12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4

Washington Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Administration, Licensing, & General Regulations

1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)

2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances

2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1

3 Chapter 3: Water Heaters & Storage Tanks

3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)

4 Chapter 4: Water Supply and Distribution Systems

4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)

5 Chapter 5: Backflow Prevention & Cross-Connection Control

5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)

6 Chapter 6: Sanitary Drainage Systems & Sizing

6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules

7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors

7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)

8 Chapter 8: Vents and Venting Fundamentals

8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)

9 Chapter 9: Vent Terminations, Traps, & Priming

9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)

10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards

10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)

11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis

11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations

12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing

12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4

13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics

13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)

14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy

14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist

12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4

Key Takeaways Explain This Topic AI

To size the meter and building supply, follow down the chosen Table 610.4 column to the first fixture-unit value equal to or greater than the load, and read the two left-hand columns (UPC 610.8).

Each branch is sized by its own fixture units, the system's total developed length, and the meter size, and no branch needs to exceed the building supply size (UPC 610.9).

Piping to a flushometer valve may never be smaller than the valve inlet, and Table 610.3 sets 1-inch minimum branches for flushometer water closets and 3/4-inch for flushometer urinals.

In the 46-60 psi range at 150 feet, Table 610.4 allows 4 fixture units on 1/2-inch pipe, 14 on 3/4-inch, 28 on 1-inch, and 128 on 1-1/2-inch pipe with a 1-1/2-inch meter.

The example office's 99.5 fixture units at 58 psi and 140 feet require a 1-1/2-inch meter and a 1-1/2-inch building supply.

Last updated: September 2026

The Column We Are Using

From Section 12.3: 58 psi , so the 46–60 psi range, and 140 feet , so the 150-foot column. Table 610.4, 46–60 psi, 150-foot column:

  • Meter and street service Building supply and branches Max fixture units
  • 3/4 1/2 4
  • 3/4 3/4 14
  • 3/4 1 28
  • 1 1 30
  • 3/4 1-1/4 39
  • 1 1-1/4 52
  • 1-1/2 1-1/4 66
  • 1 1-1/2 85
  • 1-1/2 1-1/2 128
  • 2 1-1/2 150
  • 1 2 85
  • 1-1/2 2 272
  • 2 2 368
  • 2 2-1/2 535
  • Step 1: Meter and Building Supply (610.8)

Load = 99.5 FU. Reading down the column: 4, 14, 28, 30, 39, 52, 66, 85, then 128 . That row gives a 1-1/2-inch meter and street service and a 1-1/2-inch building supply . It satisfies the 3/4-inch minimum.

If the drawing states an existing 1-inch meter , the 1-inch rows (30, 52, 85, and 85 for 2-inch pipe) cannot carry 99.5 FU. The meter itself would have to be upsized, which is why the meter and supply are chosen together.

Step 2: Branches (610.9)

Section 610.9 sizes each branch from its own fixture units , the total developed length of the system (the same 150-foot column), and the meter size . Two limits bracket the answer:

Upper limit: no branch needs to be larger than the building supply (1-1/2 inches here).

Lower limit: the Table 610.3 minimum fixture branch size, and for flushometers, never smaller than the valve inlet (610.10).

Reading method: Stay in the same column. Find the smallest branch size whose fixture-unit value is at least the branch load, using rows for the installed 1-1/2-inch meter. For the small sizes (1/2, 3/4, and 1 inch), the table only lists 3/4-inch or 1-inch meters. Those smaller-meter rows are conservative for a building with a larger meter, so use them.

  • Segment Load (FU) Table 610.4 result Code minimum Size
  • S2 main to heater tee 97.0 1-1/2 (128) — 1-1/2 in
  • S3 cold main to restroom 95.4 1-1/2 (128) — 1-1/2 in
  • S4 flushometer branch (2 WC + 1 UR) 90 1-1/4 carries 66 at most, so 1-1/2 (128) 1 in 1-1/2 in
  • S4a single water closet 40 1 in carries 30 at most; 1-1/4 carries 66 1 in (Table 610.3) 1-1/4 in
  • S4b single urinal 20 3/4 carries 14; 1 in carries 28 3/4 in 1 in
  • S5 cold branch to lavatories, sinks, fountain 5.375 1/2 carries 4; 3/4 carries 14 1/2 in 3/4 in
  • Lavatory, cold or hot 0.75 1/2 (4) 1/2 in 1/2 in
  • Mop sink, cold or hot 2.25 1/2 (4) 1/2 in 1/2 in
  • Hose bibb branch 2.5 (note 8) 1/2 (4) 1/2 in 1/2 in
  • S6 cold feed to water heater 4.875 3/4 (14) — 3/4 in
  • H1 hot main 4.875 3/4 (14) — 3/4 in
  • H2 hot to lavatories 1.5 1/2 (4) 1/2 in 1/2 in
  • H3 hot to sinks 3.375 1/2 (4) 1/2 in 1/2 in

Observations:

The flushometer water closet branch is 1-1/4 inches, not 1 inch. The 1-inch minimum in Table 610.3 is a floor. At 46–60 psi and 150 feet, 1-inch pipe carries only 28 or 30 FU, less than a flushometer's 40.

The urinal branch is 1 inch , larger than its 3/4-inch minimum, for the same reason: 3/4 inch carries only 14 FU in this column.

Hot branches are small because only three-quarters of each fixture's value lands on the hot side.

Step 3: Velocity and Special Cases

Section 610.12 limits copper velocity to 8 ft/s cold and 5 ft/s hot , and 610.1 requires every design to stay within the code's maximum velocities.

Flushometer tanks (pressure-assist tanks) are sized like flush tank water closets, not flushometer valves (610.11).

Section 610.13 exempts engineered systems acceptable to the AHJ, minor alterations and additions where the AHJ finds the supply adequate, replacement fixtures, and piping that is part of fixture equipment.

The Complete Answer Set for the Example

  • Question Answer
  • Total fixture units on the building supply 99.5
  • Pressure range 46–60 psi
  • Length column 150 feet
  • Meter and street service size 1-1/2 inch
  • Building supply size 1-1/2 inch
  • Flushometer branch serving 2 WC + 1 UR 90 FU; 1-1/2 inch
  • Single flushometer water closet branch 40 FU; 1-1/4 inch
  • Cold feed to water heater 4.875 FU; 3/4 inch
  • Hot main 4.875 FU; 3/4 inch
  • If You Get Stuck

Recheck the occupancy column (public or private).

Recheck the flushometer count per section (40, 70, 90, 105, or 115 plus 10 each).

Recheck 1/2 psi per foot , not 0.433.

Confirm the length column is at or above the developed length.

Confirm the building supply is at least 3/4 inch and no branch exceeds the building supply.