12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot
Washington Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Administration, Licensing, & General Regulations
1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)
2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances
2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1
3 Chapter 3: Water Heaters & Storage Tanks
3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)
4 Chapter 4: Water Supply and Distribution Systems
4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)
5 Chapter 5: Backflow Prevention & Cross-Connection Control
5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)
6 Chapter 6: Sanitary Drainage Systems & Sizing
6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules
7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors
7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)
8 Chapter 8: Vents and Venting Fundamentals
8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)
9 Chapter 9: Vent Terminations, Traps, & Priming
9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)
10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards
10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)
11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis
11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations
12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing
12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4
13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics
13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)
14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy
14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist
12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot
Key Takeaways Explain This Topic AI
Table 610.3 values represent the total load on the cold water building supply; hot and cold branch loads may each be taken as three-quarters of the listed value (note 3).
Flushometer fixture units depend on how many valves a section serves: 40 for one water closet, 70 for two, and 20 for one urinal, with water closets and urinals added together (Table 610.10).
A water heater's cold inlet carries the hot-side fixture units of the fixtures it serves.
The first hose bibb counts 2.5 fixture units and each additional hose bibb 1.0 on shared piping, but each hose bibb branch is sized for 2.5 (Table 610.3 note 8).
In the example office, the building supply carries 99.5 fixture units: 90 for the flushometers plus 9.5 for the other fixtures.
Last updated: September 2026
The Rules for Counting
Use the right column of Table 610.3 (private, public, or assembly). An office restroom is public .
Flushometer valves use Table 610.10 , counted by the number of valves on each pipe section :
- Valves on the section Water closets (FU) Urinals (FU)
- 1 40 20
- 2 70 35
- 3 90 45
- 4 105 53
- 5 or more 115, plus 10 per valve over 5 58, plus 5 per valve over 5
Water closet and urinal values are added when both are on a section (Example 610.10: 2 WC plus 2 UR = 70 + 35 = 105).
3. Hot and cold separation (note 3): For fixtures with both hot and cold, the listed value is the building supply load . Each separate hot or cold branch may be counted at 3/4 of the listed value. Cold-only fixtures (drinking fountain, hose bibb, flushometers) count their full value on the cold side.
4. Hose bibbs (note 8): the first counts 2.5 and each additional counts 1.0 on shared piping. Each hose bibb's own branch is sized for 2.5 .
5. Continuous demands (note 5) are added in gpm , separately from fixture units.
Example Values (Table 610.3, Public)
- Fixture Listed FU (public) Cold side (3/4) Hot side (3/4)
- Lavatory 1.0 0.75 0.75
- Service or mop basin 3.0 2.25 2.25
- Kitchen sink, domestic type 1.5 1.125 1.125
- Drinking fountain 0.5 0.5 (cold only) —
- Hose bibb 2.5 2.5 (cold only) —
- 2 flushometer water closets + 1 flushometer urinal 70 + 20 = 90 90 (cold only) —
- Segment Ledger
- Cold side
- Segment Serves Fixture units
- S1 building supply (meter to hose bibb tee) Everything 90 + 2 × 1.0 + 3.0 + 1.5 + 0.5 + 2.5 = 99.5
- HB hose bibb branch Hose bibb 2.5
- S2 (hose bibb tee to water heater tee) All but the hose bibb 90 + 2.0 + 3.0 + 1.5 + 0.5 = 97.0
S3 cold main to restroom Flushometers plus the cold side of the other fixtures 90 + (0.75 × 2 + 2.25 + 1.125 + 0.5) = 95.375
- S4 flushometer branch 2 WC + 1 UR 90
- S4a single water closet branch 1 WC 40
- S4b urinal branch 1 UR 20
- S5 cold branch to lavatories, sinks, fountain Cold side only 1.5 + 2.25 + 1.125 + 0.5 = 5.375
- S6 cold feed to water heater Hot side of the lavatories and sinks 1.5 + 2.25 + 1.125 = 4.875
- Hot side
- Segment Serves Fixture units
- H1 hot main Lavatories, mop sink, kitchen sink 4.875
- H2 hot to lavatories 2 lavatories 0.75 × 2 = 1.5
- H3 hot to sinks Mop sink and kitchen sink 2.25 + 1.125 = 3.375
- Why S2 is 97 and not 100.25
Upstream of the water heater tee, the pipe carries each fixture's combined hot and cold demand, and Table 610.3's listed value already represents that. Downstream of the split, each side is counted at 3/4. Adding the two sides back together (95.375 + 4.875 = 100.25) double-counts . Always use listed values for piping that carries both the hot and cold demand, such as the building supply and the main ahead of the heater.
Private Occupancy Example (A Quick Contrast)
A house has 2 tank water closets (2.5 each), 2 lavatories (1.0 each), 1 tub/shower (4.0), 1 shower (2.0), a kitchen sink (1.5), a dishwasher (1.5), a clothes washer (4.0), and 2 hose bibbs (2.5 + 1.0).
Building supply: 5.0 + 2.0 + 4.0 + 2.0 + 1.5 + 1.5 + 4.0 + 3.5 = 23.5 FU .
Hot main: 0.75 × (2 × 1.0 + 4.0 + 2.0 + 1.5 + 4.0) + dishwasher. A dishwasher is hot-only, so count its full 1.5 . That gives 0.75 × 13.5 + 1.5 = 10.125 + 1.5 = 11.625 FU .
A Quick Self-Check
Before moving on to sizing, confirm three things on your ledger:
Flushometer sections: every section serving flushometers uses Table 610.10's cumulative value for the valves downstream of that point . The branch past the first water closet serves one valve (40), and the branch serving both serves two (70).
Hot plus cold does not equal total. Downstream of the heater tee, the hot and cold sides are each 3/4 of listed values. Upstream, the listed total applies.
No fixture is missing. Count the fixtures on the drawing and compare with your ledger. A missed hose bibb or drinking fountain changes the building supply total.
Common Counting Errors
Treating each flushometer water closet as 40 on a section serving two. Two valves on one section = 70, not 80.
Using public values in a house, or private values in an office.
Forgetting the cold feed to the water heater , which carries the hot-side load.
Counting the second hose bibb at 2.5 on the shared main. It is 1.0 , but its own branch is still sized for 2.5.
Applying the 3/4 rule to the building supply . The building supply uses full listed values.