6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3)
Washington Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Administration, Licensing, & General Regulations
1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)
2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances
2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1
3 Chapter 3: Water Heaters & Storage Tanks
3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)
4 Chapter 4: Water Supply and Distribution Systems
4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)
5 Chapter 5: Backflow Prevention & Cross-Connection Control
5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)
6 Chapter 6: Sanitary Drainage Systems & Sizing
6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules
7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors
7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)
8 Chapter 8: Vents and Venting Fundamentals
8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)
9 Chapter 9: Vent Terminations, Traps, & Priming
9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)
10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards
10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)
11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis
11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations
12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing
12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4
13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics
13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)
14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy
14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist
6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3)
Key Takeaways Explain This Topic AI
In UPC Table 702.1, a 1.6 gpf water closet has a 3-inch minimum trap and carries 3 DFU private, 4 DFU public, and 6 DFU assembly.
A lavatory has a 1-1/4-inch minimum trap and 1.0 DFU; a bathtub or bath/shower has a 1-1/2-inch trap and 2.0 DFU; a single-head shower has a 2-inch trap and 2.0 DFU.
UPC Table 702.2(1) limits trap and trap arm loads to 1, 3, 4, 6, and 8 DFU for 1-1/4, 1-1/2, 2, 3, and 4-inch sizes.
Continuous flow from pumps, ejectors, or air-conditioning equipment counts 2 DFU per gallon per minute (UPC 702.3).
A battery of three or more clothes washers is rated at 6 DFU each when sizing common horizontal and vertical piping (Table 702.1 note 5).
Last updated: September 2026
What a Drainage Fixture Unit Represents
A drainage fixture unit (DFU) measures a fixture's probable load on the drainage system, based on its discharge rate, volume, and frequency of use. Section 702.1 says the unit values in Table 702.1 are based on the size of the trap required . Fixtures not listed are rated by their trap or trap arm size. You add DFUs along the direction of flow, then size each pipe from Table 703.2 (Section 6.3).
Occupancy columns: Private covers dwellings and private rooms, public covers general commercial use, and assembly covers public-use assembly occupancies. Public and assembly values are higher because those fixtures are used more often. Part 2 drawings state which column to use. When the drawing does not say, a single-family house is private.
Selected Rows of Table 702.1
- Fixture Min. trap and trap arm Private Public Assembly
- Bathtub or combination bath/shower 1-1/2 in 2.0 2.0 —
- Bidet 1-1/4 in 1.0 — —
- Clothes washer, domestic, standpipe 2 in 3.0 3.0 3.0
- Dishwasher, domestic, independent drain 1-1/2 in 2.0 2.0 2.0
- Drinking fountain or water cooler 1-1/4 in 0.5 0.5 1.0
- Floor drain 2 in 2.0 2.0 2.0
- Floor drain, emergency 2 in — 0.0 0.0
- Shower, single-head trap 2 in 2.0 2.0 2.0
- Shower, each additional head 2 in 1.0 1.0 1.0
- Lavatory 1-1/4 in 1.0 1.0 1.0
- Lavatories in sets 1-1/2 in 2.0 2.0 2.0
- Sink, kitchen, domestic (with or without disposer or dishwasher) 1-1/2 in 2.0 2.0 —
- Sink, laundry 1-1/2 in 2.0 2.0 2.0
- Sink, bar (private) 1-1/2 in 1.0 — —
- Sink, commercial with food waste 1-1/2 in — 3.0 3.0
- Sink, clinical 3 in — 6.0 6.0
- Service or mop basin 2 in — 3.0 3.0
- Service sink, flushing rim 3 in — 6.0 6.0
- Urinal, integral trap, 1.0 gpf 2 in 2.0 2.0 5.0
- Urinal, exposed trap 1-1/2 in 2.0 2.0 5.0
- Water closet, 1.6 gpf (gravity tank, flushometer tank, or flushometer valve) 3 in 3.0 4.0 6.0
- Water closet, over 1.6 gpf 3 in 4.0 6.0 8.0
- Mobile home trap 3 in 12.0 — —
- Table notes worth memorizing
Indirect waste receptors are sized by the total drainage capacity of the fixtures that drain into them, using Table 702.2(2).
Some fixtures (kitchen and laundry sinks, dishwashers, bar and special-purpose sinks, urinals) require a 2-inch minimum drain .
A battery of three or more clothes washers is rated at 6 DFU each when sizing common horizontal and vertical drainage piping.
Water closets count as 6 DFU when sizing septic tanks under Appendix H.
Trap sizes may not be increased to the point that the fixture discharge can no longer scour the trap.
Maximum Load on a Trap (Table 702.2(1))
- Trap and trap arm size Maximum DFU
- 1-1/4 in 1
- 1-1/2 in 3
- 2 in 4
- 3 in 6
- 4 in 8
The table does not apply to self-service laundries. It lets you rate an unlisted fixture from its trap size and check that a trap is not overloaded.
Converting Flow to DFU
Intermittent flow, Table 702.2(2) , applies to devices that discharge occasionally at a known rate:
- Discharge rate DFU
- Up to 7-1/2 gpm 1
- Over 7-1/2 to 15 gpm 2
- Over 15 to 30 gpm 4
- Over 30 to 50 gpm 6
Rates over 50 gpm are set by the AHJ.
Continuous flow (702.3): A pump, sump ejector, air-conditioning unit, or similar device discharging continuously counts 2 DFU per gpm . A 12 gpm continuous discharge therefore adds 24 DFU . Section 710.5 applies the same 2 DFU per gpm to building drains that receive pump or ejector discharge.
Worked Example: Totaling a Bathroom Group
A private bathroom has a 1.6 gpf water closet (3.0), a lavatory (1.0), and a bathtub/shower (2.0). Total: 6.0 DFU.
The same group in a public restroom (water closet, lavatory, and a public shower instead of a tub): 4.0 + 1.0 + 2.0 = 7.0 DFU .
A single-family house with two such private bathrooms, a kitchen sink (2.0), a dishwasher (2.0), a clothes washer (3.0), and a laundry sink (2.0): 6.0 + 6.0 + 2.0 + 2.0 + 3.0 + 2.0 = 21 DFU on the building drain.
Common Exam Traps
Lavatory trap 1-1/4 in, but shower trap 2 in. A shower is not a 1-1/2-inch fixture in the UPC.
Water closet DFU depends on the column. Private 3, public 4, assembly 6.
Kitchen sink with disposer and dishwasher on the same trap is still 2.0 DFU private. The row reads "with or without food waste disposer, dishwasher, or both." A dishwasher with its own independent drain adds 2.0.
Clothes washer standpipe trap is 2 inches. Standpipe height rules are in Chapter 8 (Section 7.3).