Study guide
2.2 Ventilation Design (A03), Enhanced Ventilation Design (A06) & Air Quality Monitoring (A08)
WELL Accredited Professional WELL AP
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: WELL Certification Process, Project Typologies & Scoring
1.1 The WELL Building Standard & Project Typologies 1.2 The WELL Certification Journey & Documentation 1.3 Scoring Rules, Preconditions & Certification Levels 1.4 Performance Verification, On-Site Testing & Recertification 1.5 Precertification, Mid-Cycle Reviews & the WELL Ratings Family 1.6 WELL Portfolio & WELL at Scale: Scope, Documentation Scales & Score
2 Chapter 2: Air — Indoor Air Quality, Ventilation, Filtration & Contaminant Control
2.1 Air Quality Thresholds (A01) & Smoke-Free Environments (A02) 2.2 Ventilation Design (A03), Enhanced Ventilation Design (A06) & Air Quality Monitoring (A08) 2.3 Construction Pollution Management (A04), Pollution Infiltration (A09) & Air Filtration (A12) 2.4 Enhanced Air Quality (A05), Enhanced Supply Air (A13) & Microbe and Mold Control (A14) 2.5 Operable Windows (A07), Combustion Minimization (A10) & Source Separation (A11)
3 Chapter 3: Water — Quality Thresholds, Legionella Management, Moisture & Hygiene
3.1 Water Quality Indicators (W01) & Drinking Water Quality (W02) 3.2 Basic Water Management (W03): Ongoing Monitoring & Legionella Plans 3.3 Enhanced Water Quality (W04), Drinking Water Quality Management (W05) & Drinking Water Promotion (W06) 3.4 Moisture Management (W07) & Hygiene Support (W08)
4 Chapter 4: Nourishment — Availability, Transparency, Portioning & Sourcing
4.1 Fruits and Vegetables (N01) & Nutritional Transparency (N02) 4.2 Refined Ingredients (N03), Food Advertising (N04), Artificial Ingredients (N05) & Portion Sizes (N06) 4.3 Nutrition Education (N07), Mindful Eating (N08) & Food Preparation (N10) 4.4 Special Diets (N09), Responsible Food Sourcing (N11), Food Production (N12) & Local Food Environment (N13)
5 Chapter 5: Light — Light Exposure, Visual Acuity, Circadian Design & Daylight
5.1 Light Exposure (L01) & Visual Lighting Design (L02) 5.2 Circadian Lighting Design (L03): EML, M-EDI and the Enhanced Daylight Trade 5.3 Electric Light Glare Control (L04), Visual Balance (L07) & Electric Light Quality (L08) 5.4 Daylight Design Strategies (L05), Daylight Simulation (L06) & Occupant Lighting Control (L09)
6 Chapter 6: Movement — Active Design, Ergonomics, Site Selection & Activity Programs
6.1 Active Buildings and Communities (V01) & Circulation Network (V03) 6.2 Ergonomic Workstation Design (V02), Active Furnishings (V07) & Self-Monitoring (V10) 6.3 Physical Activity Opportunities (V06), Spaces and Equipment (V08) & Promotion (V09) 6.4 Facilities for Active Occupants (V04) & Site Planning and Selection (V05)
7 Chapter 7: Thermal Comfort — Performance, Zoning, Individual Control & Humidity
7.1 Thermal Performance (T01) & Verified Thermal Comfort (T02) 7.2 Thermal Zoning (T03), Radiant Thermal Comfort (T05) & Thermal Comfort Monitoring (T06) 7.3 Individual Thermal Control (T04) & Humidity Control (T07)
8 Chapter 8: Sound — Acoustic Zoning, Noise Limits, Isolation & Masking
8.1 Sound Mapping (S01) & Maximum Noise Levels (S02) 8.2 Sound Barriers (S03) & Minimum Background Sound (S06) 8.3 Reverberation Time (S04) & Sound Reducing Surfaces (S05)
9 Chapter 9: Materials — Restrictions, Hazard Management, VOCs, Transparency & Cleaning
9.1 Material Restrictions (X01) & Enhanced Material Restrictions (X05) 9.2 Interior Hazardous Materials Management (X02), CCA and Lead Management (X03) & Site Remediation (X04) 9.3 VOC Restrictions (X06), Materials Transparency (X07) & Materials Optimization (X08) 9.4 Waste Management (X09), Pest Management and Pesticide Use (X10) & Cleaning Products and Protocols (X11)
10 Chapter 10: Mind — Mental Health, Nature and Place, Restoration & Substance Use
10.1 Mental Health Promotion (M01), Services (M03) & Education (M04) 10.2 Nature and Place (M02) & Enhanced Access to Nature (M09) 10.3 Restorative Opportunities (M06), Restorative Spaces (M07) & Restorative Programming (M08) 10.4 Stress Management (M05), Tobacco Cessation (M10) & Substance Use Services (M11)
11 Chapter 11: Community — Health Promotion, Integrative Design, Emergency Preparedness & Equity
