3.4 Feeder Sizing, Overcurrent Protection & Voltage Drop
Wisconsin Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Wisconsin Administrative Rules, Licensing & Electrical Safety
1.1 Wisconsin Journeyman Licensing, Eligibility & Scope 1.2 Current SPS 316 Adoption, Enforcement & Wisconsin Amendments 1.3 Supplemental Job Safety: Shock, Arc-Flash & Work Practices 1.4 Electrical Theory & Mathematical Fundamentals
2 Chapter 2: General Code Rules, Definitions & Enclosure Sizing
2.1 NEC Article 100 Definitions & Article 110 General Installation Requirements 2.2 Conductor Sizing, Ampacity Ratings & Temperature Limitations 2.3 Conductor Ampacity Correction & Adjustment Calculations 2.4 Outlet Box, Device Box & Conduit Body Sizing
3 Chapter 3: Branch Circuits, Feeders & Calculations
3.1 Branch Circuit Ratings, Multiwire Circuits & General Receptacle Outlets 3.2 Wisconsin GFCI & AFCI Protection: NEC 2017-to-2023 Transition 3.3 Dwelling Branch Circuits, Receptacle Spacing & Wisconsin Countertop Rules 3.4 Feeder Sizing, Overcurrent Protection & Voltage Drop
4 Chapter 4: Services & Dwelling Load Calculations
4.1 Dwelling Unit Load Calculations: Standard Method 4.2 Dwelling Unit Load Calculations: Optional Method 4.3 Service Conductors, Disconnects & Current SPS 316.230 Amendments
5 Chapter 5: Grounding and Bonding
5.1 Grounding & Bonding Principles, Systems & Definitions 5.2 Grounding Electrode Systems & GEC Sizing 5.3 Main Bonding Jumpers & Supply-Side Bonding 5.4 Equipment Grounding Conductors & Enclosure Bonding
6 Chapter 6: Wiring Methods, Raceways & Cable Assemblies
6.1 General Wiring Rules & Underground Installations 6.2 Cable Assemblies: NM, NMC, MC, and AC 6.3 Raceways, Conduit Bending & Support Requirements 6.4 Conduit Fill Calculations & Pull Box Sizing
7 Chapter 7: Equipment for General Use: Motors, Generators & Transformers
7.1 Motor Branch Circuit Sizing & Full-Load Currents 7.2 Motor Branch-Circuit Short-Circuit & Overload Protection 7.3 Transformers & Overcurrent Protection
8 Chapter 8: General Loads & Utilization Equipment
8.1 General & Non-Dwelling Load Calculations 8.2 Luminaires, Lighting Systems & Electric Signs 8.3 Appliances, Fixed Electric Space Heating & Water Heating 8.4 Air-Conditioning & Refrigeration Equipment
9 Chapter 9: Special Occupancies & Emergency Systems
9.1 Hazardous (Classified) Locations & Commercial Applications 9.2 Health Care Facilities & Essential Electrical Systems 9.3 Pools, Spas, Hot Tubs & Fountains 9.4 Emergency Systems, Standby Power & Generators
10 Chapter 10: Modern Energy & Low-Voltage Systems
10.1 EV Charging, Photovoltaics, Energy Storage & Interconnections 10.2 Fire Alarm, Signaling & Communications Systems
11 Chapter 11: Exam Logistics & Success
11.1 Exam Logistics, Authorized References & 2026 Code Transition 11.2 Code Navigation, Time Management & Formula Review
3.4 Feeder Sizing, Overcurrent Protection & Voltage Drop
Key Takeaways Explain This Topic AI
Feeder conductors must have an ampacity not less than 100% of non-continuous loads plus 125% of continuous loads (NEC 215.2(A)(1)).
Feeder neutral sizing under NEC 220.61 permits a 70% demand factor for cooking appliances, electric clothes dryers, and the portion of linear unbalanced load exceeding 200 amperes, but derating is prohibited for nonlinear loads.
Under the next higher standard rating rule (NEC 240.4(B)), conductors with an ampacity up to 800 amperes can be protected by the next standard breaker rating in Table 240.6(A) if their ampacity does not match a standard size and the circuit does not supply multioutlet receptacle loads.
Feeder tap rules (NEC 240.21(B)) permit 10-foot taps with an ampacity of at least 1/10th and 25-foot taps with at least 1/3rd of the feeder OCPD rating, while voltage drop formulas calculate circular mils to maintain the recommended 3% branch/feeder (5% overall) thresholds.
