates UPC 905.2 and 905.5.

Washington requires cleanouts at the upper terminal, every 100 feet, and for turns totaling more than 135 degrees, with 12 or 18 inches of clearance (WA 707.4, 707.9).

Last updated: September 2026

Why Violation Questions Appear

L&I's Part 2 description centers on sizing, but a drawing that shows fixtures, piping, vents, and cleanouts also lets the exam ask whether a connection or arrangement is legal. The rules are the same ones you use for Part 1, applied to a picture. Work through the drawing with this checklist.

Fittings and Changes of Direction

  • Look for Violation Code
  • Sanitary tee joining two horizontal lines Must be a wye or combination wye and 1/8 bend 706.3
  • Vertical line dropping into a horizontal drain through a sanitary tee Same requirement 706.4
  • Double sanitary tee whose barrel is not two sizes larger than its largest inlet Prohibited 706.2

Double hub, tapped tee, side inlet quarter bend, running thread, band, or saddle used as a drainage fitting Prohibited 310.1

  • Any waste connected to a closet bend or water closet stub Prohibited 310.3
  • Drain or vent drilled and tapped for a connection Prohibited 310.2
  • Drain reduced in size in the direction of flow Obstructs flow 310.5
  • Sizing
  • Look for Violation Code
  • Water closet on 2-inch drain No water closets on 2-inch pipe Table 703.2 note 3

Four or more water closets on a 3-inch horizontal drain Limit 3 (Washington exception only for single-family additions or alterations with AHJ approval) Table 703.2 note 4

  • Five or more water closets on a 3-inch vertical stack Limit 4 Table 703.2 note 4
  • Two or more DFU on a 1-1/2-inch horizontal drain Limit 1 DFU Table 703.2

A 1-1/2-inch drain on a kitchen sink, dishwasher, or urinal where a 2-inch drain is required Minimum 2-inch drain Table 702.1 note 2

A 1-1/2-inch trap on a shower Showers need a 2-inch trap and waste outlet (WA exception only for a tub-to-shower replacement with AHJ approval) Table 702.1; WA 408.4

  • Slope of 1/8 inch per foot on 3-inch pipe Only 4-inch and larger, with AHJ approval 708.1
  • Traps
  • Look for Violation Code
  • S-trap, bell trap, crown-vented trap, or a trap with movable parts Prohibited 1004.1, 1004.2
  • Two traps in series on one fixture ( double trapping ) Prohibited 1004.1
  • Fixture tailpiece longer than 24 inches Prohibited 1001.2

Trap arm longer than Table 1002.2 (30, 42, 60, 72, or 120 inches for 1-1/4 through 4-inch arms) Too long 1002.2

  • Water closet more than 6 feet from its vent, measured from the top of the flange Too long Table 1002.2 note 2
  • Trap larger than one pipe size over Table 702.1, or not the same size as its trap arm Prohibited 1003.3
  • Clothes washer trap below the floor , or a standpipe under 18 or over 30 inches Prohibited 804.1
  • Vents
  • Look for Violation Code
  • Vent taken off the bottom of a horizontal drain, or below its centerline Must be above the centerline 905.2
  • Vent opening below the trap weir (other than water closets) Acts like a crown vent 905.5, 1002.4

Vent turning horizontal below 6 inches above the flood-level rim without drainage fittings and grade Violation 905.3

  • Vent with sags or pockets Must drip back to the drain 905.1
  • Individual vent smaller than half the drain, or smaller than 1-1/4 inches Undersized 904.1
  • Vents through the roof whose total area is less than the required building sewer Aggregate venting fails 904.1
  • Vent reduced in size through the roof Must be undiminished 905.4

Vent terminal within 10 feet of a window or air intake and not 3 feet above it, or less than 6 inches above the roof Termination 906.1, 906.2

  • A branch with no vent at all (single-stack, unvented branch) Prohibited 310.4
  • Restaurant kitchen equipment on a circuit-vented branch Washington prohibition WA 911.1
  • Cleanouts (Washington 707)
  • Look for Violation Code
  • No cleanout at the upper terminal of a horizontal drain (unless an exception applies) Missing WA 707.4
  • Horizontal run over 100 feet with no intermediate cleanout One required per 100 feet or fraction WA 707.4
  • Horizontal turns totaling more than 135 degrees without an added cleanout Missing WA 707.4
  • Branch shorter than 5 feet serving a sink or urinal with no cleanout Exception 1 does not apply WA 707.4
  • Less than 12 inches in front of a 2-inch cleanout, or 18 inches for larger Clearance WA 707.9
  • Undersized cleanout plug Table 707.1 sizes 707.10
  • Other Items

Fixtures below the next upstream manhole cover with no backwater valve (710.1).

Drainage connections within 8 feet of the base of a suds-producing stack serving three or more stories (711.1).

Ejector discharge entering a horizontal drain from the side instead of from the top through a wye (710.4).

A dishwasher tied into the discharge side of a disposer (419.2).

Practice: Find the Four Violations

A drawing shows a second-floor restroom. A 2-inch horizontal branch carries two lavatories and a floor drain, then a water closet connects to the same 2-inch branch. A sanitary tee joins that branch to a 3-inch horizontal main. The floor drain's 2-inch trap arm runs 6 feet to its vent. The lavatory vents rise 3 inches above the lavatory rims, then run horizontally to the branch vent.

Answers:

The water closet on the 2-inch branch violates note 3 . The branch must be 3 inches from the closet connection downstream.

The sanitary tee joining two horizontal lines violates 706.3 . Use a wye or combination wye and 1/8 bend.

A 6-foot (72-inch) trap arm on a 2-inch floor drain exceeds the 60-inch limit in Table 1002.2.

The lavatory vents turn horizontal only 3 inches above the rims, which violates 905.3 . They must rise 6 inches above the flood-level rim, or be installed with drainage fittings and grade.