3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)
Washington Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Administration, Licensing, & General Regulations
1.1 Washington Plumber Certification Law: RCW 18.106, WAC 296-400A, Trainees, & Supervision 1.2 Permits, Inspections, Tests, & Disinfection (UPC Chapter 1, 609, 712) 1.3 General Regulations: Prohibited Fittings, Pipe Protection, Nail Plates, Sleeves, & Trenching (UPC Chapter 3) 1.4 Hangers, Supports, Rod Sizes, Dissimilar Metals, & Expansion (UPC 313, Table 313.3)
2 Chapter 2: Plumbing Fixtures, Fittings, & Clearances
2.1 Fixture Setting, Clearances, Closet Flanges, & Water Closets (UPC 402, 411, 413; WA 402.5) 2.2 Showers, Shower Pans, Bathtubs, Lavatories, Bidets, & Scald Limits (UPC 407–410; WA 408) 2.3 Urinals, Floor Drains, Floor Sinks, Sinks, Dishwashers, Disposers, & Special Fixtures (UPC 412–421) 2.4 Minimum Fixture Counts in Washington: IBC Table 2902.1, Not UPC Table 422.1
3 Chapter 3: Water Heaters & Storage Tanks
3.1 Water Heater Permits, Sizing (WA Table 501.1), Bedroom and Bathroom Locations, & Safety Devices 3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5) 3.3 Water Heater Installation Details: Garages, Pans, Supports, Attic and Under-Floor Access, & Washington's Mechanical Code Deletions 3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)
4 Chapter 4: Water Supply and Distribution Systems
4.1 Water Piping Materials, Joints, Lead Limits, Under-Slab Rules, & Velocity (UPC 604, 605, 609, 610.12) 4.2 Water Supply Fixture Units & the Sizing Tables (UPC 610.3, 610.4, 610.8, 610.10) 4.3 Water Pressure Limits, Booster Pumps, Potable Water Tanks, & Water Hammer (UPC 607–609) 4.4 Water Valves, Shutoffs, Manifolds, & Hot Water Distribution (UPC 606, 609.11; WA 210.0 and 609.11)
5 Chapter 5: Backflow Prevention & Cross-Connection Control
5.1 Backflow Principles: Backsiphonage, Backpressure, & Degree of Hazard (UPC 602–603; WAC 246-290-490) 5.2 Backflow Assemblies and Devices: RP, DC, PVB, SVB, AVB, & Installation Rules (UPC 603.3, 603.4, Table 603.2) 5.3 Air Gaps, Critical Level, & Specific Backflow Applications (UPC Table 603.3.1, 603.5) 5.4 Backflow Testing, Certified Testers, & Washington's Cross-Connection Program (WA 603.4.2; WAC 246-290-490, 246-292)
6 Chapter 6: Sanitary Drainage Systems & Sizing
6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2) 6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3) 6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4) 6.4 Building Drains, Grade, Gravity Drainage, Backwater Valves, & Washington's Deletion of Building Sewer Rules
7 Chapter 7: Cleanouts, Sumps and Ejectors, Indirect Wastes, & Interceptors
7.1 Cleanouts: Location, Spacing, Size, and Clearance (UPC 707 as Amended by Washington) 7.2 Sumps, Sewage Ejectors, Grinder Pumps, & Macerating Systems (UPC 710) 7.3 Indirect Wastes, Air Gaps and Air Breaks, Receptors, Standpipes, & Condensate (UPC Chapter 8) 7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)
8 Chapter 8: Vents and Venting Fundamentals
8.1 Venting Fundamentals: Trap Seal Protection, Vent Sizing, the Half-Drain Rule, & Aggregate Venting (UPC 901–904) 8.2 Vent Grades and Connections, Vent Stacks, Relief and Yoke Vents, & Suds Relief (UPC 905, 907, 711) 8.3 Wet Venting and Circuit Venting (UPC 908, 911; WA 908.2.4 and 911.1) 8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)
9 Chapter 9: Vent Terminations, Traps, & Priming
