Study guide
6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4)
Washington Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Administration, Licensing, & General Regulations
1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)
2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances
2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1
3 Chapter 3: Water Heaters & Storage Tanks
3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)
4 Chapter 4: Water Supply and Distribution Systems
4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)
5 Chapter 5: Backflow Prevention & Cross-Connection Control
5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)
6 Chapter 6: Sanitary Drainage Systems & Sizing
6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules
7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors
7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)
8 Chapter 8: Vents and Venting Fundamentals
8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)
9 Chapter 9: Vent Terminations, Traps, & Priming
9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)
10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards
10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)
11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis
11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations
12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing
12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4
13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics
13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)
14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy
14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist
6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4)
Key Takeaways Explain This Topic AI
UPC Table 703.2 allows 3-inch drainage pipe to carry 48 DFU vertically and 35 DFU horizontally, and 4-inch pipe to carry 256 DFU vertically and 216 DFU horizontally.
No water closet may discharge into 2-inch drainage pipe (Table 703.2 note 3).
A 3-inch vertical drain may serve no more than four water closets, and a 3-inch horizontal drain no more than three (Table 703.2 note 4).
Washington's exception to note 4 allows four 1.6 gpf water closets on a 3-inch horizontal drain in a single-family addition or alteration when 4-inch is not readily available and the AHJ approves.
Horizontal Table 703.2 values assume 1/4 inch per foot; at 1/8 inch per foot, multiply the horizontal fixture units by 0.8 (Table 703.2 note 5).
Last updated: September 2026
The Table You Must Memorize
L&I states that Tables 702.1, 610.3, 610.4, and 610.10 are provided on the journey level exam, and Table 703.2 is not . Part 2 asks you to provide fixture units and pipe sizes for a waste and vent drawing using minimum sizing, so you need this table in your head.
UPC Table 703.2: Maximum Unit Loading and Maximum Length of Drainage and Vent Piping
- Pipe size (in) 1-1/4 1-1/2 2 3 4 5 6 8
- Drainage, vertical (max DFU) 1 2 16 48 256 600 1,380 3,600
- Drainage, horizontal (max DFU) 1 1 8 35 216 428 720 2,640
- Drainage, vertical max length (ft) 45 65 85 212 300 390 510 750
- Vent, max DFU (horizontal and vertical) 1 8 24 84 256 600 1,380 3,600
- Vent, max length (ft) 45 60 120 212 300 390 510 750
For 10-inch pipe, drainage is 5,600 vertical and 4,680 horizontal. For 12-inch, it is 8,400 vertical and 8,200 horizontal. Horizontal drainage length is unlimited.
The notes (where most exam questions come from)
Unit loadings exclude the trap arm ; trap arms are sized from Table 702.1 and Table 1002.2.
1-1/2-inch vertical (2 DFU): except sinks, urinals, and dishwashers, which may not exceed 1 fixture unit on this size.
2-inch pipe (16 vertical, 8 horizontal): except six-unit traps or water closets . No water closet may drain into 2-inch pipe.
3-inch pipe: only four water closets or six-unit traps on a vertical pipe or stack , and not more than three on a horizontal branch or drain .
Washington exception: In a single-family dwelling addition or alteration where a 4-inch horizontal waste is not readily available, four water closets not exceeding 1.6 gpf each may be allowed on a 3-inch horizontal waste when approved by the AHJ .
Horizontal values are based on 1/4 inch per foot slope. At 1/8 inch per foot , multiply horizontal fixture units by 0.8 .
Vent notes (used in Chapter 8): an individual vent is at least 1-1/4 inches and at least one-half the diameter of the drain it serves. No more than one-third of a vent's permitted length may be horizontal. Increasing a vent one pipe size for its entire length removes the length limits.
How to Size a Drain
Total the DFU entering each section of pipe, working downstream from the most remote fixture (Table 702.1).
Decide whether the section is vertical or horizontal. Horizontal limits are lower because the pipe runs partly full.
Pick the smallest size whose limit is equal to or greater than the load.
Apply the notes: check water closet counts (notes 3 and 4) and slope (note 5).
Check the trap and trap arm minimums from Table 702.1. A pipe can never be smaller than the trap it serves.
Do not reduce size in the direction of flow. A smaller pipe downstream retards the flow, which 310.5 prohibits, so a drain should never be smaller than any drain upstream of it.
Worked Examples
Example 1: Single-family house. Two private bathrooms (3 + 1 + 2 each), a kitchen sink (2), a dishwasher (2), a clothes washer (3), and a laundry sink (2) total 21 DFU , with 2 water closets.
Building drain (horizontal): 3 inches allows 35 DFU and up to 3 water closets. 3 inches works.
If the design grows to 4 water closets , note 4 forces a 4-inch horizontal drain. In Washington, the exception permits 3 inches only in a single-family addition or alteration, with 1.6 gpf closets, when 4-inch is not readily available and the AHJ approves.
Example 2: Commercial restroom branch. Public values: 6 water closets (6 × 4 = 24), 4 lavatories (4), 3 integral urinals (6), and 1 floor drain (2) total 36 DFU .
DFU alone: 3-inch horizontal allows only 35, so 36 already needs 4 inches .
Water closet count: 6 closets on a horizontal branch exceeds note 4's limit of three. 4 inches either way.
Example 3: Reduced slope. A 4-inch horizontal drain installed at 1/8 inch per foot (permitted for 4-inch and larger by 708.1 when the AHJ approves) carries at most 216 × 0.8 = 172.8, so 172 DFU .
Example 4: Stack. A three-story stack carrying 3 floors of private bathrooms (3 × 6 = 18 DFU, 3 water closets): 3-inch vertical allows 48 DFU and 4 water closets, and the stack height must stay within 212 feet . 3 inches works.
Vertical Length Limits
The "maximum length" rows limit how tall a vertical drain or vent of that size may be. A 2-inch vertical drain may be no taller than 85 feet , and a 2-inch vent no longer than 120 feet of developed length. Part 2 drawings rarely approach these limits, but Part 1 may ask for the number directly.
Memory Aids
"16-8, 48-35, 256-216" gives vertical and horizontal DFU for 2, 3, and 4-inch pipe.
"Two-inch: no toilets. Three-inch: 4 up, 3 across."
Vent DFU row: "1-8-24-84-256" for 1-1/4 through 4-inch. It matches the drainage vertical row from 4 inches up.