13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure
Washington Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Administration, Licensing, & General Regulations
1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)
2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances
2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1
3 Chapter 3: Water Heaters & Storage Tanks
3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)
4 Chapter 4: Water Supply and Distribution Systems
4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)
5 Chapter 5: Backflow Prevention & Cross-Connection Control
5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)
6 Chapter 6: Sanitary Drainage Systems & Sizing
6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules
7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors
7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)
8 Chapter 8: Vents and Venting Fundamentals
8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)
9 Chapter 9: Vent Terminations, Traps, & Priming
9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)
10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards
10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)
11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis
11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations
12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing
12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4
13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics
13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)
14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy
14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist
13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure
Key Takeaways Explain This Topic AI
For a 45-degree offset, travel equals the offset times 1.414, and the run equals the offset; for 22-1/2 degrees the multiplier is 2.613 and for 60 degrees it is 1.155.
A rolling offset's true offset equals the square root of roll squared plus set squared; travel equals the true offset times the fitting multiplier.
Pipe capacity in gallons per foot equals 0.0408 times the inside diameter in inches squared, so 4-inch pipe holds about 0.65 gallon per foot.
Water weighs about 8.33 pounds per gallon and 62.4 pounds per cubic foot; 1 cubic foot holds about 7.48 gallons, and 1 gallon is 231 cubic inches.
Water exerts about 0.433 psi per foot of head, and 1 psi supports about 2.31 feet of water.
Last updated: September 2026
Calculator and Scratch Paper
The PSI bulletin allows silent, battery-operated, non-programmable calculators without paper tape or an alphabetic keyboard. PSI provides scratch paper and a pencil. Practice these formulas on a basic calculator so exam-day arithmetic is routine.
Offsets
An offset moves a pipe out of line and back to parallel. It forms a right triangle: the offset (also called set, or rise) is one leg, the run is the other leg, and the travel is the hypotenuse, measured center to center of the fittings.
- Fitting angle Travel = offset × Run = offset ×
- 60° 1.155 0.577
- 45° (1/8 bend) 1.414 1.000
- 30° 2.000 1.732
- 22-1/2° (1/16 bend) 2.613 2.414
- 11-1/4° (1/32 bend) 5.126 5.027
The multipliers are 1 ÷ sine of the angle (travel) and 1 ÷ tangent of the angle (run). To work backward, offset = travel ÷ multiplier. For 45 degrees, offset = travel × 0.707.
Example: A 45° offset must move a drain 18 inches. Travel = 18 × 1.414 = 25.45 inches center to center, and the run is also 18 inches.
Example: The same 18-inch offset with 22-1/2° fittings: travel = 18 × 2.613 = 47.03 inches , and run = 18 × 2.414 = 43.45 inches .
Rolling Offsets
A rolling offset moves the pipe both up (the set ) and over (the roll ).
True offset = square root of (roll² + set²).
Travel = true offset × the multiplier for the fitting angle.
Example: roll 12 inches, set 16 inches, 45° fittings. True offset = square root of (144 + 256) = square root of 400 = 20 inches . Travel = 20 × 1.414 = 28.28 inches .
With a calculator, you can also get travel as the square root of (roll² + set² + run²). Here the run equals the true offset for 45 degrees: square root of (144 + 256 + 400) = square root of 800 = 28.28 inches, which matches.
Cut Length
Travel is center to center of the fittings. To get the length of pipe to cut, subtract the fitting allowance (takeoff) of each fitting. The takeoff is the distance from the fitting's center to the point where the pipe end seats.
Cut length = center-to-center length − (takeoff of fitting 1 + takeoff of fitting 2).
For threaded pipe, add back the thread engagement. Takeoffs come from the manufacturer's dimensions for the specific fittings.
Example: 28.28-inch travel between two fittings with 1-1/4-inch takeoffs each: cut length = 28.28 − 2.5 = 25.78 inches (about 25-3/4 inches).
Drainage Grade
Fall = slope × length. At 1/4 inch per foot, 48 feet falls 12 inches . At 1/8 inch per foot, 48 feet falls 6 inches .
Percent grade = fall ÷ run × 100. A fall of 1/4 inch per foot is 0.25 ÷ 12 × 100 ≈ 2.08% , which the code calls 2 percent. A fall of 1/8 inch per foot is about 1% .
Trap arm check: a 1-1/2-inch arm at its 42-inch maximum falls 3.5 × 0.25 = 0.875 inch at 1/4 inch per foot.
Areas (for Aggregate Venting and Combination Waste and Vent)
Area = 0.7854 × d² (d is the inside diameter in inches).
- Size (in) 1-1/4 1-1/2 2 2-1/2 3 4 6
- Area (sq in) 1.23 1.77 3.14 4.91 7.07 12.57 28.27
Area grows with the square of the diameter. A 4-inch pipe has four times the area of a 2-inch pipe, not twice.
Volume and Weight
Pipe capacity: gallons per foot = 0.0408 × d² . For a 4-inch pipe: 0.0408 × 16 = 0.65 gallon per foot . A 50-foot, 4-inch drain holds about 32.6 gallons during a water test.
Cylinder (tank): volume in cubic inches = 0.7854 × d² × h. Divide by 231 for gallons. Alternatively, use cubic feet × 7.48 .
Example: a tank 18 inches in diameter and 48 inches tall holds 0.7854 × 324 × 48 = 12,215 cubic inches, and 12,215 ÷ 231 ≈ 52.9 gallons .
Weight: water is about 8.33 lb per gallon and 62.4 lb per cubic foot . A 52.9-gallon tank of water weighs about 441 lb, before the tank itself.
Grease interceptor capacity (Example 1014.2.1): length × width × depth in inches ÷ 231 = gallons, then × 0.75 fill factor.
Pressure and Head
Pressure (psi) = head (ft) × 0.433. A 10-foot water test head exerts about 4.33 psi at the bottom.
Head (ft) = psi × 2.31. A 60 psi main can lift water about 139 feet with no flow.
Table 610.4 method: use 1/2 psi per foot (610.8), not 0.433 (Section 12.3).
Temperature
°F = °C × 1.8 + 32 , and °C = (°F − 32) ÷ 1.8 . For example, 49°C = 120.2°F (the scald limit), 60°C = 140°F, and 43°C = 109.4°F.