Study guide
1.2 Current SPS 316 Adoption, Enforcement & Wisconsin Amendments
Wisconsin Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Wisconsin Administrative Rules, Licensing & Electrical Safety
1.1 Wisconsin Journeyman Licensing, Eligibility & Scope 1.2 Current SPS 316 Adoption, Enforcement & Wisconsin Amendments 1.3 Supplemental Job Safety: Shock, Arc-Flash & Work Practices 1.4 Electrical Theory & Mathematical Fundamentals
2 Chapter 2: General Code Rules, Definitions & Enclosure Sizing
2.1 NEC Article 100 Definitions & Article 110 General Installation Requirements 2.2 Conductor Sizing, Ampacity Ratings & Temperature Limitations 2.3 Conductor Ampacity Correction & Adjustment Calculations 2.4 Outlet Box, Device Box & Conduit Body Sizing
3 Chapter 3: Branch Circuits, Feeders & Calculations
3.1 Branch Circuit Ratings, Multiwire Circuits & General Receptacle Outlets 3.2 Wisconsin GFCI & AFCI Protection: NEC 2017-to-2023 Transition 3.3 Dwelling Branch Circuits, Receptacle Spacing & Wisconsin Countertop Rules 3.4 Feeder Sizing, Overcurrent Protection & Voltage Drop
4 Chapter 4: Services & Dwelling Load Calculations
4.1 Dwelling Unit Load Calculations: Standard Method 4.2 Dwelling Unit Load Calculations: Optional Method 4.3 Service Conductors, Disconnects & Current SPS 316.230 Amendments
5 Chapter 5: Grounding and Bonding
5.1 Grounding & Bonding Principles, Systems & Definitions 5.2 Grounding Electrode Systems & GEC Sizing 5.3 Main Bonding Jumpers & Supply-Side Bonding 5.4 Equipment Grounding Conductors & Enclosure Bonding
6 Chapter 6: Wiring Methods, Raceways & Cable Assemblies
6.1 General Wiring Rules & Underground Installations 6.2 Cable Assemblies: NM, NMC, MC, and AC 6.3 Raceways, Conduit Bending & Support Requirements 6.4 Conduit Fill Calculations & Pull Box Sizing
7 Chapter 7: Equipment for General Use: Motors, Generators & Transformers
7.1 Motor Branch Circuit Sizing & Full-Load Currents 7.2 Motor Branch-Circuit Short-Circuit & Overload Protection 7.3 Transformers & Overcurrent Protection
8 Chapter 8: General Loads & Utilization Equipment
8.1 General & Non-Dwelling Load Calculations 8.2 Luminaires, Lighting Systems & Electric Signs 8.3 Appliances, Fixed Electric Space Heating & Water Heating 8.4 Air-Conditioning & Refrigeration Equipment
9 Chapter 9: Special Occupancies & Emergency Systems
9.1 Hazardous (Classified) Locations & Commercial Applications 9.2 Health Care Facilities & Essential Electrical Systems 9.3 Pools, Spas, Hot Tubs & Fountains 9.4 Emergency Systems, Standby Power & Generators
10 Chapter 10: Modern Energy & Low-Voltage Systems
10.1 EV Charging, Photovoltaics, Energy Storage & Interconnections 10.2 Fire Alarm, Signaling & Communications Systems
11 Chapter 11: Exam Logistics & Success
11.1 Exam Logistics, Authorized References & 2026 Code Transition 11.2 Code Navigation, Time Management & Formula Review
1.2 Current SPS 316 Adoption, Enforcement & Wisconsin Amendments
Key Takeaways Explain This Topic AI
Wisconsin SPS 316 now adopts the 2023 NEC for state electrical-code administration, but DSPS continues to test from the 2017 NEC through September 30, 2026 and changes the exam reference to the 2023 NEC on October 1, 2026.
SPS 316 can substitute text, omit a national NEC requirement, or add a Wisconsin rule; the state amendment controls whenever it changes the adopted NEC.
The 2026 rule adds permit rules for covered work on vacant land or structures and requires municipal electrical-inspection records to be retained for 7 years after completion.
High-yield current amendments include Wisconsin-specific GFCI/AFCI and island-receptacle rules, an 8-foot inside limit for certain feeder/service conductors, outside-disconnect location limits, mandatory supplementation of a single rod/pipe/plate electrode, and omission of NEC 225.41 and 230.85.
