Study guide

8.1 General & Non-Dwelling Load Calculations

Wisconsin Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Wisconsin Administrative Rules, Licensing & Electrical Safety

1.1 Wisconsin Journeyman Licensing, Eligibility & Scope 1.2 Current SPS 316 Adoption, Enforcement & Wisconsin Amendments 1.3 Supplemental Job Safety: Shock, Arc-Flash & Work Practices 1.4 Electrical Theory & Mathematical Fundamentals

2 Chapter 2: General Code Rules, Definitions & Enclosure Sizing

2.1 NEC Article 100 Definitions & Article 110 General Installation Requirements 2.2 Conductor Sizing, Ampacity Ratings & Temperature Limitations 2.3 Conductor Ampacity Correction & Adjustment Calculations 2.4 Outlet Box, Device Box & Conduit Body Sizing

3 Chapter 3: Branch Circuits, Feeders & Calculations

3.1 Branch Circuit Ratings, Multiwire Circuits & General Receptacle Outlets 3.2 Wisconsin GFCI & AFCI Protection: NEC 2017-to-2023 Transition 3.3 Dwelling Branch Circuits, Receptacle Spacing & Wisconsin Countertop Rules 3.4 Feeder Sizing, Overcurrent Protection & Voltage Drop

4 Chapter 4: Services & Dwelling Load Calculations

4.1 Dwelling Unit Load Calculations: Standard Method 4.2 Dwelling Unit Load Calculations: Optional Method 4.3 Service Conductors, Disconnects & Current SPS 316.230 Amendments

5 Chapter 5: Grounding and Bonding

5.1 Grounding & Bonding Principles, Systems & Definitions 5.2 Grounding Electrode Systems & GEC Sizing 5.3 Main Bonding Jumpers & Supply-Side Bonding 5.4 Equipment Grounding Conductors & Enclosure Bonding

6 Chapter 6: Wiring Methods, Raceways & Cable Assemblies

6.1 General Wiring Rules & Underground Installations 6.2 Cable Assemblies: NM, NMC, MC, and AC 6.3 Raceways, Conduit Bending & Support Requirements 6.4 Conduit Fill Calculations & Pull Box Sizing

7 Chapter 7: Equipment for General Use: Motors, Generators & Transformers

7.1 Motor Branch Circuit Sizing & Full-Load Currents 7.2 Motor Branch-Circuit Short-Circuit & Overload Protection 7.3 Transformers & Overcurrent Protection

8 Chapter 8: General Loads & Utilization Equipment

8.1 General & Non-Dwelling Load Calculations 8.2 Luminaires, Lighting Systems & Electric Signs 8.3 Appliances, Fixed Electric Space Heating & Water Heating 8.4 Air-Conditioning & Refrigeration Equipment

9 Chapter 9: Special Occupancies & Emergency Systems

9.1 Hazardous (Classified) Locations & Commercial Applications 9.2 Health Care Facilities & Essential Electrical Systems 9.3 Pools, Spas, Hot Tubs & Fountains 9.4 Emergency Systems, Standby Power & Generators

10 Chapter 10: Modern Energy & Low-Voltage Systems

10.1 EV Charging, Photovoltaics, Energy Storage & Interconnections 10.2 Fire Alarm, Signaling & Communications Systems

11 Chapter 11: Exam Logistics & Success

11.1 Exam Logistics, Authorized References & 2026 Code Transition 11.2 Code Navigation, Time Management & Formula Review

8.1 General & Non-Dwelling Load Calculations

Key Takeaways Explain This Topic AI

A load calculation begins by classifying each load, applying the correct unit load or nameplate value, and separating continuous from noncontinuous load.

Feeder and service calculations may apply demand factors only where the assigned NEC expressly permits them; demand factor and load factor are not interchangeable.

General-use receptacle loads in non-dwelling occupancies are calculated from the outlet count or specified VA and then receive only the demand treatment permitted for that occupancy.

Show windows, track lighting, signs, multioutlet assemblies, motors, and HVAC have specific calculation rules and should not be buried in a generic lighting total.

Three-phase current calculations use VA divided by line voltage times √3; keep units and phase configuration visible throughout the solution.

Last updated: September 2026

8.1 General & Non-Dwelling Load Calculations

Commercial calculation questions are easiest when treated as an accounting problem. List every load, identify the controlling rule, convert each to volt-amperes, apply only authorized demand factors, and then convert the final VA to current. Skipping the classification step is the usual reason a calculation goes wrong.