9.1 Vent Terminations: Roof Height, Clearances, Used Roofs, Outdoor Vents, & Frost Closure (UPC 906) 9.2 Traps, Trap Arms, Table 1002.2 Distances, & Prohibited Traps (UPC 1001–1004) 9.3 How Trap Seals Are Lost & How the Code Protects Them: Venting, Seal Depth, and Trap Seal Primers (UPC 901.3, 1005, 1007)
10 Chapter 10: Alternate Water, Rainwater Catchment, Definitions, & Referenced Standards
10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington) 10.2 Nonpotable Rainwater Catchment Systems (UPC Chapter 16 as Amended by Washington) 10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)
11 Chapter 11: Part 2 — Waste & Vent Isometric Drawings & Plan Analysis
11.1 Part 2 Explained: Reading the Waste and Vent Drawing 11.2 Part 2 Worked Example: Accumulating DFU and Sizing Every Drain Segment 11.3 Part 2 Worked Example: Sizing Individual, Branch, and Main Vents and Checking Aggregate Venting 11.4 Spotting Code Violations on Waste and Vent Drawings: A Checklist with Code Citations
12 Chapter 12: Part 3 — Water Supply Isometric Drawings & Pipe Sizing
12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data 12.2 Part 3 Worked Example: Accumulating Water Supply Fixture Units, Cold and Hot 12.3 Part 3: Available Pressure, Elevation, Regulators, Device Losses, and the Length Column 12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4
13 Chapter 13: Washington Amendments Review, Plumbing Math, & Water Service Special Topics
13.1 Washington's Amendments to the 2015 UPC (WAC 51-56): A Consolidated Review 13.2 Plumbing Math for the Exam: Offsets, Rolling Offsets, Grade, Areas, Volumes, and Pressure 13.3 Water Service Details, Treatment Units, Softeners, & Residential Sprinklers (UPC 604, 609, 611, 612; WA Amendments)
14 Chapter 14: Comprehensive Exam Preparation & Test-Taking Strategy
14.1 The PSI Exam Day: Structure, Fees, Retakes, Rules, and Pacing 14.2 Using the Provided Tables Fast (702.1, 610.3, 610.4, 610.10) and Writing the Missing Ones from Memory 14.3 High-Yield Number Review, Classic Traps, and a Final Readiness Checklist
3.4 Seismic Strapping, Thermal Expansion Tanks, Pressure Regulators, & Temperature Controls (WA 507.2, 608.2, 608.3)
Key Takeaways Explain This Topic AI
Washington's 507.2 requires every water heater to be strapped within its upper and lower thirds, keeping at least 4 inches between the controls and the lower strap.
A water system closed by a check valve, backflow preventer, or other normally closed device needs a listed expansion tank on the building side (WA 608.3).
Instantaneous hot water systems installed per the manufacturer's instructions are exempt from Washington's expansion tank requirement in 608.3.
Where static pressure exceeds 80 psi, a pressure regulator with an upstream strainer must reduce it to 80 psi or less, and Table 610.4 sizing uses 80 percent of the reduced pressure (UPC 608.2).
An expansion tank is also required in the cold water piping downstream of each pressure regulator (UPC 608.2).
Last updated: September 2026
Seismic Strapping (Washington 507.2)
Unrestrained water heaters topple in earthquakes. That can break gas connections, start fires, and flood buildings. The unamended 2015 UPC requires strapping only in Seismic Design Categories C through F. Washington applies the rule to every water heater. Its amendment reads:
507.2 Seismic Provisions. Water heaters shall be anchored or strapped to resist horizontal displacement due to earthquake motion. Strappings shall be at points within the upper one-third and lower one-third of its vertical dimensions. At the lower point, a distance of not less than four (4) inches shall be maintained from the controls to the strapping .
