Study guide
9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment
Wisconsin Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Licensing, Exam Rules & Code Administration
1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards
2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)
2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers
3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)
3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses
4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices
4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)
5 Chapter 5: Water Supply Systems (SPS 382.40)
5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks
6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)
6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration
7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)
7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances
8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)
8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)
9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)
9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment
10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping
10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers
11 Chapter 11: Special Plumbing Installations & Water Reuse
11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration
9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment
Key Takeaways Explain This Topic AI
Table 383.43-1 places soil dispersal components at least 10 feet from buildings, 5 feet from property lines, 15 feet from pools and 50 feet from navigable waters, and treatment or holding tanks at least 5 feet from buildings.
NR 812.08 sets well separations of 25 feet to septic and holding tanks and 50 feet to dispersal components under 12,000 gpd (250 feet at 12,000 gpd or more).
Inspection, evaluation, maintenance and servicing reports go to the governmental unit within 30 days, and the governmental unit keeps them at least 6 years.
Pre-July 2000 POWTS with in situ soil components must be visually inspected for surface ponding at least every 3 years, by a plumber, POWTS inspector, septage operator or POWTS maintainer.
Abandoned tanks and pits are disconnected, have their piping sealed, are pumped, and are removed or have their covers removed and are filled with soil, gravel or inert solid material.
Last updated: October 2026
Setbacks (SPS 383.43 (8) (i) and Table 383.43-1)
Physical feature Soil treatment or dispersal component Exterior subsurface treatment tank or holding tank Forcemains, service suction and pump discharge lines
- Building 10 ft 5 ft (except RV transfer tanks) None (access permitting)
- Property line 5 ft 2 ft 2 ft
- Swimming pool 15 ft None None
- Ordinary high-water mark of navigable waters 50 ft 10 ft 10 ft
- Water service and private water main 10 ft 10 ft 5 ft
- Public water main Per NR 811 Per NR 811 Per NR 811
- Well Per NR 811 and 812 Per NR 811 and 812 Per NR 811 and 812
Road right-of-way lines may be more restrictive than property lines, and WisDOT has its own highway setbacks.
Well separation (NR 812.08, Table A, selected). NR 812 is DNR's well code. It is not on the exam's reference list, but the plumbing code points to it for every well setback:
- Source Minimum distance to a well
- POWTS treatment component (septic tank, aerobic unit, filter) 25 ft
- POWTS holding tank 25 ft
- POWTS dispersal component under 12,000 gpd 50 ft (200 ft for school wells)
- POWTS dispersal component 12,000 gpd or more 250 ft
- Grease interceptor (buried) 25 ft
- Sanitary building sewer 8 ft
- Sanitary collector sewer 25 ft
- Pit privy / vault privy 50 ft / 25 ft
Worked check. A mound proposed 45 feet from a private well serving a house (design flow 600 gpd) fails NR 812.08's 50-foot dispersal setback. The septic tank, 30 feet from the well, passes its 25-foot setback. The same mound must also be at least 10 feet from the house and 10 feet from the water service.
The management plan (SPS 383.54 (1))
Every POWTS has a management plan, submitted with plan review. It lists the maintenance needed to keep the system working as designed:
- Solids removal requirements
- Influent and effluent quantity and quality
- Metering and monitoring schedules
- Load and rest schedules
- Servicing frequencies
- Installation and inspection checklists
- Mechanical component schedules
- Start-up and shutdown procedures
- Abandonment procedure
Changing how the system is operated requires a written request to the agency that reviewed the plans. Metering, when required, may use event counters and elapsed-time meters, water meters on the supply, or wastewater meters.
Responsibilities (SPS 383.52 and 383.55)
Party Duty
Owner Ensures operation and maintenance per the plan, keeps access covers locked or secured, and is responsible for reporting
Owner with a plan requiring evaluation or maintenance at intervals of 12 months or less Keeps a contract with a registered POWTS maintainer
Owner with a plan requiring servicing at 12 months or less Keeps a contract with a certified septage servicing operator (NR 114)
Owner or agent Files each inspection, evaluation, maintenance or servicing report with the governmental unit within 30 calendar days (POWTS ID, location, date and the license, certification or registration number of the person)
Governmental unit Keeps records at least 6 years ; runs an inventory of all POWTS and a maintenance program that tracks reports, notifies delinquent owners and reports annually to DSPS
A POWTS not maintained per its plan, or per SPS 383.54 (4) for older systems, is considered a human health hazard . Chemical or physical restoration products may be used only if department-approved (SPS 383.53).
Older systems (SPS 383.54 (4))
POWTS existing before July 1, 2000 still follow the 1/3 sludge-and-scum and 1-foot-below-inlet servicing triggers. Those with in situ soil components must be visually inspected at least once every 3 years for effluent ponding on the ground surface. The inspection may be done by:
- a licensed master plumber or master plumber-restricted service
- a licensed journeyman plumber or journeyman plumber-restricted service
- a certified POWTS inspector
- a certified septage servicing operator
- a registered POWTS maintainer
A county with a completed inventory may extend the interval to 5 years for occasionally occupied structures.
Abandonment (SPS 383.33)
A subsurface tank or pit that is no longer used as a POWTS component must be abandoned by:
Disconnecting all piping to the tanks and pits.
Sealing all disconnected piping.
Pumping and properly disposing of the contents.
Either removing the tanks, or removing the covers and filling the tanks and pits with soil, gravel or an inert solid material.
Municipalities may require connection to an available public sewer under s. 281.45, Stats. That is the usual reason a POWTS is abandoned.
Other ch. SPS 386 and 387 items
Ch. SPS 386, under s. 30.71, Stats., regulates sewage from boats equipped with toilets: holding tanks, overboard discharge inactivation and on-shore disposal facilities. Ch. SPS 387 is the Wisconsin Fund financial assistance program for replacing or rehabilitating failing POWTS. Its printed note says the chapter is repealed effective June 30, 2021 under CR 17-065. Both chapters are in the permitted SPS 381 to 387 binder, but neither is central to journeyman installation questions.