DSPS does not publish percentage weights for the journeyman exam; the official scope is the authorized SPS 305, SPS 316, and NEC reference set.
Last updated: September 2026
1.2 Current SPS 316 Adoption, Enforcement & Wisconsin Amendments
The National Electrical Code becomes enforceable in Wisconsin only through state adoption. SPS 316 incorporates an NEC edition and then changes selected provisions. A Wisconsin answer therefore has two layers: first find the national rule, then determine whether SPS 316 substitutes, excludes, or supplements it.
Code edition versus exam edition
Wisconsin's 2026 SPS 316 rule adopts the 2023 NEC for state code administration. The examination calendar has a short transition lag: the DSPS Journeyman Electrician exam page authorizes the 2017 NEC through September 30, 2026 and the 2023 NEC beginning October 1, 2026 .
This distinction is essential:
On a job, determine which code applies to the installation, permit, and jurisdiction.
On the exam, use the code edition and SPS material on the DSPS reference list for the scheduled date.
Do not answer a pre-October exam question from an unapproved 2023 book, and do not prepare for an October-or-later exam as though Wisconsin still tests only the 2017 edition.
How an amendment operates
SPS 316 uses three common mechanisms:
Substitution: Wisconsin replaces national wording. Apply the state text, not both rules at once.
Exclusion: Wisconsin says a cited NEC requirement is not included. Do not enforce that omitted national provision as part of SPS 316.
Addition: Wisconsin adds a state requirement alongside the adopted NEC.
Exam stems often turn on the mechanism. Highlight words such as “substitute,” “not included,” and “in addition to” in the bound SPS 316 reference.
Administration, permits, and records
The Authority Having Jurisdiction may be DSPS or a municipality exercising the applicable inspection authority. Verify the permit and inspection office for the actual location; do not assume every project is handled by the same state office.
The current rule addresses electrical work on vacant land and on or within structures and adds targeted permit rules. It also requires municipal electrical-inspection records to be retained for 7 years after completion ; state-contracted inspectors follow the record provisions in the contract that applied when the inspection was completed.
SPS 316 also defines the AHJ for its administration and retains the variance process. A variance or special permission is formal approval, not a field electrician's personal judgment that an alternative is “equivalent.” Listed or labeled equipment is installed and used according to its instructions unless those instructions conflict with the Wisconsin code.
High-yield 2026 amendment map
Use this map as an index, then read the actual section:
Wisconsin section Exam-facing effect
SPS 316.210 Substitutes the dwelling GFCI scope, omits selected 2023 GFCI/AFCI provisions, and replaces the island/peninsula receptacle rule.
SPS 316.220 Defines dwelling floor area for load calculations and excludes open porches, garages, and unfinished areas not adaptable to future habitable or occupiable use.
SPS 316.225 Limits certain feeder/branch-circuit wiring to 8 feet inside before the disconnect; an outside disconnect must be within sight and no more than 30 feet from the served structure; NEC 225.41 is omitted.
SPS 316.230 Applies the corresponding 8-foot service-conductor rule and outside-disconnect location; NEC 230.85 is omitted.
SPS 316.250 Requires a single rod, pipe, or plate electrode to be augmented and contains Wisconsin grounding/bonding amendments.
Other amendments remain important. Use the table of contents and index in the current SPS 316 rather than assuming this high-yield list is exhaustive.
Avoid obsolete Wisconsin rules
The 2026 final order repealed several prior provisions, including older text in SPS 316.230 and the former state sections across parts of Articles 511 through 701. That means a familiar rule from an old Wisconsin handout may no longer exist as a state amendment. For example, current SPS 316 omits the national dwelling emergency-disconnect mandate in NEC 230.85; an old “Wisconsin cold-sequence” study note is not a substitute for current section text.
Blueprint and study method
DSPS publishes authorized references and logistics, but it does not publish a percentage-weighted journeyman content outline. Treat any neat five-domain percentage chart as a study organizer, not an official weighting.
For each practice problem, write three labels: NEC edition , NEC section , and SPS effect . If the state section says “not included,” stop applying that national paragraph. If it substitutes wording, solve from the substituted text. This habit is more reliable than memorizing an unsourced list of “Wisconsin exceptions.”