Last updated: September 2026
3.4 Feeder Sizing, Overcurrent Protection & Voltage Drop
Feeders comprise all circuit conductors between the service equipment (or the generator/transformer source of a separately derived system) and the final branch-circuit overcurrent device. Master electrical calculations on the Wisconsin Journeyman exam require precise application of NEC Article 215 (Feeders), NEC Article 220 (Calculations), NEC Article 240 (Overcurrent Protection), and the fundamental physics of voltage drop.
1. Feeder Sizing Fundamentals (NEC 215.2)
Under NEC 215.2(A)(1) , feeder conductors must have an allowable ampacity not less than the minimum required to supply the calculated load. The general formula for determining minimum feeder conductor ampacity is: Minimum Feeder Ampacity = 1.00 × ( Non-continuous Loads ) + 1.25 × ( Continuous Loads ) \text{Minimum Feeder Ampacity} = 1.00 \times (\text{Non-continuous Loads}) + 1.25 \times (\text{Continuous Loads}) Minimum Feeder Ampacity = 1.00 × ( Non-continuous Loads ) + 1.25 × ( Continuous Loads )
A continuous load is defined in NEC Article 100 as a load where the maximum current is expected to continue for 3 hours or more (e.g., commercial retail lighting, office fluorescent/LED banks, space heating, and water heating). Non-continuous loads operate intermittently.
Worked Example: Commercial Feeder Sizing
An electrical feeder supplies a subpanel in a commercial office building with the following balanced 208Y/120V loads:
- Non-continuous receptacle and office equipment load: 45 amperes
- Continuous general office lighting load: 80 amperes
Calculate the minimum conductor ampacity: Minimum Ampacity = 45 A + ( 1.25 × 80 A ) = 45 A + 100 A = 145 Amperes \text{Minimum Ampacity} = 45\text{ A} + (1.25 \times 80\text{ A}) = 45\text{ A} + 100\text{ A} = 145\text{ Amperes} Minimum Ampacity = 45 A + ( 1.25 × 80 A ) = 45 A + 100 A = 145 Amperes
Conductor Selection from NEC Table 310.16 (75°C Copper THHN):
- 1 AWG Copper = 130 Amperes (Insufficient: 130 A < 145 A 130\text{ A} < 145\text{ A} 130 A < 145 A )
- 1/0 AWG Copper = 150 Amperes (Compliant: 150 A ≥ 145 A 150\text{ A} \ge 145\text{ A} 150 A ≥ 145 A )
- 2. Feeder Neutral Sizing & Reductions (NEC 220.61)
The feeder neutral conductor must be sized to carry the maximum unbalanced load determined between the neutral and any one ungrounded conductor under NEC 220.61(A) .
Permitted Neutral Reductions (NEC 220.61(B))
To reflect practical diversity in load usage, the code permits specific demand factors when calculating feeder neutral conductors:
Cooking Appliances & Dryers : A demand factor of 70% (0.70) is permitted for the neutral load of electric ranges, wall ovens, counter-mounted cooking units, and electric clothes dryers.
Neutral Loads Over 200 Amperes : For feeders supplying 3-wire single-phase or 4-wire three-phase systems, that portion of the unbalanced neutral load in excess of 200 amperes is permitted to be reduced by a 70% demand factor :
First 200 Amperes of neutral load: Calculated at 100% (200 A).
Portion over 200 Amperes: Calculated at 70% (0.70).
Worked Example: Feeder Neutral Derating Over 200A
A multi-family residential building feeder has a calculated maximum linear unbalanced neutral load of 360 amperes .
First 200 amperes @ 100%: 200 A × 1.00 = 200 Amperes 200\text{ A} \times 1.00 = 200\text{ Amperes} 200 A × 1.00 = 200 Amperes
Portion exceeding 200 amperes: 360 A − 200 A = 160 Amperes 360\text{ A} - 200\text{ A} = 160\text{ Amperes} 360 A − 200 A = 160 Amperes
Apply 70% demand factor to excess: 160 A × 0.70 = 112 Amperes 160\text{ A} \times 0.70 = 112\text{ Amperes} 160 A × 0.70 = 112 Amperes
Total minimum neutral ampacity: Neutral Ampacity = 200 A + 112 A = 312 Amperes \text{Neutral Ampacity} = 200\text{ A} + 112\text{ A} = 312\text{ Amperes} Neutral Ampacity = 200 A + 112 A = 312 Amperes
Prohibited Neutral Reductions (NEC 220.61(C))
Reductions to the feeder neutral conductor are strictly prohibited under two circumstances:
Nonlinear Loads : No neutral reduction is allowed for circuits supplying electronic data processing equipment, LED electronic drivers, computers, or fluorescent lighting with electronic ballasts. These loads produce 3rd, 9th, and 15th harmonic currents ( triplen harmonics ) that do not cancel in the neutral but add arithmetically, causing neutral current to exceed phase current.
