Study guide

5.3 Electric Light Glare Control (L04), Visual Balance (L07) & Electric Light Quality (L08)

WELL Accredited Professional WELL AP

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: WELL Certification Process, Project Typologies & Scoring

1.1 The WELL Building Standard & Project Typologies 1.2 The WELL Certification Journey & Documentation 1.3 Scoring Rules, Preconditions & Certification Levels 1.4 Performance Verification, On-Site Testing & Recertification 1.5 Precertification, Mid-Cycle Reviews & the WELL Ratings Family 1.6 WELL Portfolio & WELL at Scale: Scope, Documentation Scales & Score

2 Chapter 2: Air — Indoor Air Quality, Ventilation, Filtration & Contaminant Control

2.1 Air Quality Thresholds (A01) & Smoke-Free Environments (A02) 2.2 Ventilation Design (A03), Enhanced Ventilation Design (A06) & Air Quality Monitoring (A08) 2.3 Construction Pollution Management (A04), Pollution Infiltration (A09) & Air Filtration (A12) 2.4 Enhanced Air Quality (A05), Enhanced Supply Air (A13) & Microbe and Mold Control (A14) 2.5 Operable Windows (A07), Combustion Minimization (A10) & Source Separation (A11)

3 Chapter 3: Water — Quality Thresholds, Legionella Management, Moisture & Hygiene

3.1 Water Quality Indicators (W01) & Drinking Water Quality (W02) 3.2 Basic Water Management (W03): Ongoing Monitoring & Legionella Plans 3.3 Enhanced Water Quality (W04), Drinking Water Quality Management (W05) & Drinking Water Promotion (W06) 3.4 Moisture Management (W07) & Hygiene Support (W08)

4 Chapter 4: Nourishment — Availability, Transparency, Portioning & Sourcing

4.1 Fruits and Vegetables (N01) & Nutritional Transparency (N02) 4.2 Refined Ingredients (N03), Food Advertising (N04), Artificial Ingredients (N05) & Portion Sizes (N06) 4.3 Nutrition Education (N07), Mindful Eating (N08) & Food Preparation (N10) 4.4 Special Diets (N09), Responsible Food Sourcing (N11), Food Production (N12) & Local Food Environment (N13)

5 Chapter 5: Light — Light Exposure, Visual Acuity, Circadian Design & Daylight

5.1 Light Exposure (L01) & Visual Lighting Design (L02) 5.2 Circadian Lighting Design (L03): EML, M-EDI and the Enhanced Daylight Trade 5.3 Electric Light Glare Control (L04), Visual Balance (L07) & Electric Light Quality (L08) 5.4 Daylight Design Strategies (L05), Daylight Simulation (L06) & Occupant Lighting Control (L09)

6 Chapter 6: Movement — Active Design, Ergonomics, Site Selection & Activity Programs

6.1 Active Buildings and Communities (V01) & Circulation Network (V03) 6.2 Ergonomic Workstation Design (V02), Active Furnishings (V07) & Self-Monitoring (V10) 6.3 Physical Activity Opportunities (V06), Spaces and Equipment (V08) & Promotion (V09) 6.4 Facilities for Active Occupants (V04) & Site Planning and Selection (V05)

7 Chapter 7: Thermal Comfort — Performance, Zoning, Individual Control & Humidity

7.1 Thermal Performance (T01) & Verified Thermal Comfort (T02) 7.2 Thermal Zoning (T03), Radiant Thermal Comfort (T05) & Thermal Comfort Monitoring (T06) 7.3 Individual Thermal Control (T04) & Humidity Control (T07)

8 Chapter 8: Sound — Acoustic Zoning, Noise Limits, Isolation & Masking

8.1 Sound Mapping (S01) & Maximum Noise Levels (S02) 8.2 Sound Barriers (S03) & Minimum Background Sound (S06) 8.3 Reverberation Time (S04) & Sound Reducing Surfaces (S05)

9 Chapter 9: Materials — Restrictions, Hazard Management, VOCs, Transparency & Cleaning

9.1 Material Restrictions (X01) & Enhanced Material Restrictions (X05) 9.2 Interior Hazardous Materials Management (X02), CCA and Lead Management (X03) & Site Remediation (X04) 9.3 VOC Restrictions (X06), Materials Transparency (X07) & Materials Optimization (X08) 9.4 Waste Management (X09), Pest Management and Pesticide Use (X10) & Cleaning Products and Protocols (X11)

10 Chapter 10: Mind — Mental Health, Nature and Place, Restoration & Substance Use

10.1 Mental Health Promotion (M01), Services (M03) & Education (M04) 10.2 Nature and Place (M02) & Enhanced Access to Nature (M09) 10.3 Restorative Opportunities (M06), Restorative Spaces (M07) & Restorative Programming (M08) 10.4 Stress Management (M05), Tobacco Cessation (M10) & Substance Use Services (M11)