11.1 Health and Wellness Promotion (C01), Integrative Design (C02) & Enhanced Promotion (C07) 11.2 Emergency Preparedness (C03) & Emergency Resources (C14) 11.3 Occupant Survey (C04), Enhanced Occupant Survey (C05) & Diversity and Inclusion (C12) 11.4 Health Services and Benefits (C06), New Parent Support (C08), New Mother Support (C09), Family Support (C10), Civic Engagement (C11) & Accessibility (C13)
12 Chapter 12: Innovation, WELL Core Applicability & Exam Strategy
12.1 Innovation Features (I01–I05), Alternative Adherence Paths & Equivalencies 12.2 WELL Core Applicability, Multifamily Residential & Sector-Specific Space Types 12.3 WELL AP Exam Mastery: Format, Domain Weights, Embedded Content & Test-Day Strategy
2.2 Ventilation Design (A03), Enhanced Ventilation Design (A06) & Air Quality Monitoring (A08)
Key Takeaways Explain This Topic AI
A03 Ventilation Design is a precondition; mechanically ventilated projects meet ASHRAE 62.1-2010 or newer, ASHRAE 62.2-2016, EN 16798-1 for Category IV buildings, AS 1668.2-2012 or newer, or CIBSE Guide A 2007 or newer, covering at least 90% of project area.
Naturally ventilated projects under A03 must also show annual average outdoor air below 15 ug/m3 PM2.5 and 30 ug/m3 PM10; the elevated-particulate option allows PM2.5 under 35 and PM10 under 70 but caps the project at Silver.
Mixed-mode projects must switch to mechanical ventilation whenever outdoor PM2.5 exceeds 15 ug/m3, measured at a device within 2.5 mi (4 km) of the project.
A06 Enhanced Ventilation Design is worth 3 points for WELL Certification and 5 for WELL Core; Part 1 awards points for exceeding ASHRAE 62.1-2010 outdoor air rates by 30% or 60%, or for demand-controlled ventilation holding CO2 below 900 ppm or 750 ppm.
A08 Part 1 requires monitors measuring at least three listed parameters at a density of at least one sensor per 3,500 ft2 (325 m2), sampling CO2 at least every 10 minutes and other pollutants at least hourly.
Last updated: September 2026
2.2 Ventilation Design (A03), Enhanced Ventilation Design (A06) & Air Quality Monitoring (A08)
Core Exam Takeaway: Get the feature numbering right — A03 Ventilation Design is the precondition, A06 Enhanced Ventilation Design is the 30%/60% and demand-controlled-ventilation optimization (3 pt WELL Certification / 5 pt WELL Core), and A08 Air Quality Monitoring and Awareness is the sensing-and-display optimization (2 pt / 1.5 pt). A05 is Enhanced Air Quality , not enhanced ventilation — a distinction candidates lose points on constantly.
Ventilation is the process of introducing outdoor air while displacing stale indoor air. A03's engineering premise is that adequate dilution prevents accumulation of metabolic C O 2 CO_2 C O 2 , human bioeffluents, moisture and background emissions.
Feature A03: Ventilation Design — Precondition +-----------------------------------------------------------------------------+
- | ASHRAE 62.1 VENTILATION RATE PROCEDURE |
- | |
- | V_bz = (R_p * P_z) + (R_a * A_z) |
- | V_ot = V_bz / E_z |
- | |
- | V_bz = Breathing zone outdoor airflow rate (cfm or L/s) |
- | R_p = Outdoor airflow rate required per person (cfm/person) |
- | P_z = Zone population (number of occupants) |
- | R_a = Outdoor airflow rate required per unit floor area (cfm/sq ft) |
- | A_z = Zone floor area (sq ft) |
- | E_z = Zone air distribution effectiveness factor |
- | V_ot = Outdoor air intake flow rate delivered to terminal zone |
- +-----------------------------------------------------------------------------+
- A03 Part 1 Option 1 — Mechanically ventilated spaces
One of the following, and note that the chosen guideline must describe ventilation rates for at least 90% of the project area :
(a) Newly installed systems designed to meet the supply and exhaust rates of one or more of:
- ASHRAE 62.1-2010 or any more recent version (Ventilation Rate Procedure or IAQ Procedure)
- ASHRAE 62.2-2016 (the residential standard)
- EN 16798-1 — for Category IV buildings
- AS 1668.2-2012 or any more recent version
- CIBSE Guide A: Environmental Design, 2007 or any more recent version
The system must be scheduled to be tested and balanced after project occupancy .