3-Wire from 4-Wire, 3-Phase Systems : Where a 3-wire circuit is derived from a 4-wire, 3-phase wye-connected system (consisting of two phase conductors and the neutral), the common neutral carries approximately the same current as the phase conductors and cannot be reduced.
- 3. Overcurrent Protection & The Next Higher Standard Rating (NEC 240)
- Standard Overcurrent Device Ratings (NEC Table 240.6(A))
Journeyman candidates must memorize the standard ampere ratings for fuses and fixed-trip inverse-time circuit breakers: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100,
- 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500,
- 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000
- The "Next Higher Standard Rating" Rule (NEC 240.4(B))
Where the allowable ampacity of a conductor does not correspond to a standard ampere rating in Table 240.6(A), the next higher standard rating OCPD is permitted to protect the conductor, provided ALL THREE of the following conditions are met:
The conductors being protected are not part of a multioutlet branch circuit supplying receptacles for cord-and-plug-connected portable loads.
The ampacity of the conductors does not correspond to a standard rating in Table 240.6(A).
The next higher standard rating selected does not exceed 800 amperes .
Warning
The 800-Ampere Ceiling (NEC 240.4(C)) : If a conductor's ampacity exceeds 800 amperes and does not correspond to a standard rating, you cannot round up . The overcurrent device rating must be rounded DOWN to a standard rating equal to or less than the conductor ampacity!
4. Feeder Tap Rules (NEC 240.21(B))
As a foundational rule under NEC 240.21 , overcurrent protection must be provided at the point where conductors receive their supply. Feeder taps represent specific exceptions permitting smaller tap conductors to be connected to a larger feeder without overcurrent protection at the tap point:
Tap Rule Maximum Length Minimum Ampacity Requirement Termination Requirement Physical Protection
10-Foot Tap (240.21(B)(1)) 10 feet (3.0 m) Not less than computed load; not less than 1/10 (10%) of feeder OCPD rating Terminates in a single OCPD or equipment rated at tap ampacity Enclosed in approved raceway
25-Foot Tap (240.21(B)(2)) 25 feet (7.5 m) Not less than 1/3 (33.3%) of feeder OCPD rating Terminates in a single circuit breaker or set of fuses limiting load Protected from physical damage in raceway
Outside Feeder Tap (240.21(B)(5)) Unlimited (outside) Sized per Article 215 loads Terminates in a single OCPD disconnecting means Protected from physical damage
Caution
No Taps of Taps : You can never tap a tap conductor. An electrical tap must originate directly from a feeder protected by an overcurrent device.
5. Voltage Drop Calculations & Formulas
While the National Electrical Code does not make voltage drop limits strictly mandatory in Article 210/215 text, Informational Note No. 2 to NEC 210.19(A) and Informational Note No. 2 to NEC 215.2(A)(1) establish design recommendations for operational efficiency and equipment longevity:
Branch Circuit Voltage Drop : Maximum 3% .
Feeder Voltage Drop : Maximum 3% .
Total Combined Voltage Drop : Maximum 5% from the service disconnect to the farthest outlet.