What the rule means on the job:
Two strap zones: one strap in the upper third of the tank height and one in the lower third.
Control clearance: the lower strap must stay at least 4 inches away from the gas valve or thermostat , so the strap does not interfere with service or crush the controls.
Structure: anchor to framing or masonry that can resist the load. Listed strap kits give fastener sizes and must be installed per their instructions.
No height rule from the floor: Washington's text does not require the lower strap a specific distance above the floor. The measured requirement is the 4 inches from the controls.
Thermal Expansion in Closed Systems (Washington 608.3)
Heating water makes it expand, roughly 1 to 2 percent between typical cold supply and storage temperatures. For a 50-gallon tank, that is about half a gallon to nearly a gallon. In an open system , the extra volume pushes back through the meter into the main. In a closed system , the water cannot escape. Because water barely compresses, pressure climbs rapidly until the T&P valve weeps at 150 psi, and fill valves and connectors are stressed along the way.
Washington's 608.3 amendment:
A water system provided with a check valve, backflow preventer, or other normally closed device that prevents dissipation of building pressure back into the water main … shall be provided with an approved, listed, and adequately sized expansion tank or other approved device having a similar function to control thermal expansion. Such expansion tank … shall be installed on the building side of the check valve, backflow preventer, or other device and shall be sized and installed in accordance with the manufacturer's installation instructions.
Exception: Instantaneous hot water systems installed in accordance with the manufacturer's installation instructions.
Devices that create a closed system include:
- A purveyor's dual check or other backflow preventer at the meter
- A pressure regulator (PRV) ; UPC 608.2 requires an expansion tank downstream of every regulator
- A containment assembly (DC or RP) on the building service
- Any check valve on the building supply
- Installing the tank
Put the tank on the cold water side , on the building side of the closing device. It is usually near the heater's cold inlet.
Support the tank so its weight, full of water, does not hang on the piping.
Set the air pre-charge per the manufacturer's instructions . Typically that means matching the incoming static pressure or the regulator setting. A tank left at a factory charge below line pressure fills with water and loses much of its capacity.
Potable-water expansion tanks must comply with NSF 61 (608.2).
Pressure Regulators (UPC 608.1 and 608.2)
Condition Code response
Residual pressure below 15 psi after friction and other losses (608.1) Install a tank and pump or other means to provide at least 15 psi; provide more where fixtures require it
Static pressure over 80 psi (608.2) Install an approved pressure regulator preceded by a strainer and reduce static pressure to 80 psi or less
More 608.2 details that make good exam questions:
Regulators 1-1/2 inches and larger do not require a strainer.
The regulator and strainer must be accessible aboveground , or in a vault with a properly sized, sloped drain to daylight. They must be protected from freezing, and the strainer must be cleanable without removing the regulator or disconnecting the piping.
When sizing with Table 610.4 , base the pipe size on 80 percent of the reduced pressure . For example, with a regulator set at 70 psi, size using 56 psi, which falls in the 46–60 psi column.
An expansion tank must be installed in the cold water distribution piping downstream of each regulator . It prevents thermal expansion pressure and maintains the regulator setting.
Temperature Controls
504.5: Every water heater or hot water storage vessel needs overtemperature protection by an approved, listed device.
505.2 (Washington): A storage heater using energy other than gas needs an overtemperature safety device in addition to its primary temperature control, plus a combination T&P valve.
In practice, the primary thermostat maintains the setpoint. A high-limit energy cutoff (ECO) shuts off the burner or elements if the thermostat fails, before the T&P valve's temperature element (about 210°F) opens. Most ECOs require a manual reset, so a tripped ECO is a signal to find the failed control.
507.1: The AHJ may require a dielectric insulator on the heater's water connections.
Exam trap: The expansion tank goes on the building side of the check valve or regulator. A tank installed on the street side of the device cannot absorb expansion that is trapped inside the building.