11 Chapter 11: Community — Health Promotion, Integrative Design, Emergency Preparedness & Equity

11.1 Health and Wellness Promotion (C01), Integrative Design (C02) & Enhanced Promotion (C07) 11.2 Emergency Preparedness (C03) & Emergency Resources (C14) 11.3 Occupant Survey (C04), Enhanced Occupant Survey (C05) & Diversity and Inclusion (C12) 11.4 Health Services and Benefits (C06), New Parent Support (C08), New Mother Support (C09), Family Support (C10), Civic Engagement (C11) & Accessibility (C13)

12 Chapter 12: Innovation, WELL Core Applicability & Exam Strategy

12.1 Innovation Features (I01–I05), Alternative Adherence Paths & Equivalencies 12.2 WELL Core Applicability, Multifamily Residential & Sector-Specific Space Types 12.3 WELL AP Exam Mastery: Format, Domain Weights, Embedded Content & Test-Day Strategy

5.3 Electric Light Glare Control (L04), Visual Balance (L07) & Electric Light Quality (L08)

Key Takeaways Explain This Topic AI

L04 Electric Light Glare Control is worth 2 points and is met either per luminaire or across the space, using a Unified Glare Rating of 16 or lower for most spaces and 19 or lower for industrial spaces.

L04 luminaire options also accept 100% of light emitted above the horizontal plane, or luminance not exceeding 6,000 cd/m2 at any angle between 45 and 90 degrees from nadir.

L07 Visual Balance requires at least three of four parameters: luminance contrast ratio no more than 10 between adjacent controlled zones, illuminance uniformity of at least 0.4, automatic lighting changes over 10 minutes, and CCT consistency within plus or minus 200 K.

L08 Part 1 requires color rendering of CRI at or above 90, or CRI at or above 80 with R9 at or above 50, or the IES TM-30 combination; circulation areas need only CRI at or above 80.

L08 Part 2 manages flicker through California Title 24 reduced flicker operation, IEEE 1789-2015 recommended practices 1 to 3, or NEMA 77-2017 limits of Pst LM at or below 1.0 and SVM at or below 1.6.

Last updated: September 2026

5.3 Electric Light Glare Control (L04), Visual Balance (L07) & Electric Light Quality (L08)

Core Exam Takeaway: These three features are about light quality . L04 (2 pt / Core 1 pt) = UGR ≤ 16 , relaxed to UGR ≤ 19 for industrial . L07 (1 pt / Core 0.5 pt) = at least three of four balance parameters. L08 (3 pt / Core 1.5 pt) = colour rendering (1 pt) plus flicker (2 pt) . Note the numbering: L07 is Visual Balance , not "Visual Balance & Surface Reflectance," and it is not L05.

Feature L04: Electric Light Glare Control — Optimization (2 pt / WELL Core 1 pt)

Intent: minimize glare caused by electric light.

L04 Part 1 — Manage Glare from Electric Lighting

For all spaces except industrial. Each luminaire meets one of the following for regularly occupied spaces, at light output representative of regular use conditions :

Option 1: Luminaire considerations

(a) 100% of light is emitted above the horizontal plane (i.e., fully indirect).

(b) Classified with Unified Glare Rating (UGR) of 16 or lower .

(c) Luminance that does not exceed 6,000 cd/m² at any angle between 45 and 90 degrees from nadir.

Option 2: Space considerations — UGR of 16 or lower in all regularly occupied spaces .

For industrial spaces , the same structure with a relaxed limit:

Option 1: meets the all-spaces requirements above, or UGR of 19 or lower .

Option 2: UGR of 19 or lower in all regularly occupied spaces.

Exclusions: wall wash fixtures and concealed fixtures installed as specified by manufacturer's data, as well as decorative fixtures , may be excluded from meeting the luminaire requirements.

WELL Core guidance: non-leased spaces; an additional point for also meeting requirements in leased spaces.

Tip

The distinction between Option 1 and Option 2 is per-fixture versus per-space compliance. Option 1 lets a specifier prove each luminaire's data sheet meets a limit; Option 2 requires a calculated UGR for the room , which accounts for geometry, surface reflectances and observer position. Option 2 is harder to document but forgiving of individual fixture choices.

Important

Nadir is straight down. The 45°–90° from nadir band in Option 1(c) is precisely the angular zone a seated occupant's eye sweeps when looking across a room — which is why the luminance cap applies there and not at nadir, where the fixture is above the line of sight.

Feature L07: Visual Balance — Optimization (1 pt / WELL Core 0.5 pt)

Intent: create lighting environments that enhance visual comfort.

L07 Part 1 — Balance Visual Lighting

Option 1: Parameters for visual balance. Ambient lighting in all regularly occupied spaces meets at least three of the following four :

(a) Horizontal and vertical luminance contrast ratios for an ambient light system are no more than 10 between adjacent independently controlled zones .

(b) Illuminance uniformity ratio of at least 0.4, or 1:2.5 (minimum light level : average light level), on any horizontal task plane within a space.

(c) Automatic changes in lighting characteristics — light levels, changes in colour and distribution — take place over a period of 10 minutes .