The Ohmic Formulas for Voltage Drop Single-Phase Voltage Drop: V D = 2 × K × I × L C M \text{Single-Phase Voltage Drop: } VD = \frac{2 \times K \times I \times L}{CM} Single-Phase Voltage Drop: V D = CM 2 × K × I × L Three-Phase Voltage Drop: V D = 3 × K × I × L C M = 1.732 × K × I × L C M \text{Three-Phase Voltage Drop: } VD = \frac{\sqrt{3} \times K \times I \times L}{CM} = \frac{1.732 \times K \times I \times L}{CM} Three-Phase Voltage Drop: V D = CM 3 × K × I × L = CM 1.732 × K × I × L
To solve for the required conductor cross-sectional area in Circular Mils (CM) to satisfy a target voltage drop limit: C M Single-Phase = 2 × K × I × L V D allowed CM_{\text{Single-Phase}} = \frac{2 \times K \times I \times L}{VD_{\text{allowed}}} C M Single-Phase = V D allowed 2 × K × I × L C M Three-Phase = 1.732 × K × I × L V D allowed CM_{\text{Three-Phase}} = \frac{1.732 \times K \times I \times L}{VD_{\text{allowed}}} C M Three-Phase = V D allowed 1.732 × K × I × L
Formula Variables Defined:
K K K (Resistivity Constant) : Specific resistance of conductor material in ohms-circular mil per foot at 75°C:
- Copper ( K K K ) = 12.9 Ω ⋅ cmil/ft \Omega\cdot\text{cmil/ft} Ω ⋅ cmil/ft
- Aluminum ( K K K ) = 21.2 Ω ⋅ cmil/ft \Omega\cdot\text{cmil/ft} Ω ⋅ cmil/ft
I I I : Actual circuit design current in amperes.
L L L : One-way length of circuit from source to load in feet (do NOT double L L L ; the factor of 2 in the single-phase equation already accounts for the return conductor).
C M CM CM : Conductor area in circular mils (lookup in NEC Chapter 9, Table 8 ).
V D VD V D : Allowable voltage drop in volts ( V nominal × % V D V_{\text{nominal}} \times \%VD V nominal × % V D ).
6. Step-by-Step Worked Voltage Drop Calculation
Exam Problem:
A 240-volt, single-phase subpanel feeder carries a continuous load of 40 amperes over a one-way distance of 150 feet using copper conductors. Calculate the maximum permitted voltage drop in volts for a 3% limit, determine the minimum conductor size in circular mils, and select the appropriate conductor from NEC Chapter 9, Table 8.
Step 1: Calculate Maximum Permissible Voltage Drop ( V D VD V D ) V D allowed = 240 Volts × 0.03 = 7.2 Volts VD_{\text{allowed}} = 240\text{ Volts} \times 0.03 = 7.2\text{ Volts} V D allowed = 240 Volts × 0.03 = 7.2 Volts
Step 2: Calculate Required Circular Mils ( C M CM CM )
Using K = 12.9 K = 12.9 K = 12.9 , I = 40 A I = 40\text{ A} I = 40 A , L = 150 ft L = 150\text{ ft} L = 150 ft , and V D = 7.2 V VD = 7.2\text{ V} V D = 7.2 V : C M = 2 × K × I × L V D allowed CM = \frac{2 \times K \times I \times L}{VD_{\text{allowed}}} CM = V D allowed 2 × K × I × L C M = 2 × 12.9 × 40 × 150 7.2 CM = \frac{2 \times 12.9 \times 40 \times 150}{7.2} CM = 7.2 2 × 12.9 × 40 × 150 C M = 154 , 800 7.2 = 21 , 500 Circular Mils CM = \frac{154,800}{7.2} = 21,500\text{ Circular Mils} CM = 7.2 154 , 800 = 21 , 500 Circular Mils
Step 3: Conductor Selection from NEC Chapter 9, Table 8
Examine the Conductor Properties table for uncoated copper:
8 AWG Copper : 16 , 510 CM 16,510\text{ CM} 16 , 510 CM ( 16 , 510 < 21 , 500 16,510 < 21,500 16 , 510 < 21 , 500 — violates 3% limit)
6 AWG Copper : 26 , 240 CM 26,240\text{ CM} 26 , 240 CM ( 26 , 240 > 21 , 500 26,240 > 21,500 26 , 240 > 21 , 500 — compliant!)
Answer: Select 6 AWG Copper conductors.
Common Exam Traps & Pitfalls
Doubling the Distance in Voltage Drop : The single-phase formula ( 2 × K × I × L 2 \times K \times I \times L 2 × K × I × L ) already includes the factor of 2. Doubling the distance manually produces a 4x conductor over-sizing error.
Single-Phase vs. Three-Phase Constant : Using 2 for a three-phase calculation instead of 1.732 1.732 1.732 ( 3 \sqrt{3} 3 ) will yield incorrect circular mil values on exam calculation items.
800A Round-Up Boundary : Remembering that NEC 240.4(B) allows rounding up to the next standard breaker ONLY up to 800A. At 801A or above, you must round DOWN per NEC 240.4(C).
Feeder Tap Rules : Attempting to use the 10-foot tap rule with conductors rated at less than 10% of the feeder breaker, or the 25-foot tap rule with conductors rated at less than 33.3% of the feeder breaker.