(b) Existing systems that have been tested and balanced within the last five years to meet the rates in one of the guidelines above.
Warning
Two traps here. First, EN 16798-1 is accepted for Category IV buildings — not Category I or II. Second, WELL sets no numeric air-balance tolerance such as "within ±10% of design"; it requires that balancing be scheduled (new systems) or performed within five years (existing systems). Do not invent a tolerance.
Compliance methodologies within ASHRAE 62.1.
Ventilation Rate Procedure (VRP): prescriptive mass-flow calculation summing the people component ( R p × P z R_p \times P_z R p × P z ) and the area component ( R a × A z R_a \times A_z R a × A z ), then adjusting by Zone Air Distribution Effectiveness ( E z E_z E z ) — ceiling supply of cool air with ceiling return E z = 1.0 E_z = 1.0 E z = 1.0 ; warm air supplied from ceiling diffusers E z = 0.8 E_z = 0.8 E z = 0.8 (buoyant warm air short-circuits to the return); underfloor or displacement supply of cool air at floor level E z = 1.2 E_z = 1.2 E z = 1.2 .
Indoor Air Quality Procedure (IAQP): performance-based mass-balance approach using contaminant emission rates, sensory evaluation and air cleaning.
A03 Part 1 Option 2 — Naturally ventilated spaces (no mechanical ventilation)
(a) Use one or more design criteria covering at least 90% of project area : the Natural Ventilation Procedure in ASHRAE 62.1-2010 or newer ; CIBSE AM10 (2005 or newer), Section 2.4 and Chapter 4; AS 1668.4-2012 or newer ; or any Option 1 reference that describes natural ventilation procedures.
(b) Vents and windows used in the ventilation calculations must be permanently open or have controls preventing closure during occupancy . Operable windows not used in the calculations may be user-operated.
(c) Outdoor air must meet, as an average for the previous year: P M 2.5 < 15 μ g/m 3 PM_{2.5} < 15\ \mu\text{g/m}^3 P M 2.5 < 15 μ g/m 3 and P M 10 < 30 μ g/m 3 PM_{10} < 30\ \mu\text{g/m}^3 P M 10 < 30 μ g/m 3 .
A03 Part 1 Option 3 — Naturally ventilated spaces in elevated-particulate areas
Same design criteria and window-control rules, but the outdoor air thresholds relax to P M 2.5 < 35 μ g/m 3 PM_{2.5} < 35\ \mu\text{g/m}^3 P M 2.5 < 35 μ g/m 3 and P M 10 < 70 μ g/m 3 PM_{10} < 70\ \mu\text{g/m}^3 P M 10 < 70 μ g/m 3 — and the project is limited to Silver regardless of total points achieved.
The mixed-mode rule (high-yield)
Mixed-mode projects must meet the natural-ventilation requirements when the mechanical system is off and the mechanical requirements when it is on. Critically: the project must use mechanical ventilation whenever outdoor P M 2.5 PM_{2.5} P M 2.5 exceeds 15 μ g/m 3 15\ \mu\text{g/m}^3 15 μ g/m 3 , based on a measuring device within 2.5 mi (4 km) of the project.
WELL Core guidance: meet A03 in the whole building. A mechanical or mixed-mode project must provide leased spaces with sufficient outdoor air but is not required to install ducts and diffusers within leased spaces .
Feature A06: Enhanced Ventilation Design — Optimization (3 pt / WELL Core 5 pt)
A06's premise is that codes deliver merely "acceptable" air. WELL cites research that airflow significantly exceeding standards is needed to minimize SBS symptoms, and that SBS risk drops significantly when C O 2 CO_2 C O 2 stays under about 800 ppm — which is why the compliance thresholds sit where they do, not what they are.
