1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22)

Wisconsin Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Licensing, Exam Rules & Code Administration

1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards

2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)

2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers

3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)

3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses

4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices

4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)

5 Chapter 5: Water Supply Systems (SPS 382.40)

5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks

6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)

6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration

7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)

7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances

8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)

8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)

9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)

9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment

10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping

10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers

11 Chapter 11: Special Plumbing Installations & Water Reuse

11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration

1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22)

Key Takeaways Explain This Topic AI

Drain and vent systems are tested with water (no section under a 10-foot head, held 15 minutes) or air (5 psi or 10 inches of mercury, held 15 minutes without adding air).

Sanitary building sewers are tested with a 10-foot water head for 15 minutes or 3 psi of air for 15 minutes; storm building sewers need no field test.

Water distribution piping, water services and private water mains are proved watertight under water pressure not less than the working pressure, using potable water.

If the inspector does not inspect by the end of the next business day after notice, the plumber may proceed with testing and installation.

A required final test uses smoke or air at a pressure equal to 1 inch of water column; the air version must hold for 5 minutes.

Last updated: October 2026

When testing is required (SPS 382.21 (1))

All new plumbing, and every part of an existing system that is altered, extended or repaired, must be tested and inspected before being put into operation . Exceptions:

No test is needed if the work adds, replaces, alters or relocates no water distribution, drain or vent piping. A direct fixture swap is an example.

Storm building sewers and storm private interceptor main sewers need no field test , but their joints must meet SPS 384.40 (1) (a).

Inspection procedure (SPS 382.21 (1) (b))

  • Step Rule
  • Notice The plumber responsible notifies the inspector in person, by phone or in writing when work is ready

If the inspector doesn't come If the inspection isn't made by the end of the normal business day following the day of notification (excluding weekends and legal holidays), the plumber may proceed with testing and installation

Self-test option Testing may be done without the inspector if the master plumber gets permission to submit a written test report in a format the inspector accepts

Preparation The plumber provides access to all parts, the test apparatus and assistance

Rough-in inspection Made when the system is roughed in and before fixtures are set; no work closed in until approved

  • Final inspection Made on completion, before final approval
  • Reinspection Corrections are made and the work resubmitted

One- and 2-family dwellings are inspected under SPS 320.08 to 320.11. The initial test of a backflow assembly follows SPS 382.22 (8) (section 6.3). The plumber furnishes all equipment, material and labor for tests, and covered work must be exposed for testing.

Test methods (SPS 382.21 (2))

System Water test Air test

Drain and vent systems (including conductors), and building drains brought to grade Fill to overflow, or test in sections; no section under a 10-foot head , and the upper 10 ft of each preceding section retested; hold 15 minutes before inspection 5 psi gauge pressure, or enough to balance 10 inches of mercury , held 15 minutes without adding air

Sanitary building sewer and sanitary private interceptor main sewer (before or after covering; manholes excluded) Plug at the public sewer, fill to at least a 10-foot head , no drop for 15 minutes 3 psi , held 15 minutes without adding air

Private water mains and water services Inspect before covering; prove watertight under water pressure not less than the working pressure , potable water -

Water distribution system Prove watertight under water pressure not less than the working pressure , potable water -

Note

NFPA 24 may impose more stringent tests on combination water services and private mains that also feed fire protection (section 5.5).

Pressure check. A 10-foot water column exerts about 10 x 0.433 = 4.3 psi at its base, which is why the air test for drain and vent piping is set at 5 psi. When testing a 3-story stack in sections, each lower section must also retest the bottom 10 feet of the section above.

Final test (SPS 382.21 (2) (h))

Where the local inspector or municipality requires it, after fixtures are set and traps filled:

Smoke test : pungent, thick smoke from smoke machines; when it appears at roof openings, close them and hold 1 inch of water column during the inspection.

Air test : add air until the system holds 1 inch of water column , constant for at least 5 minutes without adding air.

The plumbing code does not include a peppermint test.

Maintenance and repairs (SPS 382.22)

The owner maintains plumbing in a safe, sanitary condition, with required devices in working order.

Existing systems may stay if maintained per their original design and installed under the code in effect then, or if they meet the current code. A system that creates a hazard must be repaired or replaced, or brought up to the current code on the authority's schedule. DSPS considers a cross connection a health hazard.

An existing sewer or water service may serve a new building only after examination and testing show it conforms.

Replacement fixtures, appliances or pipe must meet the current code. Where old drain or vent piping doesn't comply, DSPS may require deep-seal traps on the new fixtures.

Reused materials need approval from DSPS or the local inspector plus the owner's written consent. Water supply piping may be reused only for an equal or higher hazard use.

Repairs must meet the code. Repair clamps or bands are allowed only in emergencies .

Demolition : seal and plug all sanitary, storm and water connections safely.

Dead ends created by removing drain piping are sealed per SPS 384.40.

Worked scenario

A plumber roughs in a 2-story addition on Monday morning and calls the inspector. If no inspector arrives by the end of Tuesday (the next business day), the plumber may test and continue. Before Monday's call, the plumber should already have:

  • capped and filled the DWV to the roof with water (10-foot sections at minimum), or charged it to 5 psi of air
  • pressurized the new water piping with potable water to at least working pressure
  • kept the new building sewer uncovered or ready for a 10-foot head or 3 psi air test

Loading diagram... Testing a new installation