Study guide

6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2)

Washington Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Administration, Licensing, & General Regulations

1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)

2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances

2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1

3 Chapter 3: Water Heaters & Storage Tanks

3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)

4 Chapter 4: Water Supply and Distribution Systems

4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)

5 Chapter 5: Backflow Prevention & Cross-Connection Control

5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)

6 Chapter 6: Sanitary Drainage Systems & Sizing

6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules

7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors

7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)

8 Chapter 8: Vents and Venting Fundamentals

8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)

9 Chapter 9: Vent Terminations, Traps, & Priming

9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)

10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards

10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)

11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis

11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations

12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing

12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4

13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics

13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)

14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy

14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist

6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2)

Key Takeaways Explain This Topic AI

Washington's 701.2 keeps galvanized steel and 304 stainless steel drainage pipe at least 6 inches aboveground and vitrified clay at least 12 inches belowground.

Copper drainage and vent tube must weigh at least Type DWV (WA 701.2).

Horizontal-to-horizontal and vertical-to-horizontal connections must use 45-degree wyes, combination wye and one-eighth bends, or fittings of equivalent sweep (UPC 706.3, 706.4).

A double sanitary tee may be used only where its barrel is at least two pipe sizes larger than the largest inlet (UPC 706.2).

Caulked cast-iron joints need oakum or hemp and at least 1 inch of molten lead in one continuous pour (UPC 705.2.1).

Last updated: September 2026

Why Fittings and Materials Matter on Part 2

The Part 2 drawing shows DWV piping, fittings, and cleanouts. Knowing which fitting belongs at each change of direction, and which material may go underground, helps you spot the violations questions ask about (Section 11.4). Part 1 questions test the same rules directly.

Drainage Materials (Table 701.2 and Washington 701.2)

UPC Table 701.2 lists the approved materials and whether each may be used underground, aboveground, or for building sewers. Common entries include ABS and PVC Schedule 40 (solid and cellular core), co-extruded ABS and PVC, cast iron (ASTM A74, ASTM A888, CISPI 301), copper and copper-alloy Type DWV, galvanized steel and malleable iron, stainless steel 304 and 316L, polyethylene (building sewer), and vitrified clay (extra strength). Washington's amendment to 701.2 adds limits:

  • Washington 701.2 item Rule
  • 1 Galvanized wrought iron or galvanized steel: not underground; keep at least 6 inches aboveground

2 ABS and PVC: install per the referenced standards. Except in individual single-family dwellings, plastic exposed in ducts or plenums must have a flame-spread index of 25 or less and smoke-developed index of 50 or less (ASTM E84 or UL 723)

3 Vitrified clay: not aboveground or where pressurized by a pump or ejector; keep at least 12 inches belowground

  • 4 Copper: at least the weight of Type DWV
  • 5 Stainless steel 304: not underground; keep at least 6 inches aboveground

6 Cast iron: listed and tested to the referenced standards, and marked with the country of origin and original manufacturer

Other material rules:

701.4 Continuous wastes and tailpieces: Use drainage materials, but where exposed or accessible they may be seamless drawn brass at least No. 20 B&S gauge .

701.5 Sheet lead: at least 4 lb per sq ft for safe pans and 3 lb per sq ft for flashings. Lead bends and traps must be at least 1/8 inch thick.

701.3 Fittings: Drainage-type fittings, the same diameter as the pipe, with a smooth waterway, made to allow 1/4 inch per foot grade. Threaded pipe uses recessed drainage fittings, and burred ends are reamed.

Fixture Connections (UPC 704)

704.1: Drainage piping must have approved inlet fittings , located for the size and type of fixture to be connected.

704.2: Two fixtures set back-to-back or side-by-side , within the allowed trap-to-vent distance, may share a single vertical drain. Each must waste separately into an approved double fixture fitting with inlets at the same level.

704.3 (Washington amendment): Unless a fixture is specifically required to be indirect, or the AHJ approves otherwise, all fixtures, drains, appurtenances, and appliances must be directly connected to the drainage system.

Joints (UPC 705)

Joint Key rule

Caulked cast iron (705.2.1) Oakum or hemp, then molten lead at least 1 inch deep in one continuous pour , caulked tight; finished lead not more than 1/8 inch below the hub rim; no coatings until tested

Compression gasket, hub and spigot (705.2.2) ASTM C564 gasket; clean hub and spigot; spigot bottomed in the hub

Hubless shielded coupling (705.2.2) Pipe seated against the center stop; bands tightened with a calibrated torque wrench set for that coupling

ABS or PVC solvent cement (705.1.2, 705.5.2) Clean, square, deburred; PVC uses purple primer (ASTM F656) and ASTM D2564 cement

  • ABS to PVC (705.8.4) Listed transition solvent cement, ASTM D3138 , in building drains and sewers
  • Copper to cast iron (705.9.1) Listed compression joint or copper-alloy ferrule
  • Slip joints (705.8.1) Allowed only in fixture drains and traps , per their approval
  • Expansion joints (705.8.2) Must be accessible, except in vent piping or drainage stacks
  • Changes in Direction (UPC 706)

Section 706.1 requires changes in direction to use approved fittings with the angle of a 1/16 bend, 1/8 bend, or 1/6 bend , or fittings of equivalent sweep.

Change Allowed fittings

Horizontal to vertical (706.2) 45° wye, 60° wye, combination wye and 1/8 bend, sanitary tee or sanitary tapped tee , or equivalent sweep

Horizontal to horizontal (706.3) 45° wye, combination wye and 1/8 bend, or equivalent sweep

Vertical to horizontal (706.4) 45° wye, combination wye and 1/8 bend, or equivalent sweep. 60° branches or offsets allowed only when installed in a true vertical position

Multiple inlets at one level (706.2): No fitting with more than one inlet at the same level may be used unless it is built so discharge from one inlet cannot readily enter another. A double sanitary tee is permitted only when the barrel is at least two pipe sizes larger than the largest inlet . The recognized pipe sizes for this count are 2, 2-1/2, 3, 3-1/2, 4, 4-1/2, 5, 6 inches, and so on. For example, 2-inch inlets need at least a 3-inch barrel (2 to 2-1/2 is one size, and 3 is the second).

Why a sanitary tee is prohibited for horizontal-to-horizontal flow: its short-radius turn shoots water across the fitting and slows it, so solids settle and the line stops up. A wye with a 1/8 bend keeps the flow sweeping in the direction of travel.

Related Rules

310.1: No double hub, single or double tee branch, side inlet quarter bend, running thread, band, or saddle as a drainage fitting (Section 1.3).

310.3: No waste connection to a closet bend or water closet stub.

316.1: Use proper increasers and reducers between sizes.

711.1 Suds relief: Do not connect any drain within 8 feet of the base of a stack, at its vertical-to-horizontal change, if the stack carries suds-producing fixtures . Those fixtures are bathtubs, laundries, washer standpipes, kitchen sinks, and dishwashers. The rule does not apply to single-family residences or to stacks receiving discharge from fewer than three stories of fixtures.