Connected load, demand, and conductor sizing

Connected load is the sum before permitted diversity. A demand factor reduces a specified group only where the NEC authorizes it. A continuous load is one expected to run at maximum current for the defined duration; branch-circuit and feeder conductors and overcurrent devices generally account for continuous load at 125%, subject to equipment listing and specific rules.

Do not apply a demand factor merely because loads are unlikely to operate together. Use a noncoincident-load provision only when its conditions are met. Likewise, do not multiply an already demand-adjusted value again unless the code directs that sequence.

Lighting loads

For a specified occupancy, use the general-lighting unit load and floor-area method in the assigned NEC edition. Article 220 was reorganized between editions, so locate the current table rather than assuming a 2017 number. Include the floor area defined by the code and Wisconsin SPS 316.220 where that state definition applies.

Continuous-load treatment for lighting depends on the type and use. A calculation problem may state that lighting is continuous or may place it in an occupancy where the applicable rule establishes that treatment. Keep the base VA and the 125% sizing value in separate columns so you do not confuse calculation demand with conductor sizing.

Show-window lighting uses the specific linear-foot or outlet rule in Article 220. Track lighting uses the load assigned per unit length unless the track is supplied through a listed current-limiting device under the applicable provision. Electric signs and outline lighting have their own minimum branch-circuit and feeder treatment. These loads should be itemized.

Receptacle loads

For non-dwelling general-use receptacles, calculate the load by the VA assigned per single or multiple receptacle on one yoke, or by the rule for a multioutlet assembly. After obtaining the connected receptacle VA, apply a receptacle demand factor only when the assigned table and occupancy permit it.

For example, a bank or office calculation may permit a demand treatment for a sufficiently large receptacle total, but a small group below the threshold remains at 100%. A receptacle intended for a specific appliance may be calculated from that appliance rather than being counted as an ordinary general-use outlet. Read the stem carefully.

Equipment and motor loads

Fixed appliances, commercial cooking equipment, elevators, welders, EV charging, and other equipment each have article-specific rules. Begin with nameplate ratings unless the code supplies another method. Motors require the Article 430 table current for conductor and short-circuit calculations in the situations covered there, and a feeder serving multiple motors adds 25% of the highest motor load to the sum of the others.

Heating and cooling may be noncoincident, but ventilation, pumps, crankcase heaters, or other components may operate with either mode. Drop only the portion that truly cannot operate at the same time.

Single-phase and three-phase conversion

For unity-power-factor apparent power: I 1 ϕ = V A V I_{1\phi}=\frac{VA}{V} I 1 ϕ ​ = V V A ​ I 3 ϕ = V A 3 × V I_{3\phi}=\frac{VA}{\sqrt{3}\times V} I 3 ϕ ​ = 3 ​ × V V A ​

For real power, include efficiency and power factor when the problem provides them and the requested quantity requires them. Never divide three-phase VA by voltage alone; that omission overstates current by a factor of √3.

Example

A 208V, three-phase feeder has 24,000 VA of calculated lighting and receptacle load, 18,000 VA of noncontinuous equipment, and 12,000 VA of continuous load after all permitted demand factors. The sizing total is: 24 , 000 + 18 , 000 + ( 12 , 000 × 1.25 ) = 57 , 000 VA 24,000+18,000+(12,000\times1.25)=57,000\text{ VA} 24 , 000 + 18 , 000 + ( 12 , 000 × 1.25 ) = 57 , 000 VA I = 57 , 000 1.732 × 208 = 158.3 A I=\frac{57,000}{1.732\times208}=158.3\text{ A} I = 1.732 × 208 57 , 000 ​ = 158.3 A

The calculation current is not the end of the design. Select conductors, overcurrent protection, and equipment with adequate ratings, apply terminal temperature limits and adjustment factors, and verify any standard-size or next-size permissions.

Exam worksheet

Build the worksheet in this order:

List the description and controlling code rule .

Enter connected VA and the permitted demand factor .

Apply the continuous-load multiplier where required.

Sum the final calculated VA only after every row is classified. This method also exposes missing loads: if the problem mentions a sign, track, motor, or show window and no row exists for it, the calculation is incomplete.