Study guide
12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column
Washington Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Administration, Licensing, & General Regulations
1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)
2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances
2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1
3 Chapter 3: Water Heaters & Storage Tanks
3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)
4 Chapter 4: Water Supply and Distribution Systems
4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)
5 Chapter 5: Backflow Prevention & Cross-Connection Control
5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)
6 Chapter 6: Sanitary Drainage Systems & Sizing
6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules
7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors
7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)
8 Chapter 8: Vents and Venting Fundamentals
8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)
9 Chapter 9: Vent Terminations, Traps, & Priming
9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)
10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards
10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)
11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis
11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations
12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing
12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4
13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics
13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)
14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy
14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist
12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column
Key Takeaways Explain This Topic AI
UPC 610.8 adjusts available pressure by 1/2 psi for each foot of elevation between the source and the highest water outlet before choosing the Table 610.4 pressure range.
Table 610.4 has three pressure ranges: 30 to 45 psi, 46 to 60 psi, and over 60 psi, all measured as available static pressure after head loss.
Where a pressure regulator is installed, Table 610.4 sizing is based on 80 percent of the reduced pressure (UPC 608.2).
Pressure loss through water filters, softeners, backflow preventers, tankless heaters, and similar devices must be included in the calculation (UPC 610.2).
Choose the Table 610.4 length column equal to or longer than the developed length to the most remote outlet: 40, 60, 80, 100, 150, 200 feet, and so on up to 1,000 feet.
Last updated: September 2026
Step 1: Start from the Right Pressure
Minimum street pressure at the meter or other source (610.7 and 610.8). If the drawing gives a range, use the low end.
Regulator installed? Use 80% of the reduced (set) pressure (608.2). A regulator set at 65 psi gives 0.80 × 65 = 52 psi to start from.
Devices with pressure loss (610.2): if the drawing gives a loss, such as 10 psi through a backflow assembly or 5 psi through a softener, include it by subtracting it from the available pressure.
Step 2: Adjust for Elevation (1/2 psi per Foot)
Section 610.8(2): add or subtract 1/2 psi for each foot of elevation difference between the source and the highest water supply outlet. Subtract when the highest outlet is above the meter. Add when every outlet is below it, for example a building downhill from the meter.
Physics versus the table. Water actually exerts 0.433 psi per foot. The table method deliberately uses 0.5 psi per foot , which is more conservative. On Part 3, when you are choosing the Table 610.4 range, use 1/2 psi per foot .
Step 3: Pick the Pressure Range
Table 610.4 note 1 describes the ranges as "available static pressure after head loss":
- Range Use when the adjusted pressure is
- 30–45 psi 30 to 45 psi
- 46–60 psi 46 to 60 psi
- Over 60 psi Above 60 psi
Below 30 psi, Table 610.4 cannot be used. Size by Appendix A, or raise the pressure. Section 608.1 requires at least 15 psi residual at fixtures.
Step 4: Pick the Length Column
Columns: 40, 60, 80, 100, 150, 200, 250, 300, 400, 500, 600, 700, 800, 900, 1,000 feet . Choose the column equal to or longer than the developed length from the meter to the most remote outlet (610.8(4)). All segments of the system, the building supply and every branch, are sized in that same column (610.9: "the total developed length of the system").
Worked Examples
- Case Start Adjustments Available Range
- Section 12.1 office 62 psi Highest outlet 8 ft up: −4 psi 58 psi 46–60
- Two-story house 55 psi Highest outlet 15 ft up: −7.5 psi 47.5 psi 46–60
- Hillside house below the street 48 psi Highest outlet 10 ft below the meter: +5 psi 53 psi 46–60
Building with RP backflow assembly 70 psi 12 psi RP loss (610.2); highest outlet 20 ft up: −10 psi 48 psi 46–60
- Regulator set at 70 psi 70 × 0.80 = 56 psi Highest outlet 12 ft up: −6 psi 50 psi 46–60
- Three-story building 58 psi Highest outlet 30 ft up: −15 psi 43 psi 30–45
High-pressure main, with regulator set at 80 psi 80 × 0.80 = 64 psi Highest outlet 6 ft up: −3 psi 61 psi Over 60
Length examples: 140 feet uses the 150 column, 95 feet uses 100 , 100 feet exactly uses 100 , and 205 feet uses 250 .
Why the Range Choice Matters
With the same load and length, a lower pressure range allows fewer fixture units per pipe size. For the 150-foot column:
- Meter / supply 30–45 psi 46–60 psi Over 60 psi
- 3/4 / 3/4 9 14 17
- 3/4 / 1 17 28 35
- 1 / 1-1/4 32 52 74
- 1-1/2 / 1-1/2 70 128 151
A 50-FU building at 150 feet needs a 1-1/2-inch supply in the 30–45 range (1 / 1-1/2 = 56), but only 1-1/4 inch in the 46–60 range (1 / 1-1/4 = 52).
Measuring Developed Length on the Drawing
Developed length follows the pipe, not the straight line. Suppose the drawing shows this path from the meter to the most remote outlet:
- Run Length
- Meter to the building wall 45 ft
- Building wall to the water heater tee 20 ft
- Tee to the restroom main 35 ft
- Rise in the wall to the ceiling 10 ft
- Ceiling run to the farthest lavatory 22 ft
- Drop to the lavatory stop 8 ft
- Total developed length 140 ft
Every piece of pipe counts, including rises and drops. The 150-foot column applies. The elevation adjustment uses only the net height of the highest outlet above the meter, which in the example is 8 feet. It does not use the 10-foot rise to the ceiling, because that pipe comes back down before any outlet.
Two Elevation Factors in One Chapter
The UPC uses two different elevation factors, and the exam can test either:
Table 610.4 method (610.8): add or subtract 1/2 psi per foot . This is more conservative than the physical value, and it keeps the arithmetic simple under exam conditions.
Appendix A method (A 104.2): multiply the elevation difference by 0.43 to get the loss in static pressure. Appendix A then uses friction-loss charts and a chosen residual pressure at the highest fixture.
On Part 3 you are applying Table 610.4, so apply 610.8 exactly as written. If a Part 1 question asks for the static pressure lost to a given rise, it is asking for the physical value of about 0.433 psi per foot .
Checklist Before You Open Table 610.4
Minimum street pressure, or 80% of the regulator setting.
Minus device losses given on the drawing.
Plus or minus 1/2 psi per foot to the highest outlet.
Range: 30–45, 46–60, or over 60.
Length column at or above the meter-to-most-remote-outlet developed length.
Total fixture units from Section 12.2, with flushometers per Table 610.10.