A06 Part 1 — Increase Outdoor Air Supply (2 pt / Core 3 pt)
Option Requirement Points (WELL Core in parentheses)
Option 1: Increased air supply (mechanically ventilated, all occupiable spaces) Exceed ASHRAE 62.1-2010 outdoor air supply rates by 30% 1 (2)
Exceed them by 60% 2 (3)
Option 2: Demand control ventilation (mechanically ventilated, ≥90% of regularly occupied spaces) DCV holds C O 2 CO_2 C O 2 below 900 ppm or 500 ppm above outdoor levels at maximum intended occupancy 1 (2)
DCV holds C O 2 CO_2 C O 2 below 750 ppm or 350 ppm above outdoor levels 2 (3)
Option 3: Enhanced natural ventilation (naturally ventilated) Engineered natural ventilation keeps breathing-zone C O 2 CO_2 C O 2 below the same 900/500 or 750/350 thresholds in all regularly occupied spaces 1 (2) / 2 (3)
C O 2 CO_2 C O 2 sensor placement rules (Option 2b): measure at return air diffusers or in the breathing zone at least 3.3 ft (1 m) away from doors, windows, air supply diffusers or occupants. At least one sensor per occupancy zone (or per air handling unit where multiple AHUs serve one zone). Adjacent areas with substantially different occupancy density, pattern or usage count as separate zones .
Warning
800 ppm is not a WELL v2 compliance threshold. It appears in A06's research narrative. The scored thresholds are 900/750 ppm absolute or 500/350 ppm above outdoor . Mixed-mode projects select the option matching whichever ventilation mode operates for the majority of annual operating hours.
A06 Part 2 — Improve Ventilation Effectiveness (1 pt / Core 2 pt)
Use a displacement ventilation system in at least 90% of regularly occupied spaces , designed on the basis of ASHRAE Guidelines RP-949 , ASHRAE 62.1-2019 "Stratified Air Distribution Systems" (Section 6.2.1.2.1) , or REHVA Guidebook No. 01 (Displacement Ventilation in non-industrial premises) . Displacement ventilation delivers fresh air at floor level and lets warmer, polluted air — including exhaled C O 2 CO_2 C O 2 — be extracted above the ventilation zone. OUTDOOR AIR DELIVERY (A06 Part 1 Option 1, relative to ASHRAE 62.1-2010)
- ASHRAE 62.1-2010 baseline: [==========] 100% (A03 precondition)
- +30% enhanced rate: [=============] 130% (A06: 1 pt / Core 2 pt)
- +60% enhanced rate: [================] 160% (A06: 2 pt / Core 3 pt)
- Feature A08: Air Quality Monitoring and Awareness — Optimization (2 pt / WELL Core 1.5 pt)
- A08 Part 1 — Install Indoor Air Monitors (1 pt / Core 0.5 pt)
Option 1 — Sensor requirements. Deploy monitors measuring at least three of the following, at the stated accuracies:
- Parameter Required accuracy
- PM2.5 or PM10 25% at 50 µg/m³
- Carbon dioxide 10% at 750 ppm
- Carbon monoxide 1 ppm at values between 0 and 10 ppm
- Ozone 10 ppb at values between 0 and 100 ppb
- Nitrogen dioxide 20 ppb at values between 0 and 100 ppb
- Total VOCs 25% at 500 µg/m³
- Formaldehyde 20 ppb at values between 0 and 100 ppb
Siting and density: monitors sited per the Performance Verification Guidebook , at a density of at least one sensor per 3,500 ft² (325 m²) .
Sampling intervals: no longer than 10 minutes for carbon dioxide and no longer than one hour for other pollutants .
Option 2 — Reporting and maintenance. Data submitted annually through the WELL digital platform, and monitors recalibrated or replaced annually with documentation submitted annually.
A08 Part 2 — Promote Air Quality Awareness (1 pt / Core 1 pt)
Only claimable if Part 1 is also achieved. Make the Part 1 data available to occupants:
(a) Either display screens positioned at a height of 3.6–5.6 ft (1.1–1.7 m) with at least one display per 3,500 ft² (325 m²) of regularly occupied space, or hosting on a website or phone application accessible to occupants with signs at least one per 3,500 ft² (325 m²) indicating where the data may be accessed.
(b) The data presented must include either the measured concentrations or qualitative results such as color-coded levels.
WELL Core guidance: meet A08 in non-leased spaces; an additional point is available for also measuring environmental parameters in all leased spaces. Data displays must be in tenant-accessible areas or otherwise made available to tenants.
Tip
The 3,500 ft² (325 m²) module recurs three times in the Air concept — A01 Part 2 Option 2 VOC sensor density, A08 Part 1 monitor density, and A08 Part 2 display or sign density. Learn it once, use it three times. Note the 3.6–5.6 ft (1.1–1.7 m) height applies to A08 Part 2 display screens , not to the sensors themselves; sensor siting defers to the Performance Verification Guidebook.