(d) The Correlated Colour Temperature (CCT) in each room for similar fixtures is consistent (± 200 K) at any point in time.

Option 2: Design for visual balance. Lighting is designed by a lighting professional and takes into account: luminance ratios on vertical and horizontal adjacent zones; illuminance uniformity on horizontal task planes; changes in lighting characteristics; and colour temperature of lights used.

Tip

Requirement (c) is the least intuitive and therefore the most examinable: automatic changes spread over 10 minutes . Abrupt transitions in a tunable or daylight-responsive system read as flicker or failure and provoke complaints; a ten-minute ramp falls below the threshold of conscious notice. Requirement (d)'s ± 200 K is a within-room consistency rule — it does not prescribe a colour temperature, only that similar fixtures agree.

Tip

Option 2 is the pragmatic route: engaging a lighting professional who documents consideration of all four topics earns the point without hitting any numeric threshold. That mirrors a pattern across WELL — a performance option and a qualified-professional option for the same outcome.

Feature L08: Electric Light Quality — Optimization (3 pt / WELL Core 1.5 pt)

Intent: enhance visual comfort and minimize flicker .

L08 Part 1 — Enhance Colour Rendering Quality (1 pt / Core 0.5 pt)

For all spaces except circulation areas. All luminaires — except decorative fixtures, emergency lights and other special-purpose lighting — meet at least one of:

  • (a) CRI ≥ 90
  • (b) CRI ≥ 80 with R9 ≥ 50
  • (c) IES Rf ≥ 78, IES Rg ≥ 100, and −1% ≤ IES Rcs,h1 ≤ 15%

If tunable white lighting is used , the requirements are met at 1,000 K intervals from the lower end (minimum 2,700 K) to the higher end (maximum 5,000 K) .

For circulation areas — a relaxed tier. Meet at least one of:

  • (a) CRI ≥ 80
  • (b) IES Rf ≥ 75, IES Rg ≥ 95, and −7% ≤ IES Rcs,h1 ≤ 15%
  • L08 Part 2 — Manage Flicker (2 pt / Core 1 pt)

All luminaires in combination with the appropriate controls — except decorative, emergency and other special-purpose lighting — used in regularly occupied spaces meet at least one of:

(a) Classified as "reduced flicker operation" per California Title 24 , tested per Joint Appendix JA-10 .

(b) Recommended practices 1, 2 or 3 as defined by IEEE standard 1789-2015 LED.

(c) Pst LM ≤ 1.0 and SVM ≤ 1.6 for indoor applications per NEMA 77-2017 .

WELL Core guidance for both parts: non-leased spaces; an additional point for also meeting requirements in leased spaces. +-----------------------------------------------------------------------------+

  • | L08: WHY FLICKER IS WORTH TWICE THE POINTS |
  • | |
  • | Colour rendering (1 pt) affects how things LOOK. |
  • | Flicker (2 pt) affects the NERVOUS SYSTEM. |
  • | |
  • | Temporal light modulation -- even above the ~60-90 Hz flicker fusion |
  • | threshold where it is invisible -- is associated with headache, |
  • | eyestrain, reduced task performance, and in susceptible individuals |
  • | migraine and photosensitive seizure. It is also invisible, so occupants |
  • | cannot report the cause. |
  • | |
  • | Note WELL's phrasing: luminaires "in combination with the appropriate |
  • | CONTROLS". A low-flicker LED module on a cheap phase-cut dimmer can |
  • | flicker badly. The pair is what is tested, not the lamp alone. |
  • +-----------------------------------------------------------------------------+

Important

CRI alone is not enough at the 80 level. WELL accepts CRI ≥ 80 only when paired with R9 ≥ 50 . R9 is the saturated red test colour — the one general CRI averaging conceals, and the one that governs whether skin tones and food look healthy. A source can post CRI 82 with a badly negative R9. That pairing rule is one of the Light concept's most reliable exam items.

Tip

The circulation-area relaxation exists because corridors and stairwells are transitional: nobody performs colour-critical work there, so CRI ≥ 80 alone suffices with no R9 condition. And note the tunable white rule — compliance must be demonstrated at 1,000 K intervals across the tuning range , so a system that renders beautifully at 4,000 K but poorly at 2,700 K fails.

The three metric families you should be able to distinguish

  • Metric family What it measures Where it appears in WELL
  • UGR (Unified Glare Rating) Discomfort glare from luminaires in a space L04 (≤ 16, or ≤ 19 industrial)
  • CRI / R9 , and IES TM-30 (Rf, Rg, Rcs,h1) Colour fidelity, gamut and chroma shift L08 Part 1
  • JA-10 / IEEE 1789 / NEMA 77 (Pst LM, SVM) Temporal light modulation, i.e. flicker L08 Part 2

Add EML / M-EDI (circadian, L03), sDA (daylight, L01 and L06) and VLT (glazing transmittance, L05) and you have the complete metric vocabulary of the Light concept — six families, each attached to specific features.